 INSTALLATION 

 

 

2.a

 PUMP MODULE 

 

The power supply must come from a different network than the air conditioner supply. 

Disconnect the power supply before installation. 

The  power  cable  must  be  connected  by  a  qualified  professional  complying  with  the  standards in 
force in the country. 
Use only the cable 3 drivers supplied with a fuse calibrated on the line. 
This power supply cable must be grounded. 
(standard NFC 15100 lays down the installation of a high sensitivity differential circuit breaker for 
dwelling units  (30 m A)) 
In case of doubt and for any interventions concerning electrical connection, it is preferable to call a 
qualified professional. 
SICCOM would not be held responsible for possible damages caused by a improper installation 
 If the power cable is damaged, it should be replaced by the manufacturer, its after-sales service or 
similarly qualified persons in order to avoid any danger. 

 
 
 
 
 
 
 
 
 
 
 

 

Installation of the pump module. 

 

The pump module may be installed in the air conditioner, in a chute (see diagram, opposite) or in 
the false ceiling. A space must be left around the pump module for it to cool in the event of 
prolonged operation. The pump module should not be covered (no insulation, no expanding foam, 
etc.). The discharge tube must be 6 x 9 mm in diameter. Use the hose clamp (supplied) to securely 
fasten the discharge hose to the pump. Make sure to observe the flow direction indicated by the 
arrow on the pump module.  

 

2.b

 DETECTION MODULE.  

 

The flexible elbow (supplied) allows connection of the detection module to the air conditioner tray. 
Suction is via the 1.50-meter flexible hose having a diameter of 6 x 9 mm (no supplied).  
Use the two hose clamps (provided) to securely fasten the flexible hose to the detection and pump 
modules. 

 

Installation of the detection module. 

 

For the mini FLOWATCH ® 0, the detection module must be installed and fastened in a horizontal 
position with the velcro adhesive support (supplied). 
Link the tip of the blowhole with a tube PVC 

 6 x 9 of approximately 50 mm (no supplied). 

 

 

OPERATION 

 

Check  that  the  maximum  water  level  in  the  condensate tray is  higher  than  the  cover level  in  the 
detection unit, to prevent the condensate tray overflowing before the alarm activates. 
Before  finishing  the  installation,  it  is  requested  to  test  the  correct  operation  of  the  condensate 
removal pump. 

 

Never try to run the pump “dry” without water (pump destructive)  

  Rinse  thoroughly  the  condensate  water  tray  in  order  to  eliminate  all  metallic  particles  and 

foreign bodies 

before connecting the detection unit

.  

  Position the detection unit in order to collect the condensate from the air conditioner 

  Pour water into the condensate tray of the air conditioner without overfilling 

  Check the pump starts, pumps water, then stops  

 

 

3.a

 MAINTENANCE. 

 

Any  maintenance  on  the  condensate  pump 

MUST  BE  DONE  WITH  THE  POWER  SUPPLIED 

SWITCHED OFF.  

At the beginning of the season, or regularly if the air conditioner is used all year long: 
Remove  the  cap  of  the  detection  unit  and  the  float.  Clean inside  the  detection  unit  and  the  float 
with water containing 5% bleach. 

Rinse thoroughly after use of a cleaning product.

  

Then  replace  the  float  with  the  black  spot  facing  up.  Replace  the  cap,  always  in  the  direction  of 
origin and do a full operational test.  

 

 

3.b

 SAFETY 

 

  A thermal cut-out set with AUTO-RESET 

  Connect the earth wire of the pump 

  Product without alarm 

SICCOM SAS strongly recommends fitting a high condensate level detector connected to an audio 
alarm (Buzzer) or a visual one (Indicator) to avoid any overflow or interruption of refrigeration in the 
event  of  an  incident in  the  system  or  lack  of  maintenance. To  do  this,  we  recommend  using  the

 

SICCOM SAS ref DS1HTCC110 detector available from your retailer. 

 

 Warranty  

 

Your pump is guaranteed to be in perfect working order at delivery. Pumps produced by SICCOM 
SAS  are  guaranteed  for  one  year  (12  months)  from  the  SICCOM  SAS  billing  date  against  all 
operating faults. In the case of detection of a fault, customers not located in France must return the 
pump  postage  paid  to  the  nearest  SICCOM  distributor.  All  products  returned  will  be  subject  to  a 
complete  analysis  of  origin  and  operation  in  relation  to  its  traceability  code  and  the  technical 
performances ascertained. If it is determined that the fault is unrelated to incorrect use of the pump 
and  that  the  installation  instructions  have  been  complied  with,  the  product  will  be  repaired  or 
replaced. 

