5.4 Requirement for electric connection

Before making any electrical connections to the Pmag, consider the following standards and be sure to have proper power

supply, conduit, and other accessories.

5.4.1 Conduit Connections

The Pmag Integral Mount Magnetic Flowmeter Transmitter has 4 M16*1.5 conduit connections.

5.4.2 Transmitter Input Power

The Pmag Transmitter is designed to be powered by voltages ranging 85÷265Vac (50 a 60 Hz), 24Vac or 24Vdc.

5.4.3 DC Power Requirements

Units powered with 24Vdc may draw up to 2 amps of current. As a result, the input power wire must meet certain

gauge requirements.

5.4.4 Disconnects

The supply wires should be connected to the device through an external disconnect or circuit breaker. The disconnect

or circuit breaker should be clearly labeled and located near the transmitter.

5.4.5 Overcurrent  Protection

Pmag requires overcurrent protection of the supply lines. Maximum rating of overcurrent devices are as follows:

Pmag 

- Installation

5.5 ENVIRONMENTAL CONSIDERATIONS

To ensure maximum transmitter life, avoid excessive heat and vibration.Typical problem areas include high-vibration lines

with integrally Mounted transmitters, warm-climate installations in direct sunlight, and outdoor installations in cold

climates. Because the Pmag System requires external power, access to a suitable power source must be ensured.

Overheating will damage the flowtube. Do not encapsulate the flowtube with heating elements

5.6 Mounting

Electric magnetic flow meter has a flanged connector, and meets standard UNI EN 1092-1 ( Ex UNI 2223).

5.7 Environment of the installation

1) The Pmag must by mounted in dry and well ventilated site. Not install the instrument in the place where the water  is easily accumulated.
2) The instrument should not be exposed. Shelter is needed where the instrument is installed outside.
3) Vibration should be avoided in the place where the instrument is to be installed.
4) Keep the instrument away from strong magnetic field where big electric motor or transformer are installed.
5) The place where the instrument is installed shall be accessible for maintenance

5.8 Selecting the place for installation

1) The arrow mark on the sensor must be in accordance with the medium flow direction in the pipeline.
2) The sensor must be full with the medium all the time.
3) The straight length of the upstream pipeline must not be less than 5xD, and the downstream 3x3D, where D is the

inner diameter of the pipe, and the middle of the sensor can be a point of the lengths

Содержание Pmag

Страница 1: ...nd reverse flow rate direct reverse and net total General A complete magnetic flowmeter system consists of two components the Smag62 microprocessor based integral mount magneti flowmeter transmitter and a flowtube The flowtube is installed in line with process piping either vertically or horizontally Coils located on opposite sides of the flowtube create a magnetic field and conductive liquid movi...

Страница 2: ...pull up resistor through JP1 1 7 Reverse Flow Instantaneous and totalized reverse flow measure 1 8 Output Testing Current Source Transmitter can be commanded to supply a specified current between 4 0 and 20 0 mA Frequency Source Transmitter can be commanded to supply a specified frequency between 0 1 and 10000 Hz 1 9 Start up Time 0 5 seconds from zero flow 1 10 Low Flow Cutoff Adjustable between ...

Страница 3: ...Page 3 of 24 Pmag Features 0 0 5 N D o t 3 N D m o r f e g n a r w o l F d r a d n a t s n i m 0 1 N D 0 0 0 2 N D o t 0 0 6 N D m o r f e g n a r w o l F 0 0 0 1 N D x a m d r a d n a t s 3 FLOW TABLES ...

Страница 4: ... 5 1 4 0 5 2 5 2 1 0 1 2 8 8 1 4 2 0 5 1 6 1 0 0 3 5 7 4 5 8 2 0 5 1 0 4 2 8 2 2 5 3 0 0 2 0 1 0 5 3 3 3 5 0 4 3 0 0 2 5 9 2 8 2 2 5 4 0 5 2 0 1 0 5 4 7 8 5 5 9 3 0 1 3 0 5 2 0 5 3 2 1 3 2 4 8 0 0 3 0 1 0 0 5 7 5 6 5 4 4 0 1 3 0 0 3 0 0 4 2 1 3 2 2 0 1 0 5 3 0 1 0 5 5 7 4 7 5 0 5 0 5 4 0 5 3 0 6 4 6 1 3 2 3 2 1 0 0 4 0 1 0 0 6 1 9 7 5 6 5 0 5 4 0 0 4 5 1 5 6 1 6 2 7 4 1 0 5 4 0 1 0 0 6 7 1 8 5 1 6...

Страница 5: ... 0 5 2 5 2 1 0 1 2 8 8 1 2 2 0 5 1 6 1 0 0 3 7 7 3 5 8 2 0 5 1 0 4 2 8 2 2 3 3 0 0 2 0 1 0 5 3 5 3 4 0 4 3 0 0 2 5 9 2 8 2 2 3 4 0 5 2 0 1 0 5 4 0 9 4 5 9 3 0 1 3 0 5 2 0 5 3 2 1 3 2 2 8 0 0 3 0 1 0 0 5 0 6 5 5 4 4 0 1 3 0 0 3 0 0 4 2 1 3 2 0 0 1 0 5 3 0 1 0 5 5 9 4 6 5 0 5 0 5 4 0 5 3 0 6 4 6 1 3 2 1 2 1 0 0 4 0 1 0 0 6 3 9 6 5 6 5 0 5 4 0 0 4 5 1 5 6 1 6 2 5 4 1 0 5 4 0 1 0 0 6 0 2 7 5 1 6 0 5 4...

Страница 6: ...ed in this manual unless qualified 5 2 3 High voltage that may be present on leads could cause electrical shock Avoid contact with leads and terminals 5 3 PRE INSTALLATION There are several pre installation steps that make the installation process easier They include identifying the options and configurations that apply to your application setting the hardware switches if necessary and considerati...

Страница 7: ...h integrally Mounted transmitters warm climate installations in direct sunlight and outdoor installations in cold climates Because the Pmag System requires external power access to a suitable power source must be ensured Overheating will damage the flowtube Do not encapsulate the flowtube with heating elements 5 6 Mounting Electric magnetic flow meter has a flanged connector and meets standard UNI...

Страница 8: ...stic pipeline or the pipeline has insulated liner 5 10 Preparation for operation Strictly check the installment and wirings before it gets into operation It shall be pointed out that the instrument including the sensor and converter has been fully adjusted calibrated with actual flow and inspected under strict measures All shipped units are certified No further adjustments are required when put it...

Страница 9: ...fore attempting to install and operate the Pmag 6 3 1 Analog output The loop may be powered from the transmitter itself Resistance in the loop must be 750ohms or less 6 3 2 Digital output The digital output if set frequency mode generates an output signal from 0 to 5000Hz Max proportional to flow rate if set in pulse mode generates an output signal in relation to totaled volume increasing The sign...

Страница 10: ...on may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Please refer to the following safety messages before performing an operation preceded by this symbol 8 2 WARNINGS Explosions could result in death or serious injury Verify that the operating atmosphere of the flowtube an...

Страница 11: ...preferred 90 rotation 6 Fasten the 4 screws that attach the LOI to the main circuit assembly 7 Replace the LOI cover 8 5 DATA ENTRY The LOI keypad has no numerical keys Enter numerical data using the following procedure 1 Access the appropriate function 2 Use to highlight the digit you want to enter or change 3 Use or to change the highlighted value For numerical data or toggles through the digits...

Страница 12: ...st of configuration menu as shown here next Press the or keys to select the desired menu then press the key to access Pmag Setting 8 6 DISPLAY PAGE The Pmag has three pages to display data and status press or to change page If there is no alarm this page will not appear Page 12 of 24 ...

Страница 13: ...m the display will be as shown here next press the key to exit and confirm the selection press the key to exit and delete the selection 8 7 1 3 Total Units Total Units specifies the counter display unit Default m3 Range L Litri m3 Metri cubi G galloni Press the key from run mode the display will be as shown here next With or select the counter display unit Press to confirm the display will be as s...

Страница 14: ...ress the key to access To access the menu System may need to enter the correct password The default password 0100 After entering you can change the password Note If forget password can not access the menu 8 7 2 1 Language Allows menu language selection Default English Press the key from run mode the display will be as shown here next Press to confirm the display will be as shown here next press th...

Страница 15: ... key to exit and confirm the selection press the key to exit and delete the selection 8 7 2 2 3 Max Limit Whenthe measurevariationislowerthanMaxLimit orhigherbutwithalowertimeperiod than thatsetinLimitTime s themeasureisnotdetected When the measurevariationis higher than MaxLimit andwithahighertimeperiodthanthatsetinLimitTime s the measureisdetected Default 0 0 Range 0 0 9 9 Press the key from run...

Страница 16: ...xit and confirm the selection press the key to exit and delete the selection 8 7 2 3 Pulse Output Press the key to enter the submenu Pulse Output 8 7 2 3 1 Freq Max Hz Sets the maximum frequency in relation to Qmax The digital output is active as a frequency output only when the parameter Liter Pulse is set to 0 0 Default 2000 0 Range 100 0 5000 0 Press the key from run mode the display will be as...

Страница 17: ...fault Active L LOW Range Active L LOW Active H HIGH Press the key from run mode the display will be as shown here next With or select the parameter setting Press to confirm the display will be as shown here next press the key to exit and confirm the selection press the key to exit and delete the selection 8 7 2 4 RS485 Output Press the key to enter the submenu RS485 Output 8 7 2 4 1 RS Protocol Se...

Страница 18: ... to exit and delete the selection 8 7 2 4 4 Parity Sets the RS485 output Parity Default NONE Range EVEN ODD NONE Press the key from run mode the display will be as shown here next With or select the parameter setting Press to confirm the display will be as shown here next press the key to exit and confirm the selection press the key to exit and delete the selection 8 7 2 4 5 Stop Bit Sets the RS48...

Страница 19: ... password can not access the menu 8 7 2 5 2 Clear Total Reset totalizer Default NO Range NO YES Press the key from run mode the display will be as shown here next With or select the parameter setting Press to confirm the display will be as shown here next press the key to exit and confirm the selection press the key to exit and delete the selection 8 7 2 5 3 FWD Preset Predetermines the positive t...

Страница 20: ...e as shown here next press the key to exit and confirm the selection press the key to exit and delete the selection 8 7 3 Calibrations Calibration Press the key from run mode then press the key to select Calibration and press the button to enter 8 7 3 1 Zero Trim Zero flow measurement calibrate The sensor must be full and the flow stopped Default NO Range YES NO Press the key from run mode the dis...

Страница 21: ...op Trim 8 7 3 3 1 4mATrim Performscalibrationof4mA Procedure connecttoanalogoutput terminals amilliammeter insert thedetected currentmeasurement thesystemwillperformanautocalibrationfunction Deafult 4 000 Range 3 000 5 000 Press the key from run mode the display will be as shown here next With or change the digit with moves the cursor Press to confirm the display will be as shown here next Press t...

Страница 22: ... exit and delete the selection 8 7 4 Test Test Press the key from run mode then press the key to select Test and press the button to enter 8 7 4 1 Loop Test Test the analog output range Default 12 Range 4 0 20 0 Press the key from run mode the display will be as shown here next With or change the digit with moves the cursor 8 7 4 2 Pulse Test Test the frequency output range Default 1000 Range 1 0 ...

Страница 23: ...m Process Noise In some circumstances process conditions themselves can cause the meter output to be unstable The basic procedure for addressing a noisy process situation is outlined below Complete them in order When the output attains the desired stability no further steps are required 1 Change coil drive to 33 Hz 2 Increase the damping 3 Activate signal processing If the basic steps for troubles...

Страница 24: ...formity to the Company procedure Quality Control Manager Production and check date Pmag Factory test certificate Products supplied by the Company are guaranteed for a period of 12 twelve months from delivery date according to the conditions specified in our sale conditions document The Company can choose to repair or replace the Product If the Product is repaired it will mantein the original term ...

Отзывы: