Operating Instructions
Chapter
4
AFS60/AFM60 EtherNet/IP
51
Commissioning
Select again
New Tag
.
In the
New Tag
dialog box enter TEMP_Value in the
Name
field, select in the
Data Type
field the data type INT and click
OK
.
Finally a further variable must be defined and declared that obtains the temperature value
from the control system.
Select again
New Tag
.
In the
New Tag
dialog box enter TEMP_Message in the
Name
field, select in the
Data
Type
field the data type MESSAGE and click
OK
.
Fig. 41 shows the resulting variable structure for reading the temperature acyclically.
Fig. 39: Definition of the
variable TEMP_Value
Fig. 40: Definition of the
variable TEMP_Message