Operating Instructions – Electronic Motor DRC.-..-DAC
9
Transmitting individual parameters via AS-Interface
Communication with AS-Interface Double Slave GLK31A
"Read request"
Once the CTT2 service "Write request" has been executed correctly, you can use the
service 0x10
hex
"Read request" to call the response telegram of the CTT2 service
previously executed.
Select index 0x02
hex
and length 0x09
hex
.
• If this service is properly transmitted to the double slave, the GLK31A double slave
replies with the response telegram 0x50
hex
"Read response OK" and the data.
• If errors occur, the GLK31A double slave sends the response telegram 0x90
hex
"Read response not OK" (for error codes, refer to the AS-Interface specification).
• If the response data of the DRC inverter are not available yet, the GLK31A double
slave sends a response with error code "Busy" = "4" after the read access. The AS-
Interface master must read the data again.
Example:
Request and OK response of the DRC inverter concerning the previous change of the
fixed setpoint value n4 (parameter
10096.38
)
"Read request" service:
The slave replies after the system-related transmission times for parameters.
"Read response OK" response telegram:
CTT2 service
Code
Index Length
0x10
0x02
0x09
Code 0x10 =
Read request
Index 0x02 =
MOVILINK
®
parameter service
Length 0X09 =
Length of the MOVILINK
®
protocol
CTT2 service
MOVILINK
®
protocol
Code
Address-
ing
Manage-
ment
Sub-
index
High
index
Low
index
MSB
data
Data
Data
LSB
data
0x50
0x00
0x32
0x26
0x27
0x70
0x00
0x00
0x00
0x00
Code 0x50 =
Read response OK
Management 0x32 =
Write parameter => no MOVILINK
®
error
Addressing 0x00 =
Addressing the command PCB because this is where the parameter is stored
Subindex 0x26 =
Subindex of parameter fixed setpoint n4 (10096.38) 38
dec
= 0x26
High index 0x27 =
High value of the index
Low index 0x70 =
Low value of the index
=> Index of the parameter = 10096
dec
= 0x2770
hex
The value 0x2770
hex
is written on the high index and low index bytes.
Data MSB 0x00
If the MOVILINK
®
service has been executed correctly, the data byte value is
0x0 = 0
dec
Data 0x00
Data 0x00
Data LSB 0x00