8.3
Teach-in mode
The MPS-G features two teach options:
Dynamic Teach
and
Manual Teach
.
Both teach options can be executed via the teach-in button.
8.3.1
Dynamic Teach
Dynamic Teach
is used to have the sensor automatically set the end points of the desired measuring range.
The sensor detects the movement stops and then assigns the respective end points to the found positions: 0 V on
the cable side and 10 V on the side of the sensor fixing screw. (The positions must be at least 1 mm apart to be
detected as two different positions).
The initial position of the piston when
Dynamic Teach
starts is NOT seen as the first stop! The
Out-Of-Range
display is
hereby deactivated.
NOTE
The magnet must be moved at a speed greater than 0.025 m/s so the
Dynamic Teach
works correctly.