SHANGHAI SERMATEC ENERGY TECHNOLOGY CO.,LTD
- 26 -
Warning
When wiring, make sure that there is no dangerous voltage at the
connection point.
Notes
All wiring is connected to the terminal from the outside through
the wire hole at the bottom of the energy storage device. After
wiring, please seal the wire hole with fireproof mud.
4.7.6 Load side wiring
•
Use the phase sequence table to measure to ensure that the
phase sequence of the connected cable is positive
sequence
;
•
Use a multimeter to measure and confirm that the cable
connected to the terminal does not have current
;
•
AC load output distribution switch 2qf A / B / C / N phase is
respectively connected to a / B / C / N phase of the load, including the
connection of PE line.
Warning
When wiring, make sure that there is no dangerous voltage at the
connection point.
Notes
All wiring is connected to the terminal from the outside through
the wire hole at the bottom of the energy storage device. After
wiring, please seal the wire hole with fireproof mud.
4.7.7 Micro source side wiring
•
Use the phase sequence table to measure to ensure that the
phase sequence of the connected cable is positive
sequence
;
•
Use a multimeter to measure and confirm that the cable
connected to the terminal does not have current
;
•
AC load output distribution switch 3Qf A / B / C / N phase is
respectively connected to a / B / C / N phase of the load, including the