background image

9(22)

Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | [email protected] | www.servodan.com

GB

Ultrasonic sensors detects movement.
In US only mode, load will be turned on when Ultrasonic sensors 
detects movement.

PIR only:
If the monitored space is free of obstacle or has high level of 
air

fl

 ow or the detection area is needed to be well speci

fi

 ed. 

For example, a small-scale of

fi

 ce with air-conditioning, a small 

conference room, etc.
In PIR only mode, load will be turned on when PIR sensors 
detects movement.

The detector is equipped with 2 led’s, a red and a green.
The LED’s are used to indicate wherever the movement was 
detected by PIR or ultrasound.
Red LED indicates PIR and the green indicates ultrasound.

Sens:
The sensitivity (Sens.) function is used to reduce the sensitivity 
against air 

fl

 ow.

Meter:
The meter setting is used to reduce the sensitivity of the 
ultrasonic detection range. 

Time:
The time setting is used to set the off-delay, before the load 
switches OFF, after the last detected movement.

Lux:
The lux setting is used to set the light level, for when below, the 
load can switch ON.

Trouble shooting

Problem:

  Load does not turn on

Possible cause:
  1. Incorrect wiring.
  2. The ambient light level is too high.

Proposed solution:
  1. Refer to wiring diagrams (See 

Fig. 4 - Fig. 6

) and check if the  

    load is malfunctioned.
  2. Check the set Lux value and adjust it if necessary (to a 
    higher lux value).

Problem:

  Load does not turn off

Possible cause:
  1. Off delay time is too long.
  2. Detector has false triggering. 
  3. Incorrect wiring. 

Proposed solution :
  1. Check the set off delay and adjust it if necessary (to a lower 
   value).
  2. Check for any objects, which may cause false triggering and 
    remove them from the detectors range.
  3. Refer to wiring diagrams (See 

Fig. 4 - Fig. 6

).

Problem:

  Red LED does not turn on

Possible cause:
  1. PIR is not chose as the triggering method.
  2. The movement is out of the PIR detection range.
  3. The lens mask is used an it coveres the movement.

Proposed solution:
  1. Choose PIR sensor as the triggering method.
  2. The movement should be in the valid detection range (ø8m).
  3. Remove or reposition the lens maske

Problem:

  Green LED does not turn on

Possible cause:
  1. Ultrasonic sensor is not chose as the triggering method.
  2. The movement is out of the detection range.

Proposed solution:
  1. Choose ultrasonic sensor as the triggering method.
  2. The movement should be in the valid detection range (10x16 m).

Problem:

 Flase 

triggering 

Possible cause:

There are heat sources, air

fl

 ow, highly re

fl

 ective objects or any 

objects which may be swayed in the wind within the detection 
range.

Proposed solution: 

Avoid aiming the detector toward any heat sources, such as 
air conditioning, electric fans, heaters or any highly re

fl

 ective 

surfaces. Make sure there are no swaying objects within the 
detection range.

NOTE:
Effects that might have in

fl

 uents on ultrasonic detection:

Air

fl

 ow:

Air

fl

 ow can cause false triggering of the ultrasonic sensor.

If air 

fl

 ow is thought to cause false triggering, try setting the Sens. 

Knob to ON.
This function will reduce the sensitivity of ultrasonic sensor 
approx. 10% ~ 40% according to the strength of the air

fl

 ow.

Sound wave absorbing materials:
The sensitivity and range can be affected by the materials such 
as carpet, sound absorbable materials, curtains, etc

Wiring:
A reverse connection in between N and L will cause lower 
sensitivity of ultrasonic sensor sensitivity and also reduce the 
detection range.

Содержание 41-800

Страница 1: ...er som store vindues eller glaspartier forårsage uønsket aktivering Fig 1 Det anbefales at sensoren loftmonteres Hvis sensoren monteres hængende fra loftet mindskes ultralydens rækkevidde Område Den anbefalede monteringshøjde for denne sensor er 2 3 m og 2 5 m er den optimale monteringshøjde PIR sensorens rækkevidde kan nå op på ø8 m og ultralydssensorens er en oval på 8 x 10 m for små bevægelser ...

Страница 2: ...kræftes det af LED erne som tændes Derpå vender tilstedeværelsessensoren tilbage til Auto tilstand Hvis indlæring af aktuel lux er uden for intervallet 10 1000 lux vil tilstedeværelsessensoren efter 10 sek indikere dette ved at LED erne blinker hurtigt i 5 sek for at indikere at indlæring af aktuel lux mislykkedes I så fald bruges følgende værdier Luxniveau over 1000 Tilstedeværelsessensoren bruge...

