(Ex.) If used voltage is 208 V and voltage drops by 10.4 V.
Three-phase: Cabtyre cables
(Unit: AWG)
Length 100 ft. (30 m)
or less
200 ft.
(61 m)
300 ft.
(91 m)
400 ft.
(122 m)
500 ft.
(152 m)
600 ft.
(183 m)
Current
50 A
10
6
6
4
2
2
100 A
6
4
2
1
1/0
1/0
150 A
6
2
1
1/0
2/0
3/0
200 A
4
1
1/0
3/0
4/0
4/0
250 A
2
1/0
2/0
4/0
-
-
300 A
2
1/0
3/0
4/0
-
-
(Ex.) If used voltage is 120 V and voltage drops by 6 V.
Single-phase Cabtyre cables
(Unit: AWG)
Length
100 ft. (30 m)
or less
200 ft. (61 m)
300 ft. (91 m)
400 ft. (122 m)
Current
10 A
14
10
8
8
20 A
10
8
6
4
30 A
8
6
4
2
50 A
6
4
2
1
100 A
4
1
2/0
3/0
150 A
2
2/0
4/0
-
200 A
1
3/0
-
-
250 A
1/0
4/0
-
-
300 A
2/0
-
-
-
350 A
2/0
-
-
-
400 A
3/0
-
-
-
7-2. Connecting Load Cables
< Note >
When connecting a load, check that the generator output setting, output terminal connection
position, and load power source are all matching.
If using the N terminal, be careful that the currents of each phase are uniform.
WARNING : ELECTRIC SHOCK
Always turn all the breakers OFF, place the starter switch in the STOP position and
stop the engine before connecting / disconnecting the load cable to the output
terminal or receptacle.
Close the output terminal cover before operating.
Do not insert a pin, needle or other metal object into the receptacle.
Do not touch the generator if the generator or casing becomes wet during operation.
CAUTION : FIRE
Do not connect the generator output to indoor wiring.