PID parameter group 08
PARAMETER DESCRIPTION 232
5.9.6 PID integral property
PID integral separation function can effectively reduce overshoot.
Parameter
Name
Default
Setting Range
Content
08-28
P.715
Integral separated
property
0
Off
---
1
Integral
separated
08-29
P.716
Integral separated
point
50.00% 0~100.00%
Set the deviation between target and feedback when
integral separate function works.
PID
integral separated function
When set 08-28(P.715) to 1, integral separation is on. If deviation between target and feedback is greater than
08-29(P.716) value, PID will only perform proportional and differential controller, which can reduce the overshoot
of PID.
5.9.7 PID differential limit
In PID control, differential controller can cause system to oscillate, so generally
differential needs to be limited to a
very small range.
Parameter
Name
Default
Setting Range
Content
08-30
P.717
PID differential limit
0.10%
0~100.00%
Set PID differential limit
PID differential limit
In PID control, differential controller is sensitive and may easily cause system oscillation. Generally differential is
set to a small range. 08-30(P.717) is used to set PID differential output range.
5.9.8 PID output deviation limit
PID output deviation limit can control the change of PID output and improve the stability of inverter operation
Parameter
Name
Default
Setting Range
Content
08-31
P.718
PID output positive
deviation limit
100.00% 0~100.00%
Set the limit for PID two outputs
08-32
P.719
PID output negative
deviation limit
100.00% 0~100.00%
PID output deviation limit
This function is used to limit the difference between two outputs of PID, which can effectively prevent PID output
from changing too fast and stabilize inverter operation.