Monitor lamp
Alarm Indication
Inspection and Remedial Measures
Red PL lights.
Open phase/phase
sequence abnormal/
frequency abnormal
Phase sequence of power supply is incorrect. Check wiring.
Operation is normal when green lamp is lit.
O.C. lights.
Over-current alarm
detected
Turn off power. Check and find cause of over-current and take appropriate measures. Then,
resupply power.
Over-current detection is not reset unless power supply to the instrument is turned off.
If over-current occurs, never resupply power without checking and taking remedial measures on
load side.
Otherwise, thyristor element may be destroyed.
FUSE lights.
Rapid fuse blown
Check load side, find cause of blown fuse, and take remedial measures. Then, replace it with new
rapid fuse. For the fuse replacement procedure, refer to 10-4 'Replacement of rapid fuse.'
H/B lights.
Heater break alarm
Check heater for heater break.
O.H. lights.
Internal temperature
abnormal
Check instrument body for overheating.
If current is 50 A or above, check fan for stoppage or slow rotation.
14-2. Troubleshooting
Symptom
Possible Cause
Remedy
Output is not produced.
Is voltage across power supply terminals (R, S, T)
normal?
Is alarm active? (Is Monitor lamp lit?)
Is control input signal normal?
Is internal power or external power setting normal?
Control board or thyristor element may have problem.
Output remains on.
Is control input signal normal?
Is internal power or external power setting normal?
Control board or thyristor element may have problem.
Alarm is output
frequently.
Is load short-circuited?
Check and repair load.
Has load insulation failed?
Check and repair load.
Is load capacity rating exceeded?
Replace the PAC46 with one having sufficient load
capacity.
Is phase sequence of power supply adjusted correctly?
Check power supply for phase sequence.
Output is out of
balance.
Is voltage across power supply terminals (R, S, T)
normal?
Is phase sequence of power supply correct?
Is one phase of load side broken?
Control board or thyristor element may have problem.
•
Model
•
Specifications
: QSV005/QSV006
: Characteristic/resistance: B/10 kΩ
: Lead: Vinyl lead 1 m included
Wire end treatment: Half-stripped
: Scale plate and knob, one each
䡡
Name and graduation
External power
(QSV005)
0 to 100%
Manual power
(QSV005)
0 to 100%
Base power
(QSV005)
0 to 100%
High-low power
(QSV005)
0 to 100%
Current limit setting
device
(QSV006)
50 to 100%
•