Display Navigation Guide, TotalSense Series
Page 7 of 19
154-0042-0B
Analog Parameters
Parameter
Description
Selections
Functionality
Settings >
Analog
Output 1>
Source
Analog out 1
reading
(terminals O1 or
O2)
Default will be
set to first
available sensor
in this order:
CO2, TVOC, RH,
Temp, slider
None
No signal will be generated
CO2
CO2 reading will be output by analog output 1. Adjust
output scale in PPM in
RH
Relative humidity reading will be output by analog
output 1. Adjust output scale in % in
Temp
Temp reading will be output by analog output 1. Adjust
output scale in
o
F in
TVOC
TVOC reading will be output by analog output 1. Adjust
output scale in PPM in
Temp Slider
Slider reading will be output by analog output 1. Adjust
output scale in
o
F in
. Please note this
reading is in addition to a resistive reading that can be
read on “slider” terminals.
PID Temp
Sets the output to a PID controller using the
temperature setpoint as the baseline, adjust this
setpoint in
PID CO2
Sets the output to a PID controller using the CO2
setpoint as the baseline, adjust this setpoint in
PID Temp Set-
Point
Sets the output to a PID controller using the
temperature slider as the baseline, adjust this setpoint
in
Settings >
Analog
Output 1>
Min V
Min voltage
output for O1
0-10V
(default 0V)
This value corresponds to the lowest point on an analog
scale. For a 0-10V signal, set to 0V. For a 2-10V signal,
set to 2V. This will override any analog dip switch
settings.
Settings >
Analog
Output 1>
Max V
Max voltage
output for O1
0-10V
(default 10V)
This value corresponds to the highest point on an
analog scale. For a 0-10V signal, set to 10V. For a 0-5V
signal, set to 5V. This will override any analog dip switch
settings.
Settings >
Analog
Output 1>
Min A
Min current
output for O2
0-20mA
(default 4mA)
This value corresponds to the lowest point on an analog
scale. For a 4-20mA signal, set to 4mA. For a 0-20mA
signal, set to 0mA.
Settings >
Analog
Output 1>
Max A
Max current
output for O2
0-20mA
(default 20mA)
This value corresponds to the highest point on an
analog scale. For a 0-20mA or 4-20mA signal, set to
20mA.