 Series 522 / 526 are designed and manufactured in accordance with sound engineering

practice as defined by the Pressure Equipment Directive 97/23/EC.  This product must not be used as a
“safety accessory” as defined by the Pressure Equipment Directive, Article 1, Paragraph 2.1.3. The CE
Mark on the unit does not relate to the Pressure Equipment Directive.

INTRODUCTION

The Series 522 / 526 pressure transducers use molecularly bonded high output strain gauges to provide
100mV output for full range pressure, when used with a 10V d.c. power supply.

Series 522 / 526 high output pressure transducers and transmitters are fitted with an  ASIC providing
various optional (at time of order) voltage outputs, and a 4-20mA current output capable of being used
in control and indicating loops without further amplification.

Series 522 / 526 with the CE Mark conform with the essential protection requirements of the EMC
Directive 89/33/EEC amended by certified type testing to EN 50082-2 and EN 50081-1.

HAZARDOUS PRODUCTS

The Consumer Protection Act of 1987, Section 6 of the Heath and Safety at Work Act 1974 and the
Control of Substances Hazardous to Health Regulations 1988 require that we advise recipients and
users of our products of any potential hazards associated with their storage, handling or use.

The products which our Company supplies may be classified as Electrical, Electro-Mechanical and
Electronic equipment.

These products are tested and supplied in accordance with our published specifications or individual
special requirements that are agreed in writing at time of order.  They are constructed so as not to affect
adversely the safety of persons and property when properly installed, maintained and used by qualified
personnel, in the applications for which they were designed and manufactured.

Conformity with the requirements of the CE mark only applies when the installation
conditions described in these instructions have been met.  For units supplied without
a cable assembly connection to the transducer must be accomplished using Setra
Systems approved cable.  See APPROVED CABLE section.

GENERAL

*

Transducer should not be subjected to greater than the maximum allowable pressure
listed on label and the following operating temperature specifications:

Compensated Temperature Range:

   

-5°F to +180°F (-20°C to +80°C)

Operable Temperature Range:

Electrical Connection Code E1           -40° to +260°F (-40°C to +125°C)
Electrical Connection Code N1          -5°F to +180°F (-20°C to +80°C)
Electrical Connection Code NA

-5°F to +125°F (-20°C to +50°C)

*

Transducer should not be subjected to mechanical impact.

*

In the event of fire the end user must ensure that the system pressure is vented to a safe
area.

Содержание 526

Страница 1: ...Installation Guide MODELS 522 526 Pressure Transducers 560550 0087 Rev A 1 800 257 3872 TOLL FREE 1 978 264 0292 FAX www Setra com Web Site ...

Страница 2: ...Setra offers a complete line of products for these industries Industrial HVAC Test Measurement Barometric Ultra High Purity Sanitary ...

Страница 3: ...y potential hazards associated with their storage handling or use The products which our Company supplies may be classified as Electrical Electro Mechanical and Electronic equipment These products are tested and supplied in accordance with our published specifications or individual special requirements that are agreed in writing at time of order They are constructed so as not to affect adversely t...

Страница 4: ...CE mark only applies when connection is made with Setra Systems approved cable see APPROVED CABLE section and is connected as shown below Millivolt Output Transducers Four wire shielded cable should be used with the cable shield connected to the instrumentation ground The cable shield should not be connected to the transducer body High Output Transducers The shield of the cable must be grounded at...

Страница 5: ...mpany carefully packed and accompanied by a detailed failure report See RETURN TO FACTORY WETTED PARTS 316 and 17 4 PH stainless steel plus Nickel Braze to BS1845 NK3 HTN2 SERVICING The transducer cannot be repaired locally and if damaged should be returned to Setra Systems with the following 1 Name and phone number of person to contact 2 Shipping and billing information 3 Full description of malf...

Страница 6: ... will occur until cleared It may ultimately be returned to you and subject to a transportation charge MAINTENANCE Routine Inspection Not required except for periodic inspection of the cable and connector to ensure that these are neither damaged nor softened by incompatible liquid ...

Страница 7: ...E R Y B W DRAIN 526BP UA YES MOLDED IMMERSIBLE R Y B W DRAIN 526BP A2 YES CONDUIT LEADS R W G BK 526XX B1 YES 8 4P A B D A C B D 526XX B3 YES 10 6P A B E A C B E 526XX C2 YES LARGE DIN 1 2 E 1 2 3 E 526XX UA YES MOLDED IMMERSIBLE R BL DRAIN R W Y DRAIN 526XX UA YES MOLDED IMMERSIBLE R BL DRAIN R W Y DRAIN 526XX A1 YES CONDUIT LEADS R BK G R BK W G OUTPUT SUPPLY VOLTAGE OUTPUT SUPPLY VOLTAGE BP 0 t...

Отзывы: