Wiring details
Circular connector M12x1, 4-pin
Circular connector M12x1, 5-pin
2 switching outputs or
1 switching
1 analogue output
2 switching o 1 analogue output
L+ = 1
M = 3
Q1 1 = 4
C/Q1 = 4
Q2 = 2 /
Q
A
= 2
L+ = 1
M = 3
Q1 = 4
C/Q1 = 4 Q2 = 2
Q
A
= 5
Ingress Protection per
IEC 60 529
IP 67
IP 67
The ingress protection classes specified only apply while the pressure transmitter is connected
with female connectors that provide the corresponding ingress protection.
7. Starting, operation
Connect the instrument to earth via the pressure connection.
For power supply, use a circuit with energy limitation (EN/UL/IEC 61010-1, section 9.3)
with the following maximum values for the current: with L + = 35 V (DC): 4.0 A. Provide a
separate switch for the external power supply. Alternative for North America: The connec
-
tion may also be made to „Class 2 Circuits“ or „Class 2 Power Units“ according to CEC
(Canadian Electrical Code) or NEC (National Electrical Code).
Electrical connection