background image

6

3.  Add  the  Btu/Hr  of  all  fuel  burning  appliances  in  the 

space.

 

Vent-free log set _______________   Btu/Hr

 

Gas water heater* ______________   Btu/Hr

 

Gas furnace ___________________   Btu/Hr

 

Vented gas heater ______________   Btu/Hr

 

Gas fireplace logs

 ______________   Btu/Hr

 

Other gas appliances*   + ________   Btu/Hr

 

Total                              = ________   Btu/Hr

 

* Do not include direct-vent gas appliances. Direct-vent 

draws combustion air from the outdoors and vents to 
the outdoors.

 

Example:

 

Vent-free log set   ______________   Btu/Hr

 

Gas water heater*   _____________   Btu/Hr

 

Total                              = ________   Btu/Hr

4.  Compare the maximum Btu/Hr the space can support with 

the actual amount of Btu/Hr used.

 

 ____ Btu/Hr (max. the space can support) 

 

 ____ Btu/Hr (actual amt. of Btu/Hr used)  

 

Example: 63,300 Btu/Hr (maximum the space can sup-

port) 

 

 

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a 

confined

 space because 

the actual Btu/Hr used is more than the maximum Btu/Hr 
the space can support. You must provide additional fresh 
air. Your options are as follows:

A. Rework work sheet, adding the space of an adjoining room. 

If the extra space provides an 

unconfined

 space, remove 

door to adjoining room or add ventilation grills between 
rooms. See Ventilation Air from Inside Building, page 5.

B. Vent room directly to the outdoors. See Ventilation Air 

from Outdoors, page 5.

C. Install a lower Btu/Hr appliance, if lower Btu/Hr size 

makes room unconfined. 

If the actual Btu/Hr used is less than the maximum Btu/Hr 
the space can support, the space is an 

unconfined

 space. 

You will need no additional fresh air ventilation. 

39,000

40,000

79,000

AIR FOR COMBUSTION 

AND VENTILATION

  WARNING:  If  the  area  in  which  the 

heater may be operated does not meet the 
required  volume  for  indoor  combustion 
air, combustion and ventilation air shall be 
provided by one of the methods described 
in the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, the International Fuel Gas Code, 
or applicable local codes.

CONTINUED

VENTED OPERATION

Note:

            When used as a vented heater, appliance must be
installed only in a solid-fuel burning fireplace with a 
working flue and constructed of noncombustible mat-
erial.

 

Area of Various Standard

Round Flues

Diameter (ins.)

Area (sq. ins.)

5"

20 sq. inches

6"

29 sq. inches

7"

39 sq. inches

8"

51 sq. inches

You may also use this heater as a vented product. There are.

three reasons for operating your heater in the vented mode.

1.

The fireplace does not meet the clearance to com- 
bustibles requirements for vent-free operation.

2.

State or local codes do not permit vent-free operation.

3.

You prefer vented operation.

If reasons number 1 or 2 above apply to you, you must per- 
manently open chimney flue damper. You must install the 
damper clamp. This will insure vented operation (see Fig- 
u r e   10).  The  damper  clamp  will  keep damper  open.
See  chart  below  for  minimum  permanent flue  opening 
you  must  provide.  Attach damper clamp so the mini- 
mum permanentflue opening will be maintained at all times.

Follow instructions Installing  Damper Clamp  on 
page 8 for location of damper in the fireplace.  

Damper
Clamp

Damper

Chimney

Minimum Permanent

Height (ft.) Flue Opening (sq. ins.)

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

 

   

   

 

 

 

The  National Fuel Gas Code A N S I Z223.1/NFPA 54 defines a confined space as a space

 

space whose volume is less than 50 ft

3

 

per 1000btu/hr (4.8 m

3

 per kw) of the aggregate

input of all appliances installed in that space. Rooms communicating directly with the 
space in which the appliances are installed, through openings not furnished with doors 
are considered a part of the unconfined space.  

Содержание GERRR18LP

Страница 1: ...MER Retain this manual for future reference This appliance may be installed in an aftermarket permanently located manu factured mobile home where not prohib ited by local codes This appliance is only for use with the type of gas indicated on the rating plate This app liance is not convertible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer Th...

Страница 2: ...blow directlyintotheappliance Avoidanydrafts that alter burner flame patterns Ceiling fans can create drafts that alter burner flamepatterns Alteredburnerpatternscan cause sooting WARNING Do not use a blower insert heat exchanger insert or other accessory not approved for use with this appliance Due to high temperatures the appliance should be located out of traffic and away from furniture and draper...

Страница 3: ...ance has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the fireplace if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 If appliance keeps shutting off see Troubleshooting pages 17 through 20 11 Do not run appliance where flammable liquids or vapors are used or stored under dusty conditions 12 Do not use this appliance to cook fo...

Страница 4: ...d a control valve The thermostat will automatically modulate the heat output to maintain a consistent room temperature This results in greater heater comfort This can also result in lower gas bills PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code ANSI Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation All spaces in homes fall into one of the followin...

Страница 5: ...ls or ducts You must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors or spaces open to the s e c a p s l w a r c d n a s c i t t a e d u l c n i s e c a p s e s e h T s r o o d t u o Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation for required size of ventilat...

Страница 6: ...ay be operated does not meet the required volume for indoor combustion air combustion and ventilation air shall be provided by one of the methods described intheNationalFuelGasCode ANSIZ223 1 NFPA 54 the International Fuel Gas Code or applicable local codes CONTINUED VENTED OPERATION Note When used as a vented heater appliance must be installed only in a solid fuel burning fireplace with a working...

Страница 7: ...this is beneficial installing appliance in rooms without enough ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventilation page 4 CHECK GAS TYPE Use the correct gas type natural or propane LP for your appliance If your gas supply is not correct or if you do not know your gas type do not install appliance INSTALLATION ITEMS NEEDED Before installing applian...

Страница 8: ...lator damage could occur For propane LP gas the installer must supply an external regulator The external regulator will reduce incoming gas pressure Youmustreduceincominggaspressuretobetween 11 and 14 of water If you do not reduce incoming gas pressure heater regulator damage could occur Install the external regulator with the vent pointing down as shown in Figure 4 Pointing the vent down protects...

Страница 9: ...nd that you install a sediment trap in supply line as shown in Figure 5 Locate sediment trap where it is within reach for cleaning Install in piping system between fuel supply and appliance Locate sediment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into appliance gas controls If sediment trap is not installed or is i...

Страница 10: ...as valve located on or near gas meter of natural gas or using compressed air 3 Check all joints from gas meter to equipment shutoff valve for natural gas or propane LP supply to equipment shutoff valve for propane LP Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 4 Correct all leaks at once CONTINUED 10 OPTIONAL REMOTE CONTROL SET INSTALLATION AND OPERATION COMMUN...

Страница 11: ...Proper Log Placement for Discovery Elm 18 Models Log 2 Log 6 Log 1 Log 5 Log 7 If you have any questions please call 800 229 5647 GERRR18 MODELS Log 3 Log 4 11 ...

Страница 12: ...Proper Log Placement for Golden Eclipse 24 Models Log 2 Log 6 Log 1 Log 5 Log 7 If you have any questions please call 800 229 5647 GERRR24 MODELS Log 3 Log 4 12 ...

Страница 13: ...ONS WARNING If fireplace has glass doors never operate this heater with glass doors closed If you operateheaterwith doorsclosed heat buildup inside fireplace willcauseglasstoburst Make suretherearenoobstructions across openings of fireplace You must operate this heater with a fireplace screen in place Make sure fireplace screen is closed before running heater NOTICE Duringinitialoperationof new heate...

Страница 14: ...ton This will light pilot The pilot is attached Note If pilot does not light no spark contact a qual ified service person or gas supplier for repairs Until re with match see Manual Lighting Procedure page 15 8 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If control knob does not pop out when released contact a qualified service person or gas...

Страница 15: ... switch see Fig ure 10 to the ON position Replace or remove low batteries as soon as possible to prevent corrosion damage to remote control acces sory 15 HAND HELD TRANSMITTER OPERATION Move the side Slide Switch into the ON position tow ards the flat end of the unit Press and hold the control button see Figure 11 on the Hand Held Remote until burner turns on Press and hold the control button agai...

Страница 16: ...nd let cool Remove blockage Blocked burner flame holes will create soot MAIN BURNER BURNER FLAME PATTERN Figure 15 shows the correct burner flame patern Figure 16 shows the incorrect burner flame patern turn Gas Log Set off see Turning OFF the Ap pliance page 15 see Cleaning and Maintenance this page see Troubleshooting page 22 CLEANING AND MAINTENANCE WARNING Turn off Gas Logs and let CAUTION keep...

Страница 17: ... See Fig 18 See Fig 18 Figure 18 Pilot Inlet Air Hole 19 17 ...

Страница 18: ...18 ...

Страница 19: ...19 ...

Страница 20: ... RMH 120 SP051 RMH 120 SP049 9 Orifice Tube Main Burner 1 RMH 120 09003 RMH 120 09003 9 Orifice Tube Main Burner 1 RMH 120 09004 RMH 120 09004 10 Elbow 375 MNPT X 375 Flare 1 RMH 120 00062 RMH 120 00062 11 Adapter 375 MNPT X 5625 Flare 1 RMH 120 00050 RMH 120 00050 12 Adapter 375 FNPT X 5625 Flare 1 FCHD1809021 FCHD1809021 13 Tube Main Gas Supply 1 WIP 120 90414 WIP 120 90414 14A Remote Receiver 1...

Страница 21: ... heater will not produce the specified heat propane LP gs supply may be low You may feel your gas pressure is too low If so contact your local natural or propane LP gas supplier Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty TECHNICAL SERVICE You may have further questions about installation opera tion or troubleshooting If so co...

Страница 22: ...n rust or discoloring of any kind use or installation contrary to instructions and applicable building codes including heating the product to temperatures above its rated specifications which can cause considerable warping disassembly including removal of the product from a built in installation damage resulting from accident alteration misuse abuse hostile environments or improper installation rep...

Отзывы: