Function of switch S1
Table 43: Switch S1: Power
Switch setting
Function
ON
Supply v24 V connected to CDM420-0006 and device via fuse
as +24 V* supply voltage.
Supply v24 V* can be additionally tapped at terminals 29 and
39.
OFF
CDM420-0006 and device disconnected from supply voltage.
Recommended setting for all connection work.
13.5.4
Connecting serial host interface RS-232 of the device in CDM420-0006
Device = Lector621 ECO = V2D621x-xxxxxYx (serial variant, Y = D or E)
Device = Lector621 = V2D621x-xxxxxYx (Ethernet variant, Y = B or C)
Device
1
CDM420-0006
Host
5
.
.
.
TxD
RxD
RxD
TxD
GND
GND
GND
12
1
9
7
6
34
T
‒
/TxD
35
R
‒
/RxD
36
GND
6
Shield
RS-232
RS-232
ON
OFF
S2 : RS 485
ON
OFF
S3: Term 422
S2
OFF
ON
2
3
3
1
7
2
6
5
4
8
13
14
17
15
9
10
12
16
11
1
10
15
6
11
5
5
4
Figure 52: Connecting data interface RS-232 of the device in the connection module CDM420-0006
1
Device
2
V2D621x-xxxxxYx (serial variant, Y = D or E): connecting cable permanently connected with the device (male connector,
D-Sub-HD, 15-pin)
3
V2D621x-xxxxxYx (Ethernet variant, Y = B or C): adapter cable (male connector, D-Sub-HD, 15-pin / female connector,
M12, 17-pin, A-coded)
4
Connection module: female connector, D-Sub-HD, 15-pin
5
V2D621x-xxxxxYx (Ethernet variant, Y = B or C): male connector, M12, 17-pin, A-coded
NOTE
Activate the RS-232 data interface in the device with a configuration tool, e.g. the con‐
figuration software SOPAS ET.
13.5.5
Connecting serial host interface RS-422 of the device in CDM420-0006
ANNEX
13
8022502/15NT/2020-02-11 | SICK
O P E R A T I N G I N S T R U C T I O N S | Lector621
93
Subject to change without notice