installation, dismantling, maintenance and any other related process of the Product.  

安装需注意事项:为了将间接雷击的风险降到最低,在设计系统时应避免形成回路。为避免人为因素造成线缆

与连接器、线缆与接线盒连接不良或损坏,影响产品电气安全或使用寿命,建议产品在安装、拆卸、维护及任何其

它相关过程中,施加在线缆和连接器、线缆和接线盒之间的作用力不得大于

60N

 

Pay attention to the direction of the wire when installing the modules. It should be connected along the wire 

direction to avoid bending the wire. 

注意组件安装时的导线方向,应顺着导线方向连接,避免导线折弯。

 

2

Electrical Connection 

连接

 

The  Direct  Current  (DC)  generated  by  the  PV  system  can  be  converted  to  Alternating  Current  (AC)  and 

connected to the public power grid. Different regions may have different policies, laws and regulations to stipulate 

the installation and grid-connection requirements of PV systems. Therefore, during the design, installation and grid-

connection of PV system, please comply with the local policies, laws and regulations. 

光伏系统产生的直流电可以转换成交流电,并与公共电网相连。不同地区可能有不同的政策和法律法规来规定

光伏系统的安装要求和并网要求,因此在光伏系统的设计、安装和并网过程中,请遵守当地的政策和法律法规要求。

 

PV modules can obtain different current and voltage outputs through series connection and parallel connection. 

Read  this  installation  manual  carefully  before  electrical  connection  and  installation.  Please  design  and  connect 

according to the current and voltage required by customers. Before connection, please ensure that the connection 

part is free from corrosion, and keep it clean and dry. 

光伏组件通过串联和并联的连接方式可以获得不同的电流和电压输出,在进行电气连接和安装前,请仔细阅读

本安装手册,并依据客户所要求的电流和电压进行设计和连线。连接前请确保连接部分无腐蚀,保持清洁和干燥。

 

Different  types  of  modules  cannot  be  connected  in  series.  Modules  connected  in  series  should  ensure  the 

consistency of their current. The voltage of the module string should not exceed the allowable system voltage value, 

which can be found on the nameplate or datasheet of the module. 

不同类型的组件产品不能串联在一起,串联在一起的组件产品要保证其电流的一致性,组件串的电压不能超过

所允许的组件系统电压值,该电压值可以在组件的铭牌或者规格书里找到。

 

Seraphim modules are provided with stranded copper cables with a cross sectional area of 4mm² which are 

rated for 1500V dc, connectors with rated current greater than 15A 

and are UV resistant. All other cables used to 

connect the DC system should have a similar (or better) specification. Seraphim recommend that all cables are run 

 

赛拉弗

 

组件提供横截面积为

  4mm² 

的铜绞线,额定电压为

  1500V  dc

,连接器为额定电流大于

15A

,,抗紫外

线。

 

用于连接直流系统的所有其他电缆都应具有类似(或更好)的规格。

  Seraphim 

建议将所有电缆铺设在适当的

导管中,并远离容易积水的区域。

 

The maximum number of modules in series depends on the system design, the type of converter used and the 

environmental  conditions.  In  general,  the  maximum  number  (N)  of  PV  modules  in  series  can  be  calculated  by 

dividing the maximum system voltage by the open circuit voltage of the relevant   Solar PV modules. When designing 

the   Solar PV system, it is necessary to take into account the characteristic that the voltage of the   Solar PV module 

changes  with  the  temperature.  Considering  the  voltage  increase  caused  by  temperature  drop  in  extreme 

environment in winter, the maximum series connection number of    Solar PV modules can be calculated by the 

following formula. 

串联组件的最大数目取决于系统设计、所用变频器的类型和环境条件。通常情况下,最大的串联太阳能光伏组

件数量(

N

)可以通过系统最大电压除以相关太阳能光伏组件开路电压的方式计算而获得,但是在设计太阳能光伏

系统时,一定要考虑到太阳能光伏组件的电压随着温度变化而变化的特性。考虑到冬季里极端环境下温度下降造成

Содержание SRP 6MA Series

Страница 1: ...Name SERAPHIM SOLAR SYSTEM CO LTD 1 2 Add No 1 2 Hengyao Road Henglin Town Wujin District Changzhou City P R China Installation Guide for SERAPHIM photovoltaic module 2021 V3 3...

Страница 2: ...TY 3 3 UNLOAD TRANSPROTATION STORAGE 4 3 1 MAKERS ON OUTER PACKAGING 5 3 2 UNLOADING WARNNING 6 3 3 SECONDARY TRANSPORT AND WARNING 7 3 4 STORAGE 8 4 UNPACKING SAFETY 28 5 1 INSTALLATION SAFETY 30 5 2...