Страница 3: ...ng 1 Kontroller den indstillede udkoblingstid og juster den om nødvendigt til en lavere værdi 2 Kontroller for genstande der kan forårsage forkert detektering og fjern dem fra sensorernes rækkevidde 3 Se ledningsføringsdiagrammer Fig 4 6 Problem Rød LED tændes ikke Mulig årsag 1 PIR er ikke valgt som detekteringsmetode 2 Bevægelsen er uden for PIR rækkevidden 3 Linseafdækningen bruges og den dække...

Страница 4: ...ælde af fejl eller driftsforstyrrelser Tekniske data Indgang Forsyningsspænding 230 V 10 50 Hz Effektforbrug 2 W Udgang Relæ NO 230 V μ 10 A Potentiale fri Belastning Glødelamper 2300 W Lysrør ukompenseret 1200 VA Halogenlamper 2300 W Sparepærer 58 x 18 W Maks kompensationskapacitet 140 μF Maks indkoblingsstrømspids 165 A 20 m sek Preformance Lux område 10 1000 lux Udkoblingstid 1 30 min Rækkevidd...

Страница 5: ...n ø8 m 50 m2 Ultrasonic Small Motion 10 x 8 m Oval 66 m2 Ultrasonic Body Motion 16 x 10 m Oval 138 m2 Top view US 10m US 8m 360 PIR ø4m PIR ø8m US 10m US 16m Open office 14m 8m Classroom Conference room 12m 7 5m 10m 8m Fig 2 14m 8m 20 overlap Fig 3 120 47 60 34 30 109 64 Fig 4 Jumper L N D2 D1 R M S 41 800 Presence detector PLUS L N Fig 1 2m 2m 2m Air duct W W ...

Страница 6: ...es Warning Installation and assembly of electrical equipment must be carried out by qualified electricians Contact a qualified electrician in the event of fault or breakdown Reserving the right to make changes Achtung Einbau und Montage elektrischer Geräte dürfen nur durch Elektrofachkräfte erfolgen Wenden Sie sich bei Störungen bzw Ausfall an einen Elektrofachkraft Änderungen vorbehalten Avertiss...

Страница 7: ...can cause unwanted activation Fig 1 It s recommended that the detector is mounted on the ceiling If the detector is mounted suspended from the ceiling the ultrasonic range is decreased Location The recommended installation height of this detector is 2 3m and 2 5m is the optimal mounting height The detection range of PIR sensor can reach up to ø8m and ultrasonic sensor is an oval shape of 8m x 10m ...

Страница 8: ...Then presence detector returns to Auto mode If Learn actual lux is out of the range of 10 1000 lux the LED s in the presence detector will after 10sec flash quickly for 5sec to indicate that Learn actual lux was unsuccessfully In that case the following values will be used Lux level is above 1000 lux the presence detector will use 1000 lux as lux setting Lux level is below 10 lux the presence dete...

Страница 9: ...e 2 Check for any objects which may cause false triggering and remove them from the detectors range 3 Refer to wiring diagrams See Fig 4 Fig 6 Problem Red LED does not turn on Possible cause 1 PIR is not chose as the triggering method 2 The movement is out of the PIR detection range 3 The lens mask is used an it coveres the movement Proposed solution 1 Choose PIR sensor as the triggering method 2 ...

Страница 10: ...ault or breakdown Technical data Input Power supply 230 V 10 50 Hz Power consumption 2 W Output Relay contact NO 230 V μ 10 A potential free Load Incandescent lamps 2300 W Fluorescent tubes not Compensated 1200 VA Halogen incandescent lamps 2300 W Energy saving bulbs 58 x 18 W Max compensation capacity 140 μF Max inrush current 165 A 20 m sec Performance Lux range 10 1000 lux Time delay 1 30 min D...

Страница 11: ... Platzierung Der Sensor reagiert auf Wärme und Bewegung in der Umgebung Vermeiden Sie es den Sensor in der Nähe von Wärmequellen wie Herden elektrischen Heizgeräten Lüftungssystemen oder Gegenständen die durch Luftströme bewegt werden zu platzieren Auch stark reflektierende Oberflächen wie große Fenster oder Glasflächen können zu einer unerwünschten Aktivierung führen Fig 1 Eine Deckenmontage des ...

Страница 12: ...wird wird er nach 2 Minuten automatisch verriegelt und ggf geänderte Einstellungen werden gespeichert Reset Nullstellen Durch Drücken der Taste Reset werden alle mit der IR Fernbedienung vorgenommenen Einstellungen gelöscht Der Präsenzmelder läuft gemäß den mit den Tasten vorgenommenen Einstellungen Test Jedes Mal wenn eine Bewegung erkannt wird wird die Last 2 Sekunden lang eingeschaltet Lux Fest...

Страница 13: ...muss Beispielsweise ein kleines Büro mit Klimaanlage ein kleiner Sitzungsraum usw Im Modus PIR wird die Last eingeschaltet wenn die PIR Sensoren eine Bewegung erkennen Der Sensor verfügt über 2 LEDs eine rote und eine grüne Die LEDs werden verwendet um anzuzeigen dass mit PIR oder Ultraschall eine Bewegung erkannt wurde Die rote LED zeigt PIR an die grüne Ultraschall Sens Die Funktion für die Empf...

Страница 14: ...en absorbieren Die Empfindlichkeit und die Reichweite kann von Materialien wie Teppichböden schallabsorbierenden Materialien Gardinen usw beeinträchtigt werden Kabelführung Eine umgekehrte Verbindung zwischen N und L verursacht eine geringere Empfindlichkeit gegenüber Ultraschall und reduziert die Reichweite Wartung Schmutz beeinträchtigt die Funktion des PIR Teils des Präsenzmelders daher muss di...

Страница 15: ... réagissent aux mouvements et aux variations de température dans l environnement concerné Eviter de positionner le détecteur à proximité d éléments dégageant de la chaleur tels que fours appareils de chauffage électriques bouches de ventilation ou d aération objets mobiles sous l effet de flux d air etc De même les surfaces fortement réfléchissantes telles que les grandes baies vitrées peuvent déc...

Страница 16: ...ent il se verrouille automatiquement à l issue de 2 minutes et les éventuels réglages modifiés sont sauvegardés Reset remise à zéro Un appui sur Reset efface tous les réglages effectués à l aide de la télécommande IR Le détecteur de présence fonctionne alors selon les réglages effectués à l aide des boutons Test L éclairage s allume pendant deux secondes chaque fois qu un mouvement est détecté Lux...

Страница 17: ...ts ou encore que la zone de détection doit être délimitée avec précision Par exemple un bureau climatisé relativement petit une petite salle de réunion etc En mode PIR only l éclairage s allume lorsque les détecteurs PIR décèlent des mouvements Le détecteur est muni de deux DEL une rouge et une verte Ces DEL servent à indiquer si les mouvements ont été détectés par PIR ou par ultrasons La DEL roug...

Страница 18: ...nores La sensibilité et la portée peuvent être influencées par des matériaux comme les moquettes et les tapis les matériaux absorbant les ondes sonores les rideaux etc Câblage Une inversion entre N et L causera une baisse de la sensibilité aux ultrasons et réduira la portée Entretien La saleté nuit au bon fonctionnement de l élément PIR du détecteur de présence La lentille du détecteur doit donc ê...

Страница 19: ...kt reflekterande ytor som stora fönster eller glaspartier kan ge upphov till oönskad aktivering Fig 1 Sensorn bör monteras i taket Monteras sensorn hängande från taket minskas ultraljudets räckvidd Område Den rekommenderade monteringshöjden för denna sensor är 2 3 meter och 2 5 meter är den optimala monteringshöjden PIR sensorns räckvidd kan nå upp till 8 meter i diameter och ultraljudssensorns ov...

Страница 20: ...ar genomförts bekräftas det av lysdioderna som tänds Därefter återgår närvarosensorn till automatiskt läge Om inlärningen av aktuell lux ligger utanför intervallet 10 1 000 lux kommer närvarosensorn efter 10 sekunder att visa detta genom att lysdioderna blinkar snabbt i fem sekunder Detta betyder att inlärningen av aktuell lux misslyckades I så fall används följande värden Luxnivå över 1000 Närvar...

Страница 21: ...för lång 2 Felaktig detektering 3 Kablarna har dragits fel Lösningsförslag 1 Kontrollera den inställda urkopplingstiden och justera den vid behov till ett lägre värde 2 Kontrollera föremål som kan orsaka felaktig detektering och flytta bort dem från sensorernas räckvidd 3 Se kabeldragningsscheman Fig 4 6 Problem Röd lysdiod tänds inte Möjlig orsak 1 PIR har inte valts som detekteringsmetod 2 Rörel...

Страница 22: ...iftstörningar Tekniska data Ineffekt Matarspänning 230 V 10 50 Hz Effektförbrukning 2 W Uteffekt Relä NO 230 V μ 10 A Potentialfri Belastning Glödlampor 2 300 W Okompenserat lysrör 1 200 VA Halogenlampor 2 300 W Energisparlampor 58 x 18 W Max kompensationskapacitet 140 μF Max inkopplingsströmtopp 165 A 20 m sek Prestanda Luxområde 10 1 000 lux Urkopplingstid 1 30 min Räckvidd 360 Ultraljud 10 x 16...