 

RESTRICTIONS: 
Any  implicit  guarantee  will  be  limited  to  the  duration  of  the  express  guarantee  specified 
above. In all cases, the responsibility related to the SICCOM SAS warranty is limited to the 
replacement  or  repair  of  the  product  supplied  plus  the  cost  of  its  transport  to  the  original 
delivery location. 
N

EITHER THE  VENDOR  NOR  THE  MANUFACTURER  IS  RESPONSIBLE FOR  INJURIES OR  DAMAGES 

DIRECTLY  RELATED  TO  THE  PRODUCT  OR  SUBSEQUENT  TO  ITS  USE 

(

INCLUDING  BUT  NOT 

LIMITED TO LOSS OF PROFIT

,

 LOSS OF TURNOVER

,

 DAMAGE TO GOODS OR PERSONS DIRECTLY 

RELATED  TO  THE  PRODUCT  OR  RESULTING  FROM  ITS  USE

)

  OR  ANY  PREJUDICE  ARISING  FROM 

THE  USE  OF  OR  INABILITY  TO  USE  THE  PRODUCT

.

 

T

HE  USER  AGREES  THAT  THIS  SITUATION  IS 

WITHOUT RECOURSE OR COMPENSATION

 

THE WARRANTY WILL BE INVALIDATED IN THE FOLLOWING CASES: 

 

-

 

Pump motor cover opened 

-

 

Product connected to an incorrect supply voltage 

-

 

Tank cable cut 

-

 

Pump used dry (no liquid supply) 

-

 

Pump used to circulate liquid other than condensates. 

-

 

Incorrect use of the pump by the customer 

 

Before using the product, the user must determine whether it is compatible with his or her 
intended  use  of  the  product.  They  will  be  responsible  for  all  risks  and  legal  implications 
resulting from its use or installation. 

 SICCOM  SAS  reserves  the  right  to  modify  the  product  completely  or  partially  without  first 
informing its customers about it 

CONFORMITY CERTIFICATE SICCOM SAS

 

Z.I. Les Bordes 2 rue Gustave Madiot - 91070 Bondoufle - FRANCE declare that the mini FLOWATCH

®

0

 

is in 

conformity with :  EN 60 335-1 

D  

 

 HINWEIS 

 

Mit geringem Platzaufwand kann unsere mini FLOWATCH 

®

 0 einfach in jede Klimaanlage 

eingebaut werden (Decken-, Wand- oder Konsole-Anlage), deren Kälteleistung 8 KW (27000 Btu, 
2,2 Tonnen) nicht überschreitet. Die mini FLOWATCH 

® 

0 besteht aus den zwei folgenden Teilen :  

 

der Pumpeneinheit  

 

dem Schwimmerschalter (2 Niveaus Pumpen-Aus, Pumpen-Ein) 

 

Allgemeine technische Daten : 

 

Maximale Leistung :  

 

10 Liter / Stunde 

Maximale Fördermenge :    

10 meter  

Maximale Einsaugung :    

1,5 Meter

 

Einspeisung der Pumpeneinheit : 

220-240 V 50 Hz 

Leistungsaufnahme der Pumpe :  

11W 

Relative Einschaltdauer:    

100% 

 

Thermische Sicherung :    

Ja. Mit auto-restart.

 

Arbeitstemperatur : 

 

5°C bis 45°C 

Maximale Temperatur der Flüssigkeit:  35°C 
Schutzklasse : 

 

IP20

 

 
 

 
 
 

 

INSTALLATION 

 

 

2.a

 DIE PUMPENEINHEIT.  

 

Die Einspeisung muss von einem anderen Netz als von der Klimaanlage herkommen.  
Vor der Installation das Klimagerät spannungsfrei schalten. 
Der  Anschluss  des  Stromversorgungskabels  muss  von  einem  qualifizierten  Fachmann  unter 
Berücksichtigung der geltenden Normen des Landes durchgeführt werden. 
Dieses  Netzkabel  muss  geerdet  sein.

 

Nur  das  mitgelieferte  Dreifachkabel  mit  einer  gut  auf  die 

Leitung abgestimmten Sicherung verwenden 
(Die Norm NFC 15100 verlangt für die Wohnung einen hochempfindlichen FI-Schutzschalter (30 m 
A).) 
Die Steckdose muss nach der Installierung zugänglich bleiben. 
Bei Zweifeln und bei allen elektrischen Eingriffen wird empfohlen, einen qualifizierten Fachmann 
heranzuziehen 
SICCOM  SAS   haftet  nicht  für  eventuelle  durch  eine  unsachgemäße  Installation  entstandene 
Schäden. 
Wenn das Versorgungskabel beschädigt ist, muss es vom Hersteller, seinem Kundendienst oder 
ähnlich qualifizierten Personen ersetzt werden, damit keine Gefährdung entsteht. 
 

 
 
 
 
 
 
 
 
 
 

 

Montage der Pumpeneinheit. 

 

Die Pumpeneinheit kann in dem Klimagerät selbst, in einem Schacht (Siehe Skizze) oder in der 
Zwischendecke montiert werden.. Um die Pumpeneinheit herum muss genügend Raum frei 
gelassen werden, damit die Pumpeneinheit bei Dauerbetrieb abkühlen kann. Die Pumpeneinheit 
darf nicht abgedeckt werden (keine Isolation, kein expandierender Schaum usw.)!  
Der Abwasserschlauch am Pumpenausgang (nicht mitgeliefert) sollte einen Innendurchmesser 
von 6 x 9 mm haben und mit dem Reduzierstück am Ablaufschlauch, (bereits an der pumpe 
befestigt) angeschlossen werden. Der Pfeil auf der Pumpeneinheit gibt die Strömungsrichtung an. 
Bitte beachten! 

 

2.b

 SCHWIMMERSCHALTER 

 

Eine Bogenmuffe (mitgeliefert) ist zwischen Schimmerschalter und dem Wasserbehälter des 
Klimagerätes anzubringen. Das Kondenswasser wird über den 1,5-Meter-Schlauch (nicht 
mitgeliefert) mit einem Durchmesser von 6x9 mm angesaugt. Verwenden 2 Schellen (mitgeliefert) 
an den flexiblen Schlauch dauerhaft zu beheben in der Detektionseinheit und der Pumpe. 

 

Montage Schwimmerschalter

 

Bei  der 

le  mini  FLOWATCH  ®  0  wird  d

er  Schwimmerschalter  waagerecht  mit  Hilfe  des  Klettbandes 

(mitgeliefert) montiert. 
Die Kappe des évent mit einem Rohr PVC 

 6 x 9 ungefähr 50 mm verbinden (nicht mitgeliefert). 

 BETRIEB 

 

Sehen Sie zu, dass der Behälter Ihrer Klimaanlage für das Kondenswasser hoch genug ist, damit 
er auch beim Überschreiten des Deckels des Schwimmerschaltes das Mehrkondenswasser bei 
Stromausfall noch zurückhalten kann. 

Use only the supplied 3 core cable: 

 

Blue / Neutral 

 

Brown / Line 

 

green / Earth 
 

 

Benutzen  Sie  das  mitgelieferte  3adrige 
Spannungskabel  zum  Anschluss  der 
Pumpeneinheit: 

 

Blau / Neutral  

 

Braun / Spannung 

 

Gelb+Grün / Erdung 

 

Содержание Mini FLOWATCH 0

Страница 1: ...arrêt de celle ci 3 a ENTRETIEN Toute intervention sur la pompe de relevage de condensats DOIT ETRE EFFECTUEE HORS TENSION En début de saison ou régulièrement si la pompe est utilisée toute l année Enlever le couvercle du bloc de détection et le flotteur Nettoyer l intérieur du réservoir ainsi que le flotteur avec une solution eau javel 5 Rincer abondamment après toute utilisation d un produit de ...

Страница 2: ...o the SICCOM SAS warranty is limited to the replacement or repair of the product supplied plus the cost of its transport to the original delivery location NEITHER THE VENDOR NOR THE MANUFACTURER IS RESPONSIBLE FOR INJURIES OR DAMAGES DIRECTLY RELATED TO THE PRODUCT OR SUBSEQUENT TO ITS USE INCLUDING BUT NOT LIMITED TO LOSS OF PROFIT LOSS OF TURNOVER DAMAGE TO GOODS OR PERSONS DIRECTLY RELATED TO T...

Страница 3: ...nel condizionatore in una canalina schema qui accanto o nel controsoffitto Va preservato uno spazio libero intorno al blocco pompa per consentire il suo raffreddamento in caso di funzionamento prolungato Il blocco pompa non deve essere isolato termicamente né isolante né schiuma espansa ecc Il tubo di mandata fornito deve avere un diametro di 6 x 9 mm Usare il collare di serraggio per fissare corr...

Страница 4: ...rma sonora Pitido o visual Piloto para evitar cualquier desbordamiento y detener la producción frigorífica en caso de que se produjese un incidente en el sistema o de que no se hubiese realizado el mantenimiento Para ello se recomienda utilizar el detector SICCOM SAS ref DS1HTCC110 que encontrará disponible en su distribuidor RESTRICCIONES Cualquier garantía implícita se limitará al período de gar...

Страница 5: ...ен внутри кондиционера а также в защитном коробе см схему или под потолком Важно чтобы пространство вокруг насоса было достаточным для его охлаждения при длительной и непрерывной работе Категорически не допускается теплоизоляция насоса не допускается использовать изоляционные материалы пеноматериалы и пр Необходимо использовать нагнетательную трубку диаметром 6 x 9 мм Для надежности соединения пом...

Отзывы: