Solar working station operation manual SR881
- 24 -
►Press “SET” button again to access program
,
can adjust parameter value now
►Press “+”“-” button, to adjust the value of parameter
►Press “ESC” button, exit program of submenu
►Press “ESC” button again, to exit main menu.
4.3 Main menu DT O & DT F Temperature difference function
Description:
Solar circuit pump P1 is triggered by the temperature difference function, so long as the
temperature difference between collector and tank reaches the switch-on DT, solar circuit
pump is triggered.
For example: the switch-on DT is 8
o
C, switch-off DT is 4
o
C, if the temperature in the bottom
part of tank is 20
o
C, then just when collector temperature rises up to 28
o
C, pump is
triggered, and when collector temperature drops to 24
o
C, pump is ceased.
Note:
the switch-on/off DT of 8
o
C and 4
o
C are standard system setting according to many
years’ experience, only in special application cases it needs to be changed, (e.g. far
distance heat transferring), normally it is recommend using default set. Switch-on and
switch-off DT are alternating set. To avoid mistake the minimum difference between two
temperature differences (ΔTon –ΔToff) is set as 2oC.
Setup the switch-on temperature difference:
Under standby status, access main menu DT O,
►Press “SET” button, to access settings program of DT O, “DT O 08
℃
” displays on screen,
“08
℃
” blinks, the switch-on temperature difference can be
set.
►Press “+”“-” button, to adjust the value of switch-on DT,
adjustable range (OFF+2
℃)~
20
℃,
factory setting is 8
℃
►Press “ESC” button to exit this setting, parameter is saved automatically.
Setup the switch-off temperature difference:
Under standby status, access main menu DT F
►Press “SET” button, to access settings program of DT F, “DT F 04
℃
” displays on screen,
“04
℃
” blinks, the switch-off temperature difference can be set.
►Press “+”“-” button to adjust the value of switch-off DT,
adjustable range 0
℃~(
ON-2
℃),
factory set is 4
℃
.
►Press “ESC” to exit menu, or wait for 20 seconds to exit