6.3 Wiring connection example
Notices
Use the recommended cable to connect the PLC and CIT-200.
Use the recommended D sub connector to connect the PLC and CIT-200.
Use a thick wire (1.25 to 2.0mm
2
) as a grounding cable.
When the communication line is RS-422A, mount a terminator referring to the Instruction manual for
each PLC.
Solderless terminal
Use a solderless terminal with an isolation sleeve that fits to the M3 screw as shown below.
(Fig. 6.3-1)
Solderless
terminal
Manufacturer
Model name
Fastening torque
Nichifu Terminal Industries CO., LTD.
1.25-Y3
Y type
Japan Solderless Terminal MFG CO., LTD. VD1.25-B3A
Nichifu Terminal Industries CO., LTD.
1.25-3
Round type
Japan Solderless Terminal MFG CO., LTD. V1.25-3
0.6N
・
m
Max. 1.0N
・
m
Recommended cable
Name Manufacturer
Communication
line
OTSC-2PVB-7/0.32TA
ONAMBA CO., LTD.
RS-232C
OTSC-3PVB-7/0.32TA
ONAMBA CO., LTD.
RS-422A
Recommended D sub connector
Model Manufacturer
Name
DE-9SF-N
Japan Aviation Electronics Ind., Ltd. D sub 9-pin ( ) connector
DE-C1-J6
Japan Aviation Electronics Ind., Ltd.
D sub 9-pin connector cover
DB-25PFT-N
Japan Aviation Electronics Ind., Ltd. D sub 25-pin ( ) connector
DB-C2-J9
Japan Aviation Electronics Ind., Ltd.
D sub 25-pin connector cover
5.8mm or less
3.2mm
3.2mm
5.8mm or less