O P E R AT I N G I N S T R U C T I O N S | L F P C U B I C
8019918/ZJA6 / 2017-07-20 | S I C K A G
Subject to change without notice
3 8
8
OPERATION
Configuration
1.
Log in to expert mode; see
.
2.
Define the parameter in the EXPRT-Pulse-MaskZn menu.
Note:
This setting can be used only in pulse mode.
8.4.5
Selection of evaluation method
You can switch between pulse mode and foam mode as an evaluation method.
Depending on the selected mode, other evaluation algorithms are used.
Configuration
1.
Log in to expert mode; see
.
2.
In the EXPRT-Config-Mode menu, select between Pulse and Foam.
The following rules apply:
•
Mode = Pulse: The sensor measures either with or without AutCal.
•
Mode = Foam: The sensor measures only with valid CalMed. If no valid
calibration is available, the CalPls message is displayed and the sensor enters
a safe state.
Note:
If AutCal is called up while the sensor is in foam mode, then AutCal is denied and
the error message !Denid is shown.
8.4.6
Testing the configuration
Testing outputs
Switching/analog outputs can be simulated. This makes it possible to check the wiring
and signal values on the connected systems, such as the PLC control, relay and lamps.
Configuration
Activate the Qx switching output
b
Set the parameter in the QxMENU-SimQx menu to QxOn.
Additional options:
•
QxOff = switching output off
•
QxNorm = switching output in measuring operation
•
QxOn = switching output is active
Note:
The simulation is automatically deactivated if the supply voltage is interrupted.