Operating Instructions

DPT267 and DPT267MR Series Low Pressure Transducers

1.

 

GENERAL INFORMATION

Every Model 267 and Model 267MR (Multi-Range) has been tested and calibrated before shipment.
Specific performance specifications are listed on Page 9 of this Guide.
The Model 267 is single range only. The Model 267MR has field selectable range capability. The
267MR is factory calibrated for the highest pressure range. The range label on the cover of the unit
indicates the factory-calibrated range. Should the 267MR be re-ranged in the field, the Multi-Range
labels are included.
Setra Systems 267 and 267MR pressure transducers sense differential or gauge (static) pressure and
convert this pressure difference to a proportional high level analog output for both unidirectional and
bidirectional pressure ranges. Two output versions are offered: A voltage output, configurable:  0 to 5
VDC or 0 to 10 VDC, and a current output: 4 to 20 mA
Sections 1 through 4 and 7 through 9 of this Guide apply to both Model 267 and 267MR. Section 5
refers to the Model 267 only. Section 6 refers to the Model 267MR only.

2.0 MECHANICAL INSTALLATION

2.1 Media Compatibility

Model 267 and 267MR transducers are designed to be used with air or non-conducting gases

.

Use with liquids or corrosive gases will damage the unit.

2.2 Environment

The operating temperature limits of the 267 and 267MR are as follows:

Operating Temperature

0°F to +150

°

F (-18°C to +65

°

C)

Compensated Temperature Range +40°F to +150

°

F (+5°C to +65

°

C)

2.3 Pressure Fittings

The Model 267 and 267MR can be supplied with three different pressure fitting configurations:

1. 3/16” O.D. Barbed Brass Pressure Fittings – Typically installed with 1/4” push-on tubing.
2.  1/4” NPT Brass Pressure Fittings – Typically installed with mating NPT male fitting.
3.  Static Pressure Probe – Installed on the duct by drilling a 7/16” hole in the duct at the desired

mounting location, inserting the pressure probe into the duct, and mounting the 267 onto the duct
with the mounting tabs.

For the 3/16” O.D. and 1/4” NPT pressure fittings, both the positive (high) pressure port and the
reference (low) pressure port are located on the bottom of the unit, labeled “HIGH” and “LOW”
respectively. For best results (shortest response times), 3/16” I.D. tubing is suggested for tubing
lengths up to 100 feet long, 1/4” I.D. for tubing lengths up to 300 feet, and 3/8” I.D. for tubing lengths
up to 900 feet.

The static pressure probe is the positive (high) pressure port located on the back of the unit. The
reference (low) pressure port is located on the bottom of the unit and can be used for differential pressure
measurements.

3.0 ELECTRICAL INSTALLATION

Wiring is through a 1/2” conduit opening or an optional PG-9 or PG-13-5 or 9-pin D-sub connector. (See
Section 3.2 for instructions on wiring the 9 pin D-sub connector.) Both current and voltage output units are
reverse wiring protected.

Содержание DPT267 Series

Страница 1: ...ng temperature limits of the 267 and 267MR are as follows Operating Temperature 0 F to 150 F 18 C to 65 C Compensated Temperature Range 40 F to 150 F 5 C to 65 C 2 3 Pressure Fittings The Model 267 and 267MR can be supplied with three different pressure fitting configurations 1 3 16 O D Barbed Brass Pressure Fittings Typically installed with 1 4 push on tubing 2 1 4 NPT Brass Pressure Fittings Typ...

Страница 2: ...e Excitation and Output are commoned on the circuit see Diagram 2 The excitation output specifications are Excitation Output 9 to 30 VAC 11 5 to 42 VDC 0 to 5 VDC 12 to 30 VAC 13 to 42 VDC 0 to 10 VDC The 267MR has field selectable 0 5 or 0 10 VDC output See Section 6 0 for switch settings to determine whether the voltage output is set to 0 5 or 0 10 VDC The 267 has either a 0 5 VDC or 0 10 VDC ou...

Страница 3: ... 3 3 3 Current Output Units 1 2 Conduit Opening PG 9 or Pg 13 5 Electrical Termination The Model 267 and 267MR is a two wire loop powered 4 to 20mA current output unit see Diagram 5 The current flows into EXC terminal and returns back to the power supply through the EXC Terminal see Diagram 6 The power supply must be a DC voltage source with a voltage range between 9 and 30 measured between termin...

Страница 4: ...d a 250ohm load The current output 9 pin D sub connector pin designations are shown in Diagram 8 CONNECTION 9 pin D sub Connector Electrical Termination EXCITATION 4 OUTPUT 9 Diagram 7 Diagram 8 3 5 4 20 mA Circuit Diagram Minimum Supply Voltage VDC 9 0 02 x resistance of receiver plus line Maximum Supply Voltage VDC 30 0 004 x resistance of receiver plus line If the current loop has a current lim...

Страница 5: ...er both zero and span adjustments are accessible under the cover of the unit below and to the right of the terminal strip The 267 and 267MR transducer is calibrated in the vertical position at the factory mounting tabs vertical 4 1 Voltage Output Zero Adjustment While monitoring the voltage between the positive output SIG and common GND and with both pressure ports open to atmosphere the zero may ...

Страница 6: ...utput Apply 5 00 W C adjust span to 20 mA 0 08mA 5 0 MODEL 267 OPTIONAL LCD DISPLAY The 267MR is available with an optional 3 1 2 digit LCD display The LCD is adjusted at the factory prior to shipment The LCD is connected to the zero and span adjustment potentiometers Therefore adjustment of the zero and span according to Section 4 adjusts the LCD display 6 0 Multi Range Operation Model 267MR only...

Страница 7: ...ability and Hyseresis Thermal Effects Compensated Range F C 40 to 150 5 to 65 Zero Span Shift FS F C 0 033 0 06 Maximum Line Pressure 10 psi in positive or negative Overpressure 10 psi in positive or negative direction Warm up Shift 0 1 FS Total Position Effects Unit is factory calibrated at 0g effect in the vertical position Range Zero Offset FS G 0 to 0 1 W C 2 1 0 to 1 W C 0 22 0 to 5 W C 0 14 ...

Отзывы: