5.5
Wiring the interfaces
5.5.1
Wiring the digital inputs
The digital inputs can be used to start a teach-in procedure or.
Electrical values
LOW: 0 V ≤ U
e
≤ 2 V
HIGH: 10 V ≤ U
e
≤ U
V
Input, teach-in (ET)
Push/pull: Teach = HIGH; Run = LOW
Input, Trigger
Recording = HIGH; Evaluation = LOW
5.5.2
Wiring the digital outputs
Switching behavior: push/pull
Electrical values
The sum current (100 mA) for all digital outputs is identical.
Push/pull
HIGH: U
V
−3 V; LOW: ≤ 3 V
In the case of a push/pull sensor, the signal must be inverted in the control system in
order to obtain the same result as a sensor with NPN switching behavior.
Table 2: Push-Pull
PWR
Q
PWR
Q
PWR
Q
Q
push-pull
(
≤
100 mA)
+ (L+)
Q
‒ (M)
+ (L+)
Q
‒ (M)