4.4.5
Connection diagrams
+24 V DC
0 V
F0
k2
k3
k1
E311016/00/2021-04-30
State
2
4
1
3
RE13
X1
Y1
Y2
24
X2
A2
14
34
I1
I2
S1
A1
23
33
13
RLY3-MULT1
CMSS
EMSS
Auto
Manual
Slow SCSD
Fast SCSD
SMAT
OSSD
1
0
F2 F1
F3
K3
K2
K1
L+
L–
Figure 4: ReLy MULT1 connection diagram
4.5
Testing plan
The safety relay must be thoroughly checked by appropriately qualified safety personnel
during commissioning, after modifications, and at regular intervals,
The regular thorough checks serve to assess the effectiveness of the safety relay and
to identify defects as a result of modifications or other influences (e.g., damage or
manipulation).
The manufacturer and user must define the type and frequency of the thorough checks
on the machine on the basis of the application conditions and the risk assessment.
Determination of the thorough checks must be documented in a traceable manner.
4.5.1
Minimum requirements for the regular thorough check
The following thorough checks must be carried out at regular intervals:
•
Thorough check of the housing for damage
•
Thorough check of the cables for damage
•
Thorough check of the safety relay for signs of misuse or manipulation
•
Thorough check of the safety function
The required interval for performing these thorough checks depends on the applicable
safety capability of the overall application,
.
PROJECT PLANNING
4
8024307/2021-07-30 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy MULT1
15
Subject to change without notice