Settings for all monitoring cases
2
Settings for a single monitoring case
3
Input conditions for the monitoring case
4
Cut-off paths with the assigned field sets
5
Configured field sets
6
Areas for defined cut-off behavior
7
Remove field set from a monitoring case
Input delay (for all monitoring cases)
In the
Input delay
field, you can set a switch-on delay between 10 and 500 ms. After the
safe multibeam scanner has detected a change in input states, the inputs are ignored
for the duration of the configured switch-on delay.
Monitoring case table
You can create different monitoring cases in the monitoring case table. You have the
following options for each monitoring case:
•
Assign the cut-off paths via a field set with fields or using a predefined cut-off
behavior.
•
Activate sleep mode for the safe multibeam scanner.
Input conditions
The input conditions are only displayed if you have created at least two monitoring
cases.
CONFIGURATION
7