14
User’s Manual
Communication error counters display. If the cause of the malfunction has been removed, in
this page you can force exit from the BUS-OFF mode by holding down the
MODE
+
EXIT
buttons.
- engine diagnostic codes
, according to the SAE J1939 standard or MTU specifications. In the
case of the J1939 standard, when a signal is present the SPN and FMI fault's codes, the
number of occurrences (OC), a specific diagnostic code of the family of engines (DTC), and an
explanatory text are displayed. For MTU engines the SPN, FMI and OC are not shown, but the
DTC code and an alphanumeric description are always displayed.
The engine diagnostic codes are stored (even if the engine removes them) until the
yellow/red indicator light warning from CanBus is acknowledged with the
MODE
button.
Page
S.03
reports the status of the serial communication and
CAN
networks. In the case of
operating errors, check the information in this page. When using a
GSM
modem the phone
company and radio signal are also shown.
Page
S.04
, as well as containing some generic information, also contains information on the fuel
pump.
Page
S.05
(available only if the
DICHRON
expansion module or an external (
SYNCHRO-CHECK
)
synchroscope is installed in the system) will display a synchroscope with the main electrical
BUS
and
GENERATOR
magnitudes, the engine speed and the phase error, otherwise the external
synchroscope is powered.
Page
S.06
displays the state of the digital inputs and outputs acquired by Gen-set.
Page
S.07
displays the state of the analog inputs and outputs acquired by Gen-set.
You can scroll through the various pages using the
LEFT
and
RIGHT
buttons.
This lets you display the measurements taken by Gen-set on the electric lines.
Page
M.01
displays the electrical magnitudes of the generator.
Page
M.02
displays the electrical magnitudes of the network or bus.
Page
M.03
shows the total and phase power values, active, reactive and apparent, power factor and
energy counters of the generator.
Page
M.04
is used during synchronization. If the
DICHRON
expansion unit is connected, a
synchroscope is also shown in this page. Using the synchroscope displayed or an external
synchroscope, with the lockable selector in position
MAN
you can perform the manual
synchronization (see par. 2.6.1).
Page
M.05
shows the parameters used to monitor the parallel function. In this page you can change
the power supplied in the network parallel applications using the
BASE LOAD
and
IMPORT/EXPORT
function.
The engine related measurements are shown in this mode. The page number displayed may
depend on the type of engine (
J1939
,
MTU
or
without communication interface
).
Some parameters may only be shown for some engine models.