17
7. Communication between the CIT-200 and
Mitsubishi PLC
7.1
Setup
7.1.1
Setup of Calculator link unit (AJ71UC24)
(1) Sets the transmission control procedure (protocol)
and control procedure of RS-422A or RS-232C.
Set to 8 (Protocol 4).
(2) Sets the instrument number of the double digit (x10).
Set the number to 0.
(3) Sets the instrument number of the single digit (x1).
Set the number to 0.
(4) Sets the transmission specifications.
See (Table 7.1.1-1).
Set the items except for the baud rate to .
(Fig.
7.1.1-1)
(Table 7.1.1-1)
Setting switch
Setting item
Setting switch ON
Setting switch OFF
SW11
Main channel setting
RS-422A
RS-232C
SW12
Data bit setting
8 bits
7 bits
Baud
rate
9600bps
19200bps
SW13 ON
OFF
SW14 OFF
ON
SW15
Transmission speed setting
ON ON
SW16 Parity
setting
Yes
No
SW17
Even/Odd parity setting
Even
Odd
SW18
Stop bit setting
2 bits
1 bit
SW21 Checksum
setting
Yes
No
SW22
Writing during RUN
Possible
Impossible
SW23
Calculator link/multi-drop link
selection
Calculator link
Multi-drop link
SW24 Not
used
STATION NO.
×
10
MODE
×
1
SW11
SW12
SW13
SW14
SW15
ON
(1)
STATION NO.
SW16
SW17
SW18
SW21
SW22
SW23
SW24
ON
(2)
(3)
(4)