background image

17

Downloading Options

[499] [Installer’s Code] [499] Initiate PC-Link (Local Downloading)

[803] Skyroute  Programming

08 Fire
09 Supervisory
11 Burglary
12 Hold-up
13 Gas
14   Heat
15   Medical
16   Panic
17   Emergency

[01]

Zone 1-4 Reporting Codes
Default

Default

00

I_____I_____I  Zone 1

00

I_____I_____I Zone 5 (not used)

00

I_____I_____I  Zone 2

00

I_____I_____I Zone 6 (not used)

00

I_____I_____I  Zone 3

00

I_____I_____I Zone 7 (not used)

00

I_____I_____I  Zone 4

00

I_____I_____I Zone 8 (not used)

[06] Skyroute Configuration Options (1-8)

Default

Option ON

Option OFF

OFF

I_____I

Option 1

A Channel Selected

A Channel Not Selected

ON

I_____I

Option 2

B Channel Selected          B Channel Not Selected

OFF

I_____I

Option 3

Home System Only           Not in Home System Operation

OFF

I_____I

Options 4 to 8

For Future Use

[07]

Home SID Number
0000

I_____I_____I_____I_____I

This is the SID (in Hex) of the cellular service that is available on the current channel.

[10]

Skyroute Test Time
9999

I_____I_____I_____I_____I    0000-2359 (in Military Time)

[11]

Test Transmission Day Mask
Default

Option ON

Option OFF

OFF

I_____I

Option 1

Test on Sunday

Disabled

OFF

I_____I

Option 2

Test on Monday

Disabled

OFF

I_____I

Option 3

Test on Tuesday

Disabled

OFF

I_____I

Option 4

Test on Wednesday

Disabled

OFF

I_____I

Option 5

Test on Thursday

Disabled

OFF

I_____I

Option 6

Test on Friday

Disabled

OFF

I_____I

Option 7

Test on Saturday

Disabled

OFF

I_____I

Option 8

For Future Use

Содержание Skyroute UT

Страница 1: ...Installation Manual...

Страница 2: ...one Line Monitor TLM 10 4 3 Swinger Shutdown 10 4 4 Skyroute Programming Sections 803 11 Activating the Skyroute Transceiver 12 Calling Connect 24 12 Skyroute Transceiver Trouble Supervision 12 Skyrou...

Страница 3: ...rogrammable zone attributes Normally closed single EOL Audible Alarm Output 700mA Supervised Bell Output current limited at 3 amps 12VDC Steady or Pulsed Output EEPROM Memory Does not lose programming...

Страница 4: ...ng PC5400 serial interface module or viewed with the LCD5500Z keypad and DLS 1 software Uploading and downloading capability Antenna 3 5 dB gain TNC connector Extension Kits available LAE 3 The 3 Foot...

Страница 5: ...or applying AC to the panel Step 2 Mounting the Skyroute Transceiver The Skyroute Transceiver can be mounted in the upper right hand corner of the panel cabinet through the knock out The Skyroute Tra...

Страница 6: ...erminal Descriptions Battery Connection A 12V 7Ah rechargeable battery is used as a backup source of power in the event of an AC power failure The battery also provides additional current when the pan...

Страница 7: ...UX the negative side to PGM1 PGM2 operates similarly to PGM1 If more than 50 mA of current are required a relay must be used For a list of the programmable output options please see section the PGM Ou...

Страница 8: ...el communicator to telephone lines intended for use with a fax machine These lines may incorporate a voice filter which disconnects the line if anything other than fax signals are detected resulting i...

Страница 9: ...t with the mounting bracket Remove the antenna from the Skyroute module and connect the extension cable to the TNC connector on the module Secure the antenna to the TNC connector mounted on the Extens...

Страница 10: ...Decimal Data A set number of programming boxes are allotted for each section requiring decimal data e g codes telephone numbers If a digit is entered for each program box the panel will automatically...

Страница 11: ...iately display all the information programmed in that section Use the arrow keys to scroll through the data being displayed Scroll past the end of the data displayed or press the key to exit the secti...

Страница 12: ...eiver SID System ID Sub Section 07 The chart below lists the different System ID for each of the territories For proper activation of the Skyroute Transceiver the correct SID for the territory that yo...

Страница 13: ...when the Skyroute Transceiver is on stand by ready to transmit mode Troubles are indicated when LED5 flashes more than once every second Shown below is the number of flashes used to indicate each tro...

Страница 14: ...09 System Trouble Output The PGM output will activate when any of the selected trouble conditions are present It will deactivate when all the selected trouble conditions are cleared The PGM attribute...

Страница 15: ...wer NOTE If you program more than one PGM output as the same output type e g if PGM1 and PGM2 are both programmed as 19 Command Output 1 the settings for output attributes 1 2 and 5 must be the same T...

Страница 16: ...When the keypad is again operational the default is complete Restore Panel to Default Programming Section 999 4 8 Installer s Lockout Installer code If Installer s Lockout is selected a hardware defa...

Страница 17: ...M 2 015 Third System Option Code Default Option ON OFF Section ON I________I 7 TLM Enabled TLM Disabled 370 Communication Variables Default Section 003 I_______I_______I_______I Swinger Shutdown Alarm...

Страница 18: ...N I_____I Option 2 B Channel Selected B Channel Not Selected OFF I_____I Option 3 Home System Only Not in Home System Operation OFF I_____I Options 4 to 8 For Future Use 07 Home SID Number 0000 I_____...

Страница 19: ...to 78 if 00 is entered then that reporting code is disabled If FF is in the section then the reporting code is enabled FF is the default value 30 Alarm Reporting Codes Zones 1 8 Default Default FF I__...

Страница 20: ...__I General System Trouble Restore FF I_____I_____I Fire Trouble Restoral FF I_____I_____I General System Supervisory Restore 77 Miscellaneous Maintenance Restoral Reporting Codes FF I_____I_____I Pho...

Страница 21: ...20 Skyroute UT Antenna Cable Installation...

Страница 22: ...Z3 COM COM Z2 Z4 RING TIP R 1 T 1 EGND PGM 1 2 SI S0 Connection for PC Link Max Min Rx Tx Status Indicator Signal Strength Indicator LED 1 LED 2 LED 3 LED 4 LED 5 GRN RED BLK YEL COM BELL OUT BELL IN...

Страница 23: ...AUX AC YEL GRN Z1 Z3 COM COM Z2 Z4 RING TIP R 1 T 1 EGND PGM 1 2 SI S0 Connection for PC Link Max Min Rx Tx Status Indicator Signal Strength Indicator LED 1 LED 2 LED 3 LED 4 LED 5 GRN RED BLK YEL CO...

Страница 24: ...PC580 BELL AUX AC YEL GRN Z1 Z3 COM COM Z2 Z4 RING TIP R 1 T 1 EGND PGM 1 2 SI S0 Connection for PC Link Max Min Rx Tx Status Indicator Signal Strength Indicator LED 1 LED 2 LED 3 LED 4 LED 5 GRN RED...

Страница 25: ...t Ground Rod PC580 BELL AUX AC YEL GRN Z1 Z3 COM COM Z2 Z4 RING TIP R 1 T 1 EGND PGM 1 2 SI S0 Connection for PC Link Max Min Rx Tx Status Indicator Signal Strength Indicator LED 1 LED 2 LED 3 LED 4 L...

Страница 26: ...Bell Positive Siren Trigger Bell always to ground and Bell switch to on alarm With this configuration Zx1 will be trigger every time the Bell is activated ORG RED BLK Bell Bell GND Zx COM BRG GND 120...

Страница 27: ...ed Null Zone Not used Delay 1 BAzz BHzz Yes Delay 2 BAzz BHzz Yes Instant BAzz BHzz Yes Interior BAzz BHzz Yes Delay H A BAzz BHzz Yes Interior H A BAzz BHzz Yes 24 Hr Burglary BAzz BHzz Yes Standard...

Страница 28: ...ower Supply Trouble YP00 YQ00 TLM Trouble Code via Skyroute LT00 General System Supervisory Restore ET00 ER00 General System Trouble Restore YX00 YZ00 TLM Restoral LR00 FTC Fail FTC Restoral YC00 YK00...

Страница 29: ......

Страница 30: ...erson purporting to act on its behalf to modify or to change this warranty nor to assume for it any other warranty or liability concerning this product In no event shall Sur Gard Ltd be liable for any...

Отзывы: