Chapter
4
Operating Instructions
AFS60/AFM60 EtherNet/IP
50
Commissioning
In the
Name
field enter TEMP_Trigger, in the
Data Type
field select the data type BOOL
and click
OK
.
To only trigger the action once, a further element, in this case an edge-sensitive element,
must be defined and declared. This element ensures that the action is only triggered if an
edge change from 0 to 1 occurs in the variable TEMP_Trigger.
Select again
New Tag
.
In the
New Tag
dialog box enter TEMP_OneShot in the
Name
field, in the
Data Type
select the data type BOOL and click
OK
.
A further variable must be added that will then contain the temperature value later (see
Tab. 19 on page 28, ID100/64h, Temperature Value).
Fig. 37: Definition of the
variable TEMP_Trigger
Fig. 38: Definition of the
variable TEMP_OneShot