Страница 3: ...ite at https www hg energy group com as these lists are updated on a regular basis https www seraphim energy cn 2 In the event of any inconsistency among different language versions of this document t...

Страница 4: ...onal electrical standards 2 Seraphim recommends that PV module installation is conducted by personnel who have been professionally trained in PV system installation Operation by personnel who are not...

Страница 5: ...id such as water to extinguish the fire 5 Do not install or handle modules when they are wet or during periods of high wind 6 At the installation site take care to keep modules and in particular their...

Страница 6: ...more people with nonslip gloves and both hands 2 6 Do not lift modules by their wires or junction box 7 Do not handle the modules over head or stack the modules 8 Do not place excessive loads on the m...

Страница 7: ...lled modules must be kept dry not expose to rain or moisture 3 1 3 Modules in carton are fragile which must be handled with care 3 1 4 The packaging must be transported upright 3 1 5 Do not step on th...

Страница 8: ...Two people shall support at the two sides of the righting carton gently to place it on the relatively flat position of the project site 2 3 2 2 Use a forklift to remove the module pallets from the tr...

Страница 9: ...tion make sure that the package is fixed securely to the shipping platform without movement Do not Stack more than two layers on truck 2 3 3 3 Only one layer stacking is only allowed for transport at...

Страница 10: ...amage or collapse of the modules caused by moisture in the packaging 5 If pallets are stored temporarily outside then place a protective covering over the pallet to protect it from direct weathering a...

Страница 11: ...65 9 7 9 77 9 83 9 88 Open Circuit Voltage Voc 48 6 2 48 8 2 49 1 2 49 4 2 49 7 2 49 9 2 50 1 2 Short Circuit Current Isc 9 8 4 9 88 4 9 93 4 9 98 4 10 05 4 10 11 4 10 16 4 Maximum Series Fuse 25 25 2...

Страница 12: ...96 4 9 03 4 9 12 4 9 20 4 Maximum Series Fuse 20 20 20 20 20 20 20 20 Rated Power Pmp 340 345 350 Power Sorting 0 4 99W 0 4 99W 0 4 99W Power Tolerance 3 3 3 Maximum Power Voltage Vmp 37 9 38 1 38 3...

Страница 13: ...10 36 10 44 10 52 10 60 10 68 10 76 Open Circuit Voltage Voc 43 9 2 44 10 2 44 20 2 44 30 2 44 50 2 44 70 2 44 9 2 45 10 2 Short Circuit Current Isc 10 73 4 10 82 4 10 91 4 10 99 4 11 08 4 11 17 4 11...

Страница 14: ...it Current Isc 9 65 4 9 73 4 Maximum Series Fuse 25 25 SRP XXX E11A HV SRP XXX E11A XXX 340 380 Electrical Characteristics Rated Power Pmp 340 345 350 355 360 365 370 375 Power Sorting 0 4 99W 0 4 99W...

Страница 15: ...30 335 340 345 350 355 360 365 Power Sorting 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W Power Tolerance 3 3 3 3 3 3 3 3 Maximum Power Voltage Vmp 37 8 38 1 38 4 38 7 39 39 3 39 6...

Страница 16: ...wer Voltage Vmp 41 8 42 0 40 78 41 03 41 29 41 55 41 81 42 05 Maximum Power Current Imp 10 77 10 84 12 88 12 92 12 96 13 13 04 13 08 Open Circuit Voltage Voc 50 10 2 50 30 2 49 02 2 49 33 2 49 4 2 49...

Страница 17: ...40 445 450 Power Sorting 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W Power Tolerance 3 3 3 3 3 3 3 3 Maximum Power Voltage Vmp 34 34 2 34 4 34 6 34 8 34 08 34 18 34 28 Maximum Powe...

Страница 18: ...urrent Imp 9 22 9 28 9 36 9 42 9 52 9 71 9 8 9 9 Open Circuit Voltage Voc 43 8 2 44 1 2 44 3 2 44 6 2 44 7 2 44 5 2 44 7 2 44 9 2 Short Circuit Current Isc 9 69 4 9 75 4 9 83 4 9 89 4 10 4 10 21 4 10...

Страница 19: ...ies Fuse 20 20 20 20 20 20 20 20 Rated Power Pmp 350 355 Power Sorting 0 4 99W 0 4 99W Power Tolerance 3 3 Maximum Power Voltage Vmp 39 3 39 6 Maximum Power Current Imp 8 91 8 97 Open Circuit Voltage...

Страница 20: ...35 6 Maximum Power Current Imp 8 26 8 36 8 44 8 53 8 60 8 69 8 76 8 85 Open Circuit Voltage Voc 40 7 2 40 9 2 41 2 2 41 4 2 41 7 2 41 9 2 42 2 2 42 4 2 Short Circuit Current Isc 8 80 4 8 89 4 8 97 4 9...

Страница 21: ...W 0 4 99W 0 4 99W 0 4 99W 0 4 99W Power Tolerance 3 3 3 3 3 3 3 Maximum Power Voltage Vmp 32 4 32 6 32 8 33 0 33 2 33 4 33 6 Maximum Power Current Imp 9 11 9 21 9 30 9 40 9 49 9 58 9 68 Open Circuit V...

Страница 22: ...5 25 25 25 25 25 25 25 SRP xxx 6PA DG xxx 315 340 Electrical Characteristics Rated Power Pmp 315 320 325 330 335 340 Power Sorting 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W Power Tolerance 3 3 3...

Страница 23: ...e Voc 49 1 2 49 3 2 49 5 2 49 7 2 49 9 2 48 7 2 48 9 2 49 2 2 Short Circuit Current Isc 9 96 4 10 04 4 10 12 4 10 19 4 10 26 4 10 9 4 10 97 4 11 04 4 Maximum Series Fuse 25 25 25 25 25 25 25 25 SRP xx...

Страница 24: ...5 2 46 7 2 46 9 2 Short Circuit Current Isc 8 80 4 8 89 4 8 95 4 9 04 4 9 11 4 9 19 4 9 27 4 Maximum Series Fuse 20 20 20 20 20 20 20 SRP xxx BPB DG xxx 265 285 Electrical Characteristics Rated Power...

Страница 25: ...09 4 10 16 4 10 25 4 10 32 4 10 40 4 10 55 4 10 97 4 11 04 4 Maximum Series Fuse 25 25 25 25 25 25 25 25 Rated Power Pmp 430 435 440 445 450 525 530 535 Power Sorting 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0...

Страница 26: ...Maximum Power Voltage Vmp 34 7 35 35 2 33 6 33 8 34 34 2 34 4 Maximum Power Current Imp 9 52 9 58 9 66 10 27 10 36 10 45 10 53 10 62 Open Circuit Voltage Voc 41 1 2 41 4 2 41 6 2 40 6 2 40 8 2 41 2 4...

Страница 27: ...9 194 9 284 9 364 9 454 Maximum Series Fuse 25 25 25 25 25 25 25 25 Rated Power Pmp 360 365 370 375 485 490 495 500 Power Sorting 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W Power...

Страница 28: ...d Power Pmp 425 430 435 440 445 450 Power Sorting 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W 0 4 99W Power Tolerance 3 3 3 3 3 3 Maximum Power Voltage Vmp 43 8 43 9 44 1 44 3 44 4 44 6 Maximum Power Curr...

Страница 29: ...d Power Pmp 545 Power Sorting 0 4 99W Power Tolerance 3 Maximum Power Voltage Vmp 31 99 Maximum Power Current Imp 17 04 Open Circuit Voltage Voc 39 30 2 Short Circuit Current Isc 17 99 4 Maximum Serie...

Страница 30: ...2201104400002 DM6772201104400012 BM6604201102800003 DM6772201104400002 DM6772201104400012 BM6604201102800003 DM6772201104400003 DM6772201104400013 BM6604201102800004 DM6772201104400003 DM6772201104400...

Страница 31: ...is required to be level to ensure that the package can be placed stably avoiding sliding 5 Wear protective gloves during unpacking to avoid hand injury and fingerprints on the glass surface 6 Each mo...

Страница 32: ...cted from the system 7 During installation if PV modules are touched by bare hands there is a risk of scalding or electric shock 8 Do not hit or put excessive load on the front or back of PV modules t...

Страница 33: ...er than 1500Vdc This maximum voltage should not be exceeded at any time and as the voltage of the module increases above data sheet values at operating temperatures below 25 C then these need to be ta...

Страница 34: ...emisphere the PV modules should typically face north When selecting the installation location avoid areas with trees buildings or obstacles because these objects will form shadows on Solar PV modules...

Страница 35: ...landscape and portrait orientation however the impact of dirt shading the solar cells can be minimized by orienting the product in portrait Sunpro Power Avoid using a mounting method that will block t...

Страница 36: ...on guides or consult a reputable Solar installer or systems integrator Dust building up on the surface of the modules can impair module performance YuHuan Sunpro Solar recommends installing the module...

