background image

5

Unusually Tight Construction

The air that leaks around doors and windows may provide 
enough fresh air for combustion and ventilation. However, in 
buildings of unusually tight construction, you must provide 
additional fresh air.

Unusually  tight  construction  is 

defined

  as  con

-

struction where:
a.  walls  and  ceilings  exposed  to  the  outside 

atmosphere  have  a  continuous  water  vapor 
retarder with a rating of one perm (6 x 10

-11 

kg 

per pa-sec-m

2

) or less with openings gasketed 

or sealed and 

b.  weather stripping has been added on openable 

windows and doors and 

c.  caulking or sealants are applied to areas such 

as  joints  around  window  and  door  frames, 
between sole plates and 

floo

rs, between wall-

ceiling joints, between wall panels, at penetra

-

tions  for  plumbing,  electrical,  and  gas  lines, 
and at other openings.  

If your home meets all of the three criteria above, 
you must provide additional fresh air. See Ventila
-
tion Air From Outdoors
, page 5. 

If your home does not meet all of the three criteria 
above, proceed to  Determining Fresh-Air Flow for 
Appliance Location
, page 6. 

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would  come  from an adjoining  unconfined 
space. When ventilating  to an adjoining  unconfined  space, 
you must provide two permanent  openings:  one within 12" 
of the  ceiling and  one  within 12" of the  floor on  the  wall 
connecting  the  two  spaces  (see  Figure  1). You can  also 
remove  door  into  adjoining  room  (see Figure 1). Follow 
the National Fuel Gas Code ANSI Z223.1/NFPA 54,  Sec-
tion  5.3, Air for Comb ustion  and Ventilation for required 
size of ventilation grills or ducts. 

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. 
You  must  provide  two  permanent  openings:  one  within 
12" of the ceiling and one within 12" of the 

floor.

 Connect 

these items directly to the outdoors or spaces open to the 

  

.

s

e

c

a

p

s

 

l

w

a

r

c

 

d

n

a

 

s

c

i

t

t

a

 

e

d

u

l

c

n

i

 

s

e

c

a

p

s

 

e

s

e

h

T

 

.

s

r

o

o

d

t

u

o
Follow the National Fuel Gas Code ANSI Z223.1/NFPA 
54,  Section  5.3,  Air  for  Combustion  and Ventilation for 
required size of ventilation grills or ducts. 

IMPORTANT:

 Do not provide openings for inlet or outlet 

air into attic if attic has a thermostat-controlled power vent. 
Heated air entering the attic will activate the power vent.

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

Figure 1 - Ventilation Air from Inside Building

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Figure 2 - Ventilation Air from Outdoors

DETERMINING FRESH-AIR FLOW 
FOR APPLIANCE LOCATION

Determining if You Ha

ve a Confined 

or Unconfined Space

Use this work sheet to determine if you have a 

confined 

or unconfined space.

Space:  Includes the room in which you will install appli-
ance plus any adjoining rooms with doorless passageways 
or ventilation grills between the rooms.

1.  Determine the volume of the space (length x width x 

height).

 

Length x Width x Height =  cu. ft. (volume of space)

 

Example:  Space size 22 ft. (length) x 18 ft. (width) x 
8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

 

If  additional  ventilation  to  adjoining  room  is  supplied 
with grills or openings, add the volume of these rooms 
to the total volume of the space. 

2.  Multiply the space volume by 20 to determine the maxi-

mum Btu/Hr the space can support.

 

 _______ (volume of space) x 20 = (Maximum Btu/Hr 
the space can support)

 

Example:   3168  cu.  ft.  (volume  of  space)  x  20  =  63,360 
(maximum Btu/Hr the space can support)

Содержание GERRR18LP

Страница 1: ...MER Retain this manual for future reference This appliance may be installed in an aftermarket permanently located manu factured mobile home where not prohib ited by local codes This appliance is only for use with the type of gas indicated on the rating plate This app liance is not convertible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer Th...

Страница 2: ...blow directlyintotheappliance Avoidanydrafts that alter burner flame patterns Ceiling fans can create drafts that alter burner flamepatterns Alteredburnerpatternscan cause sooting WARNING Do not use a blower insert heat exchanger insert or other accessory not approved for use with this appliance Due to high temperatures the appliance should be located out of traffic and away from furniture and draper...

Страница 3: ...ance has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the fireplace if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 If appliance keeps shutting off see Troubleshooting pages 17 through 20 11 Do not run appliance where flammable liquids or vapors are used or stored under dusty conditions 12 Do not use this appliance to cook fo...

Страница 4: ...d a control valve The thermostat will automatically modulate the heat output to maintain a consistent room temperature This results in greater heater comfort This can also result in lower gas bills PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code ANSI Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation All spaces in homes fall into one of the followin...

Страница 5: ...ls or ducts You must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors or spaces open to the s e c a p s l w a r c d n a s c i t t a e d u l c n i s e c a p s e s e h T s r o o d t u o Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation for required size of ventilat...

Страница 6: ...ay be operated does not meet the required volume for indoor combustion air combustion and ventilation air shall be provided by one of the methods described intheNationalFuelGasCode ANSIZ223 1 NFPA 54 the International Fuel Gas Code or applicable local codes CONTINUED VENTED OPERATION Note When used as a vented heater appliance must be installed only in a solid fuel burning fireplace with a working...

Страница 7: ...this is beneficial installing appliance in rooms without enough ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventilation page 4 CHECK GAS TYPE Use the correct gas type natural or propane LP for your appliance If your gas supply is not correct or if you do not know your gas type do not install appliance INSTALLATION ITEMS NEEDED Before installing applian...

Страница 8: ...lator damage could occur For propane LP gas the installer must supply an external regulator The external regulator will reduce incoming gas pressure Youmustreduceincominggaspressuretobetween 11 and 14 of water If you do not reduce incoming gas pressure heater regulator damage could occur Install the external regulator with the vent pointing down as shown in Figure 4 Pointing the vent down protects...

Страница 9: ...nd that you install a sediment trap in supply line as shown in Figure 5 Locate sediment trap where it is within reach for cleaning Install in piping system between fuel supply and appliance Locate sediment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into appliance gas controls If sediment trap is not installed or is i...

Страница 10: ...as valve located on or near gas meter of natural gas or using compressed air 3 Check all joints from gas meter to equipment shutoff valve for natural gas or propane LP supply to equipment shutoff valve for propane LP Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 4 Correct all leaks at once CONTINUED 10 OPTIONAL REMOTE CONTROL SET INSTALLATION AND OPERATION COMMUN...

Страница 11: ...Proper Log Placement for Discovery Elm 18 Models Log 2 Log 6 Log 1 Log 5 Log 7 If you have any questions please call 800 229 5647 GERRR18 MODELS Log 3 Log 4 11 ...

Страница 12: ...Proper Log Placement for Golden Eclipse 24 Models Log 2 Log 6 Log 1 Log 5 Log 7 If you have any questions please call 800 229 5647 GERRR24 MODELS Log 3 Log 4 12 ...

Страница 13: ...ONS WARNING If fireplace has glass doors never operate this heater with glass doors closed If you operateheaterwith doorsclosed heat buildup inside fireplace willcauseglasstoburst Make suretherearenoobstructions across openings of fireplace You must operate this heater with a fireplace screen in place Make sure fireplace screen is closed before running heater NOTICE Duringinitialoperationof new heate...

Страница 14: ...ton This will light pilot The pilot is attached Note If pilot does not light no spark contact a qual ified service person or gas supplier for repairs Until re with match see Manual Lighting Procedure page 15 8 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If control knob does not pop out when released contact a qualified service person or gas...

Страница 15: ... switch see Fig ure 10 to the ON position Replace or remove low batteries as soon as possible to prevent corrosion damage to remote control acces sory 15 HAND HELD TRANSMITTER OPERATION Move the side Slide Switch into the ON position tow ards the flat end of the unit Press and hold the control button see Figure 11 on the Hand Held Remote until burner turns on Press and hold the control button agai...

Страница 16: ...nd let cool Remove blockage Blocked burner flame holes will create soot MAIN BURNER BURNER FLAME PATTERN Figure 15 shows the correct burner flame patern Figure 16 shows the incorrect burner flame patern turn Gas Log Set off see Turning OFF the Ap pliance page 15 see Cleaning and Maintenance this page see Troubleshooting page 22 CLEANING AND MAINTENANCE WARNING Turn off Gas Logs and let CAUTION keep...

Страница 17: ... See Fig 18 See Fig 18 Figure 18 Pilot Inlet Air Hole 19 17 ...

Страница 18: ...18 ...

Страница 19: ...19 ...

Страница 20: ... RMH 120 SP051 RMH 120 SP049 9 Orifice Tube Main Burner 1 RMH 120 09003 RMH 120 09003 9 Orifice Tube Main Burner 1 RMH 120 09004 RMH 120 09004 10 Elbow 375 MNPT X 375 Flare 1 RMH 120 00062 RMH 120 00062 11 Adapter 375 MNPT X 5625 Flare 1 RMH 120 00050 RMH 120 00050 12 Adapter 375 FNPT X 5625 Flare 1 FCHD1809021 FCHD1809021 13 Tube Main Gas Supply 1 WIP 120 90414 WIP 120 90414 14A Remote Receiver 1...

Страница 21: ... heater will not produce the specified heat propane LP gs supply may be low You may feel your gas pressure is too low If so contact your local natural or propane LP gas supplier Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty TECHNICAL SERVICE You may have further questions about installation opera tion or troubleshooting If so co...

Страница 22: ...n rust or discoloring of any kind use or installation contrary to instructions and applicable building codes including heating the product to temperatures above its rated specifications which can cause considerable warping disassembly including removal of the product from a built in installation damage resulting from accident alteration misuse abuse hostile environments or improper installation rep...

Отзывы: