Communication error counters display. If the cause of the malfunction has been removed, in 

this page you can force exit from the BUS-OFF mode by holding down the 

MODE 

 + 

EXIT 

 buttons. 

- engine diagnostic codes

, according to the SAE J1939 standard or MTU specifications. In the 

case of the J1939 standard, when a signal is present the SPN and FMI fault's codes, the 
number of occurrences (OC), a specific diagnostic code of the family of engines (DTC), and an 
explanatory text are displayed. For MTU engines the SPN, FMI and OC are not shown, but the 
DTC code and an alphanumeric description are always displayed. 

The engine diagnostic codes are stored (even if the engine removes them) until the 

yellow/red indicator light warning from CanBus is acknowledged with the 

MODE 

 button.  

Page 

S.03

 reports the status of the serial communication and 

CAN

 networks. In the case of 

operating errors, check the information in this page. When using a 

GSM

 modem the phone 

company and radio signal are also shown.  

Page 

S.04

, as well as containing some generic information, also contains information on the fuel 

pump. 

Page 

S.05

 (available only if the 

DICHRON

 expansion module or an external (

SYNCHRO-CHECK

synchroscope is installed in the system) will display a synchroscope with the main electrical 

BUS 

and 

GENERATOR

 magnitudes, the engine speed and the phase error, otherwise the external 

synchroscope is powered. 

Page 

S.06

 displays the state of the digital inputs and outputs acquired by Gen-set. 

Page 

S.07

 displays the state of the analog inputs and outputs acquired by Gen-set.

 

 

 

You can scroll through the various pages using the 

LEFT

 and 

RIGHT

 buttons. 

This lets you display the measurements taken by Gen-set on the electric lines. 

 
Page 

M.01

 displays the electrical magnitudes of the generator.  

 
Page 

M.02

 displays the electrical magnitudes of the network or bus. 

Page 

M.03

 shows the total and phase power values, active, reactive and apparent, power factor and 

energy counters of the generator. 
 

Page 

M.04

 is used during synchronization. If the 

DICHRON

 expansion unit is connected, a 

synchroscope is also shown in this page. Using the synchroscope displayed or an external 
synchroscope, with the lockable selector in position 

MAN

 you can perform the manual 

synchronization (see par. 2.6.1). 

Page 

M.05

 shows the parameters used to monitor the parallel function. In this page you can change 

the power supplied in the network parallel applications using the 

BASE LOAD

 and 

IMPORT/EXPORT

 function. 

 

 

 

The engine related measurements are shown in this mode. The page number displayed may 
depend on the type of engine (

J1939

MTU

 or 

without communication interface

). 

Some parameters may only be shown for some engine models. 

Содержание DST4601/PX

Страница 1: ...Filename EAAM019704EN docx Rev 04 Date 08 05 2013 ID Document EAAM0197 Product DST4601 PX...

Страница 2: ...codes 11 2 5 1 2 Setting the parameters 12 2 5 1 3 How to input string value 13 2 5 1 4 Direct access to the previous page 13 2 5 1 5 Alarms and protection parameters 13 2 5 2 Status information S xx...

Страница 3: ...WER OFF is used to indicate a fault that prevents the generator from operating and causes the standard automatic engine shutoff including a cooling phase WARNING is used to indicate a fault that requi...

Страница 4: ...is required AUTO TEST Gen set is in automatic mode all the functions are controlled automatically The combination of the buttons START and MODE lets you activate deactivate the TEST mode the STOP but...

Страница 5: ...crease the engine speed if set to synchronized or the power supplied if in power mode ENTER Lets you enter the programming mode and open submenus change a variable and confirm the operation Furthermor...

Страница 6: ...rogramming parameters in the version with CANBUS it also lets you force the exit from BUS OFF mode START In MAN mode it is used to start the generator In AUTO mode it is used with the MODE button to e...

Страница 7: ...at a command is being sent from one of the serial ports the second serial port is managed in signalling only if configured as the COM port and not the I O expansion Indicates at least one of the two s...

Страница 8: ...open after a closing command Flashing at 75 ON if the KG is closed after an opening command Flashing at 50 in synchronization phase with BUS LIVE indicator GCB The MCB is open The MCB is closed Flashi...

Страница 9: ...ed to navigate between the modes Use the LEFT and RIGHT buttons to display the pages in the mode In some modes ex mode P xx and mode H xx to display the pages press the ENTER button and then the UP an...

Страница 10: ...rrow buttons or both indicates there are other pages which can be viewed using the relevant LEFT and RIGHT buttons E 01 ENGINE 03 04 06 18 23 Press Bar Temp C Level Oil xx x xxx x xx x Coolant xx x xx...

Страница 11: ...t only be changed by qualified personnel Parameters can be protected by password see par Access codes This mode lets you display and change the programming parameters Each programming parameter has a...

Страница 12: ...displayed press EXIT to return to the previous menu and try opening the page again The set access code remains in the memory for about 10 minutes after programming has been completed After that it mu...

Страница 13: ...exited programming This is the case if no programming operations are performed for 60 consecutive seconds or if the lockable selector is switched to MAN or AUTO Protections and alarms can generally be...

Страница 14: ...synchroscope with the main electrical BUS and GENERATOR magnitudes the engine speed and the phase error otherwise the external synchroscope is powered Page S 06 displays the state of the digital input...

Страница 15: ...s the old one so the identification number may change in time Enable the mode with the ENTER button A menu will guide you through the selection of the required function WARNING Before proceeding with...

Страница 16: ...breaker closes the speed reference is set as close as possible to the nominal value so Gen set can regulate the power properly Warning As some slow power ramps may have been set check the command aga...

Страница 17: ...set wait for a few seconds then power it up again Note in this phase do not press the STOP and START buttons Gen set implements the full management of the fuel pump to pump fuel from the storage tank...

Страница 18: ...ge with the sequence of buttons SHIFT and EXIT Pressing the sequence of buttons SHIFT and EXIT again you can change the fuel pump command from MANUAL ON pump on the pump starts and will only stop when...

Страница 19: ...the right to modify this document without prior notice SICES has made any effort to ensure that the information herein provide are correct in any case SICES does not assume any liability for the use t...

Отзывы: