Low Voltage Disconnection:

 (LVD) of the batteries is provided to prevent deep 

discharge of the battery. Automatic reconnection occurs when battery voltage 
recovers. Battery Current Drain is less than 2mA.

Trickle Charge:

 Trickle Charge to the battery is always present. When the battery 

voltage is below the LVD (Low voltage disconnect) re­connect voltage (<10V and 
the mains power or auxiliary power is available, the battery will be charging at 
0.8A. When the battery voltage is sufficient (>10.5V for first power up, 11.5V and 
11.7V for subsequent reconnection with and without mains respectively) the LVD 
will connect the battery and allow float charging at 10A/15A (ST20­III/ST35­III). 
The Trickle Charge feature is provided to allow “very” flat batteries to be charged 
at a rate, which will extend their life.

Remote Battery Isolate Switch:

 The ST­III series power supplies allow for 

connection to a remotely positioned switch that provides a manual disconnection 
of the battery from the loads and  the main charger. When the switch contacts are 
closed, the battery will be isolated from the loads.

NOTE: When the battery is isolated from the loads using the battery isolate 
switch it will NOT charge at the 10/15 A rate even if the mains is connected 
to the power supply. In this condition it will ONLY charge at the Trickle 
charge rate.

Front Panel Indicators:

 The ST­III series power supplies have 3 indicators 

visible on the front fascia.

Mains(GREEN) – is illuminated when mains power is present.

Battery(ORANGE) – is illuminated when the battery is connected to the loads.

Fault(RED) – is illuminated when there is a fault with the power supply.

Battery fuse Blown1

    

Battery connected reverse polarity2

     

Shut down condition (UV and OT)3

        

Main PCB micro controller malfunction4

Notes

1.

Flashing 1s ON, 1s OFF.

2.

Solid ON.

3.

Flashing 1s ON, 1s OFF, with no battery connected the power supply 
may be in hiccup mode which will cause the indication to flash with 
random duty cycle and frequency.

4.

Fault Led= Solid On, All other leds = OFF, irrespective of actual mains or 
LVD status.

Auxiliary Power Input:

 The power supply terminal “Aux In +VE” provides an 

alternative option for powering of the load and float charging of the batteries when 
mains voltages are not present. This input is to be powered by a suitable  +12V 
system. (i.e. CAR).  The voltage of the auxiliary power source should not exceed 

7

Содержание ST-III Series

Страница 1: ...ST III Series POWER SUPPLY Owner s Manual Please read the Installation section of this manual before installing the product...

Страница 2: ...or suitability of the information contained in this manual Setec Pty Ltd accepts no liability for any loss or damage which may occur as a result of improper or unsafe use of its products Warranty is...

Страница 3: ...nctional Diagram 6 ST III Basics 6 Installing The ST III Power Supply 9 Wiring Up 10 Servicing 12 Specifications 13 Battery Management 14 Frequently Asked Questions 15 Anderson Plug Operation 16 After...

Страница 4: ...not cause short circuits Remove any personal metal adornment such as a chain watch or ring which could cause short circuits and personal injury CAUTION Failure to observe these instructions properly m...

Страница 5: ...and powering of the load from an external 13 8V DC power source The units are fully enclosed ready for direct wall mounting All connections are at the rear of unit providing convenient wiring and ins...

Страница 6: ...the load current plus battery current is equal or less than the maximum output current The charging current will be reduced in situations where the difference between the rated output current and the...

Страница 7: ...loads NOTE When the battery is isolated from the loads using the battery isolate switch it will NOT charge at the 10 15 A rate even if the mains is connected to the power supply In this condition it w...

Страница 8: ...of power supply Serious power supply damage or internal explosion may occur If a flat 12 volt battery has to be charged using the generators 12 volt output it should first be disconnected from the pow...

Страница 9: ...CAUTION Do not install unit in same compartment as batteries or flammable material such as petrol Ensure that the installation meets the ventilation requirements above Mechanical and Mounting Depth o...

Страница 10: ...put Connections Connectors are 0 8 x 6 3mm QC tabs Use mating QC connector suitable for cable size Connector pin out is shown below 10 F4 F5 F6 F7 F8 FBATT L1 L2 L3 L4 L5 VBATT Fuse Panel ve terminals...

Страница 11: ...cedures Battery should be disconnected as per the following steps 1 Turn power supply off and all 12 volt equipment connected to power supply 2 Disconnect negative battery terminal connection to Batt...

Страница 12: ...ause short circuits Remove any personal metal adornment such as a chain watch or ring which could cause short circuits and personal injury Do not charge non rechargeable batteries Failure to do so may...

Страница 13: ...ection ST20 III 20A to 25A load battery current ST35 III 35A to 38A load battery current Battery Current Limit 10A 1A ST20 III 15A 1A ST35 III Battery Connect Disconnect Connect 10 50 0 2V Input Mains...

Страница 14: ...s float charging current VFloat 13 65V the unit utilises a storage mode voltage VStore 13 25V when no activity on the battery is detected This extends the battery life During store mode the unit exits...

Страница 15: ...age and may not provide the voltage required to run the ST III ST III When the Aux IN terminal is used from the tow car is this a straight through connection to the battery The AUX in provides another...

Страница 16: ...Trailer Plug Operation To wire the ST III to the car follow the diagrams for the different plug types For more information please contact your dealer 16...

Страница 17: ...After sales Service WARNING Do not disassemble modify or repair the unit Doing so may result in electric shocks or fire Repairs and After sales Service Consult your Setec dealer 17...

Страница 18: ...im under this warranty you must a Ensure the product is installed by a suitably qualified person and is installed in accordance with this Owner s Manual and any applicable Australian Standard b The pr...

Страница 19: ...000000 Rev 5A DESIGNED AND MANUFACTURED IN AUSTRALIA...

Отзывы: