21(33)
F.10
Shortage metering alarm
Set the number of times that the material doesn
’
t fall into the
hopper, and it should alarm after several times of this error
occurs.
Alarm cleaning mode:
1.The alarm will dismiss when it feeds the materials again.
2. Ent key on the panel can be cancelled.
3.Turn on the power again.
Set 9 as cancelling this function.
Corresponding action: A.01
3
1-9 times
F.11
Shutdown alarm for the times of material shortage
Set the number of times that no material falling into the
hopper. The times of material shortage that it should alarm.
1.ENT key on the panel can be cancelled.
2.Turn on/off the power again.
Corresponding action: A.04
3
[F.10]-99
F.12
The time waiting for motor stoppage (suitable for sal-430 /
460) .
After motor starts, it only takes next action after the time
countdown is finished.
20 secs.
0-99 secs.
F.13
Buzzer alarm type
0:
Lasting alarm
1: Slow and interrupted alarm
2:Fast and interrupted alarm
0
0-2
F.14
Motor delay stop time
After [F.01] suction time is ended, the delay time before
motor stop.
0 secs.
0~999
secs.
F.15
Motor working time
Check motor working time and clear the time.
The method to clear the motor working time: Set the setting
value as 0, and press ENT key to cancel.
0
(unit:
10 hrs.)
0-999
Only 0
means
clearing
the time.