Страница 37: ...om building chimney and tree etc and even the partially shading such as the dirt snow and aerial wire etc should be avoided The generation gain is related to the ground reflectivity the module install...

Страница 38: ...n approved by Seraphim the modules will not continue to carry a valid warranty Modules shall not be subjected to wind or snow loads which is exceeding the maximum permissible designed loads and shall...

Страница 39: ...on install maintenance and safety Seraphim will not supply the related material for system installation 1 Screw Installation Each PV module has 8 mounting holes shown as drawing 1 The downward mechani...

Страница 40: ...tand a downward force of up to 5400 Pa 550 kg m2 or 2400 Pa 244 kg m2 according to where they are clamped Site specific loads such as wind or snow which may exert forces in a different way need to be...

Страница 41: ...Type 11 Type 12 Type 13 SRP XXX BPZ SRP XXX BPZ HV SRP XXX BMZ SRP XXX BMZ HV SRP XXX BMZ TB SRP XXX 6PA SRP XXX 6PA HV SRP XXX 6MA SRP XXX 6MA HV SRP XXX 6PB SRP XXX 6PB HV SRP XXX 6MB SRP XXX 6MB HV...

Страница 42: ...5400 180 480 5400 50 480 2400 1776 1755 1052 1038 50mm 200 500 5400 1916 1890 1909 1134 1133 1134 50mm 250 550 5400 200 500 5400 50 500 2400 2102 2073 2093 1134 1133 1134 50mm 270 570 5400 280 580 540...

Страница 43: ...e to the series of PV modules as listed below Table 2 The selection and installation of the clamps shall obey the requirement according to table 3 Otherwise the module may not satisfy the mechanical l...

Страница 44: ...42 Type Load Pa Clamp Length Installation Drawing Type1 150mm Type2 200mm 2400 2400 2400 2400 Type3 150mm Type4 200mm 2400 2400 2400 2400 Type5 2400 2400 200mm...

Страница 45: ...able to the series of PV modules as listed below Table 2 The selection and installation of the clamps shall obey the requirement according to table 3 Otherwise the module may not satisfy the mechanica...

Страница 46: ...44 Table 3 Type Load Pa Clamp Length Installation Drawing Type1 50mm Type2 50mm 5400 2400 5400 2400 Type3 50mm Type4 50mm 5400 2400 5400 2400 Type5 50mm 5400 2400...

Страница 47: ...sed However failure to comply with the above recommendations will result in a lowering of the load handling capabilities below the empirical value and product failure as a result of an overload situat...

Страница 48: ...2 Fig 3 Split J Box at module middle position for horizontal direction 3 Precautions To minimize risk in the event of an indirect lightning strike avoid forming loops when designing the system In orde...

Страница 49: ...modules cannot be connected in series Modules connected in series should ensure the consistency of their current The voltage of the module string should not exceed the allowable system voltage value...

Страница 50: ...the devices used in the system The modules must not be connected together to create a voltage that is higher than the permitted system voltage Product can be irreparably damaged if an array string is...

Страница 51: ...DC electricity whenever light falls on it similarly the inverter automatically turns ON as soon as there is sufficient energy from the solar array to efficiently convert this into grid quality AC powe...

Страница 52: ...tions must be followed to meet Seraphim warranty conditions 3 Bypass secondary If PV module part by shadow block which can lead to reverse voltage related to Solar cells PV modules in other unaffected...

Страница 53: ...r of strings in parallel Parallel module configurations fuse rating Isc Isc 5 Grounding All PV module frames and mounting brackets must be properly grounded in accordance with the applicable national...

Страница 54: ...1 Grounding by unused mounting holes 2 Other professional grounding devices The electrical contact points of all the above grounding methods should penetrate the anodized film of the aluminum frame PV...

Страница 55: ...s grade and adequate ventilation should be provided between the backplane and the mounting surface Different roof structure and installation will affect the fire safety performance of the building If...

Страница 56: ...to prevent electric shock Exposure of PV modules to sunlight will generate high voltages this is dangerous Please pay attention to safety when maintenance and it must be done by professionals Wear cut...

Страница 57: ...put and may cause hot spots So the surface of PV modules should be kept clean Maintenance work should be performed at least once six months or frequently Warning It should be carried out by trained pe...

Страница 58: ...back surface of the module normally does not need to be cleaned but in the event this is deemed necessary avoid the use of any sharp projects that might damage the penetrating the substrate material W...

Страница 59: ...TROUBLESHOOTING If the PV system does not work properly please inform your installer immediately It is recommended to perform a preventive inspection every six months please don t change any modules...

Отзывы: