The effects of decomposition of unstable fluids should be considered by the user when
placing this device in service.

*

The pressure transducer has no means of draining or venting, this must be performed by
another component in the end users system.

*

Pressure range must be compatible with the maximum pressure being measured.

*

Pressure media must be compatible with the transducer/transmitter wetted parts listed in
these instructions.

*

Liquid must not be allowed to freeze in the pressure port.

*

The gasket must be fitted under the electrical connector.

MECHANICAL INSTALLATION

Mounting

: Pressure Transducer is designed to be attached by the coupling thread only.

 

Omni-

directional, self supported directly into the pipework.  Use a 19mm AF (3/4") wrench on the hexagon
provided to apply a maximum torque of 11.6  lb.ft (15.8Nm).

  

The Customer must ensure that the

pressure seal is suitable for the application.  If in doubt contact Setra Systems.

ELECTRICAL INSTALLATION

All types with the CE Mark include suppression devices providing transient protection to EN 61000-4-2
and EN 61000-4-4.  Conformity with the requirements of the CE mark only applies when connection is
made with Setra Systems approved cable, see APPROVED CABLE section, and is connected as
shown below:-

Millivolt Output Transducers

:  Four wire shielded cable should be used with the cable shield

connected to the instrumentation ground.  The cable shield should not be connected to the transducer
body.

High Output Transducers

:  The shield of the cable must be grounded at the instrumentation end.  If

a ‘ground loop’ problem is encountered when the body of the unit is grounded by the piping it is
permissible to remove the cable shield from the instrumentation ground.

APPROVED CABLE

Setra Systems uses cables comprising 2, 3 or 4 color-coded wires, enclosed by an aluminised polyester
shield where the shield is in contact with a separate drain wire.  The outer shield is chrome PVC and
overall diameter is approximately 0.20in.

OPERATION

Having installed the transducer as instructed, it is ready for use. The transducer should not be removed
while the system is at pressure

Before applying power, check that the correct polarity and excitation

levels are being applied.  See Table 1 for electrical connections.

CALIBRATION

Transducers are calibrated at time of order:

Code A

Absolute datum

Code G

Gauge datum vented to atmosphere via the electrical connector or cable

Code C

Compound datum

Содержание 526

Страница 1: ...Installation Guide MODELS 522 526 Pressure Transducers 560550 0087 Rev A 1 800 257 3872 TOLL FREE 1 978 264 0292 FAX www Setra com Web Site ...

Страница 2: ...Setra offers a complete line of products for these industries Industrial HVAC Test Measurement Barometric Ultra High Purity Sanitary ...

Страница 3: ...y potential hazards associated with their storage handling or use The products which our Company supplies may be classified as Electrical Electro Mechanical and Electronic equipment These products are tested and supplied in accordance with our published specifications or individual special requirements that are agreed in writing at time of order They are constructed so as not to affect adversely t...

Страница 4: ...CE mark only applies when connection is made with Setra Systems approved cable see APPROVED CABLE section and is connected as shown below Millivolt Output Transducers Four wire shielded cable should be used with the cable shield connected to the instrumentation ground The cable shield should not be connected to the transducer body High Output Transducers The shield of the cable must be grounded at...

Страница 5: ...mpany carefully packed and accompanied by a detailed failure report See RETURN TO FACTORY WETTED PARTS 316 and 17 4 PH stainless steel plus Nickel Braze to BS1845 NK3 HTN2 SERVICING The transducer cannot be repaired locally and if damaged should be returned to Setra Systems with the following 1 Name and phone number of person to contact 2 Shipping and billing information 3 Full description of malf...

Страница 6: ... will occur until cleared It may ultimately be returned to you and subject to a transportation charge MAINTENANCE Routine Inspection Not required except for periodic inspection of the cable and connector to ensure that these are neither damaged nor softened by incompatible liquid ...

Страница 7: ...E R Y B W DRAIN 526BP UA YES MOLDED IMMERSIBLE R Y B W DRAIN 526BP A2 YES CONDUIT LEADS R W G BK 526XX B1 YES 8 4P A B D A C B D 526XX B3 YES 10 6P A B E A C B E 526XX C2 YES LARGE DIN 1 2 E 1 2 3 E 526XX UA YES MOLDED IMMERSIBLE R BL DRAIN R W Y DRAIN 526XX UA YES MOLDED IMMERSIBLE R BL DRAIN R W Y DRAIN 526XX A1 YES CONDUIT LEADS R BK G R BK W G OUTPUT SUPPLY VOLTAGE OUTPUT SUPPLY VOLTAGE BP 0 t...

Отзывы: