1.0 General information

Every Model 231RS has been calibrated and tested before shipment to guarantee performance 
of all pressure ranges. 

The  Model  231RS  has  field  selectable  unidirectional  and  bidirectional  pressure  ranges, 
configurable  0  to  5  VDC,  0  to  10  VDC  ,  and  1  to  5  VDC  output,  true  two-wire  4  to  20  mA 
output, and auto-zero capability. Each unit is factory calibrated to the highest pressure range. 
The range label on the side of the unit indicates the factory calibrated range. 

Reminder:

 

Your 

application’s highest line pressure should be less than or equal to the highest pressure 
range of the 231RS range code you selected when you purchased the 231RS. See Range 
Codes in table below. (Range codes also listed on inside of housing cover).

Model 231RS pressure transducers sense differential pressure and convert this difference 
in pressure to a proportional high level analog output for unidirectional and bidirectional 
pressure ranges.  

Your Model 231RS Multi-Sense pressure transducer has been ordered in one of the following 
versions: 

231RS w/ Conduit

231RS w/ Cable

231RS w/ Armored Cable

is shipping with the following:

Version

Unidirectional

Bidirectional

RS1

5, 10, 25, 50, psid

±

5, 

±

10, 

±

20, 

±

50, psid

RS2

7.5, 15, 37.5, 75 psid

±

7.5, 

±

15, 

±

37.5, 

±

75 psid

RS3

10, 20, 50, 100 psid

±

10, 

±

20, 

±

50, 

±

100 psid

RS4

15, 30, 75, 150 psid

±

15, 

±

30, 

±

75, 

±

150 psid

RS5

25, 50, 125, 250 psid

±

25, 

±

50, 

±

125, 

±

250 psid

Conduit Version
(231GRSX3MX)

Cable Version
(231GRSX4MXXX)

Armored Cable Version
(231GRSXAJXXX)

Item

Qty. Item

Qty. Item

Qty.

Housing

1 Housing

1

Housing

1

Pressure transducers

2 Pressure Transducers

2

Pressure Transducers

2

User Manual

1 Cable Assemblies

2

Cable Assemblies

2

User Manual

1

User Manual

1

Содержание Multi-Sense 231RS

Страница 1: ...Model 231RS Operating Instructions Setra Systems Inc 159 Swanson Road Boxborough MA 01719 800 257 3872 www setra com ...

Страница 2: ...unting 4 2 5 Installation procedures 4 3 0 Electrical installation 7 3 1 Electrical termination Wiring 2 wire 4 to 20 mA and Remote zero 7 3 2 Electrical terminations Wiring 3 wire 0 to 5 0 to 10 1 5VDC and Remote zero 8 3 3 Remote sensors installation 9 4 0 Configurations 13 5 0 Return products for repair 14 6 0 Warranty limitation of liability 15 ...

Страница 3: ...housing cover Model 231RS pressure transducers sense differential pressure and convert this difference in pressure to a proportional high level analog output for unidirectional and bidirectional pressure ranges Your Model 231RS Multi Sense pressure transducer has been ordered in one of the following versions 231RS w Conduit 231RS w Cable 231RS w Armored Cable is shipping with the following Version...

Страница 4: ...SSURE SENSOR Match up the high pressure sensor to the high pressure electrical terminals and the low pressure sensor to the low pressure electrical terminals Otherwise the performance may not meet the product linearity specifications Moisture precautions The Model 231RS is provided with a 0 875 DIA conduit opening for electrical termination intended for a 1 2 I D conduit connection This opening mu...

Страница 5: ...Valve B Low side valve 1 Valves not included Pipe Pipe Figure 1 Model 231RS Conduit version P N 231GRSX3MXXX Outline drawing Figure 2 1 98 50 3 4 0 10 2 5 56 141 2 6 0 152 4 2 0 50 8 R 0 1 2 5 0 35 8 Front view Side view 21 95 2x 5 16 131 1 1 56 39 6 1 220 30 99 1 240 0 95 31 50 24 1 1 2 Conduit Opening Bottom view 0 864 ...

Страница 6: ...RS Armored Cable Version P N 231GRSXAJXXX Outline Drawing Figure 3 2 0 50 8 1 22 31 1 66 42 2 6 0 152 4 5 56 141 2 0 35 8 8 R 0 1 2 5 1 98 50 3 4 0 10 2 4 87 5 08 129 1 56 39 6 5 16 131 1 1 2 Conduit Opening 0 95 24 1 123 6 Front view Side view Bottom view ...

Страница 7: ...emote Zero Model 231RS when configured as a current output transducer is a true 2 wire 4 20 mA current output device and delivers rated current into any external load of 0 250 ohms When configured as a 4 20 mA current output device the current flow is in one direction only PLEASE OBSERVE POLARITY WARNING Damage may result on the unit if AC power is applied when the output switch is configured in p...

Страница 8: ... 30 VDC 18 30 VAC nominal output power supply Note The Zero terminals connected to digital output provide a contact closure relay for automatic reset to zero pressure by the monitoring system CAUTION ZERO input is for dry contact do no apply voltage to ZERO Terminals The optional remote zero is a normally open relay wired between COM and REMOTE ZERO terminals In order to initiate ZERO function the...

Страница 9: ... sensor to the low pressure electrical terminals Otherwise the performance may not meet the product linearity specifications 2 Install a 1 2 conduit fitting into the remote sensor top cover and fasten the retaining nut 3 Feed wires from a flexible conduit through the remote sensor top cover fasten the wires to terminals 4 Screw on the top cover 5 Fit conduit into conduit fitting and tighten condui...

Страница 10: ...ion CAUTION Reverse excitation will permanently damage unit Please follow wiring instructions carefully Figure 6 Dimensional Drawing 1 40 35 48 3 61 91 74 3 4 HEX 1 4 NPT 1 62 41 22 1 68 42 57 in mm 1 2 inch conduit opening Conduit adapter Terminal block GND OUT COM EXC 4 3 2 1 ...

Страница 11: ... high HI pressure electrical terminals and the low LO pressure sensor to the low pressure electrical terminals Otherwise the performance may not meet the product linearity specifications 2 Attach the cable provided to the 3 Pin Packard connector on the remote sensor 3 Feed the cable through the PG fitting on the bottom of the unit and tighten the fitting 4 Remove the terminal blocks from the circu...

Страница 12: ...NSOR respectively Match up the high pressure sensor to the high HI pressure electrical terminals and the low LO pressure sensor to the low pressure electrical terminals Otherwise the performance may not meet the product linearity specifications 2 Attach the cable provided to the 3 Pin Packard connector on the remote sensor 3 Feed the cable through the PG fitting on the bottom of the unit and tight...

Страница 13: ...ctrical connections Electrical termination for power supply 3 wire voltage output and 2 wire true 4 20 mA current output and remote zero wiring BAR PSI Jumper selectable engineering units in Bar ranges or PSI A REV NORM A REV Analog Reverse When in reverse mode the output increases when the differential pressure decreases and decreases as pressure increases NORM When in Normal mode output increase...

Страница 14: ...Shipping and billing instructions Full description of the malfunctions Identify any hazardous material used with the product NOTES Please remove any pressure fittings and plumbing that you have installed and enclose any required mating electrical connectors and wiring diagrams Allow approximately 3 weeks after receipt at Setra for the repair and return of the unit Non warranty repairs will not be ...

Страница 15: ...herwise specified in a manual or warranty card or agreed to in a writing signed by a SETRA officer SETRA pressure and acceleration products shall be warranted for one year from date of sale The foregoing warranty is in lieu of all warranties express implied or statutory including but not limited to any implied warranty of merchantability for a particular purpose SETRA s liability for breach of war...

Страница 16: ...Setra Systems Inc 159 Swanson Road Boxborough MA 01719 800 257 3872 www setra com SS231RS REV E 07 2019 ...

Отзывы: