5.
If necessary, remove contamination from the sealing groove and the bearing sur‐
face of the safety laser scanner. Use a residue-free plastic cleaner (
6.
Check whether the mirror on the motor is dirty and, if necessary, remove dirt using
an optic brush.
7.
Set 1.0 Nm ... 1.2 Nm tightening torque on the torque wrench.
8.
During the following steps, wear the gloves supplied with the new optics cover.
9.
Take the new optics cover out of the packaging and remove the seal’s protective
cap.
10. Remove any packaging residue if necessary.
11. Carefully push the optics cover over the mirror. Make sure that the optics cover
does not touch the mirror.
12. Place the optics cover onto the safety laser scanner. Make sure that the optics
cover rests over the whole area without any gaps.
13. Screw in new fixing screws,
14. Tighten the screws using the set tightening torque.
15. Make sure that the optics cover is clear of dirt and damage.
How to recommission the safety laser scanner
1.
Properly remount the safety laser scanner,
.
2.
Reconnect all electrical connections to the safety laser scanner.
3.
Carry out the optics cover calibration,
see "Optics cover calibration", page 101
4.
Start the safety function using Safety Designer,
see "Starting and stopping safety
5.
Check the effectiveness of the protective device.
°
Generally, the protective device is checked exactly as during commissioning,
see "Check during commissioning and modifications", page 105
.
°
If, during project planning, the possible tolerances of the devices have been
considered and it is ensured that neither the configuration nor the wiring or
the alignment of the safety laser scanner have been changed, a function test
is sufficient,
see "Thorough check of the principal function of the protective
10.4
Replacing the safety laser scanner
If the safety laser scanner is damaged or defective, you must replace it.
DANGER
Hazard due to lack of effectiveness of the protective device
If an unsuitable configuration is saved in the system plug, it may cause the dangerous
state to not end in time.
b
After replacement, make sure the same system plug is used or the configuration is
restored.
b
Make sure that the safety laser scanner is aligned correctly after the replacement.
NOTICE
Enclosure rating IP65 only applies if the safety laser scanner is closed and the system
plug is mounted.
NOTICE
If the system plug is mounted with excessive force, the contacts can break or bend.
b
Plug in the system plug carefully.
b
Do not force it.
10
MAINTENANCE
112