Display Navigation Guide, TotalSense Series 

Page 7 of 19

 

154-0042-0B 

 

Analog Parameters 

Parameter 

Description 

Selections 

Functionality 

Settings > 

Analog 

Output 1> 

Source 

Analog out 1 

reading 

(terminals O1 or 

O2) 

 

Default will be 

set to first 

available sensor 

in this order: 

CO2, TVOC, RH, 

Temp, slider 

None 

No signal will be generated 

CO2 

CO2 reading will be output by analog output 1.  Adjust 
output scale in PPM in 

CO2

 

Settings

 

RH 

Relative humidity reading will be output by analog 
output 1.  Adjust output scale in % i

 

RH 

Settings

.

 

Temp 

Temp reading will be output by analog output 1.  Adjust 
output scale in 

o

in 

Temp

 

Settings

. 

TVOC 

TVOC reading will be output by analog output 1.  Adjust 
output scale in PPM in 

TVOC

 

Settings

Temp Slider 

Slider reading will be output by analog output 1.  Adjust 
output scale in 

o

in 

Slider

 

Settings

.  Please note this 

reading is in addition to a resistive reading that can be 
read on “slider” terminals. 

PID Temp 

Sets the output to a PID controller using the 
temperature setpoint as the baseline, adjust this 
setpoint i

Temp

 

Settings

PID CO2 

Sets the output to a PID controller using the CO2 
setpoint as the baseline, adjust this setpoint in 

CO2

 

Settings.

 

PID Temp Set-

Point 

Sets the output to a PID controller using the 
temperature slider as the baseline, adjust this setpoint 
in 

Temp

 

Settings

Settings > 

Analog 

Output 1> 

Min V 

Min voltage 

output for O1 

0-10V  

(default 0V) 

This value corresponds to the lowest point on an analog 
scale.  For a 0-10V signal, set to 0V.  For a 2-10V signal, 
set to 2V. This will override any analog dip switch 
settings. 

Settings > 

Analog 

Output 1> 

Max V 

Max voltage 

output for O1 

0-10V  

(default 10V) 

This value corresponds to the highest point on an 
analog scale.  For a 0-10V signal, set to 10V.  For a 0-5V 
signal, set to 5V. This will override any analog dip switch 
settings. 

Settings > 

Analog 

Output 1> 

Min A 

Min current 

output for O2 

0-20mA 

(default 4mA) 

This value corresponds to the lowest point on an analog 
scale.  For a 4-20mA signal, set to 4mA.  For a 0-20mA 
signal, set to 0mA.  

Settings > 

Analog 

Output 1> 

Max A 

 

Max current 

output for O2 

0-20mA 

(default 20mA) 

This value corresponds to the highest point on an 
analog scale.  For a 0-20mA or 4-20mA signal, set to 
20mA.   

Содержание TotalSense Series

Страница 1: ...54 0042 0B Rev Release Date By Description of Change ECR 0A NAK Initial Release 0B 6 10 2022 NJS Updates for engineering CI release Copyright 2022 All rights reserved This document contains Senva Sens...

Страница 2: ...ttings 10 PM Settings 10 RH Settings 11 Temp Settings 11 TVOC Settings 12 Slider Settings 12 Relay Settings 13 PIR Settings 14 Advanced Settings Diagnostics 15 Advanced Settings 15 Diagnostics 15 Air...

Страница 3: ...he up and down arrows for 5 seconds to unlock Figure 1 Default Home Display Figure 2 Sample Display If you see a lock icon hold the up and down arrows for 5 seconds to unlock To change any setting pre...

Страница 4: ...set each digit individually and press enter to move cursor to the left When all digits are set the value will be saved when enter is pressed again To view comms navigate to view comms in the main men...

Страница 5: ...size in PM Settings Readings over 999 will be shown as mg m3 Slider Setpoint Value corresponding to position of slider set point will be displayed in center Slider range can be adjusted in Slider Set...

Страница 6: ...2 reading Current CO2 reading will be displayed in PPM Temp reading Current Temp reading will be displayed in either o F or o C See Temp Settings RH reading Current RH reading will be displayed in PM...

Страница 7: ...int as the baseline adjust this setpoint in Temp Settings PID CO2 Sets the output to a PID controller using the CO2 setpoint as the baseline adjust this setpoint in CO2 Settings PID Temp Set Point Set...

Страница 8: ...re decreases Settings Analog Output 1 PID KP Proportional Coefficient 0 100 default 0 Sets the Proportional gain PID Coefficient Settings Analog Output 1 PID Ki Integral Coefficient 0 100 default 0 Se...

Страница 9: ...isabled Settings Air Quality Use PM Use PM in the Air Quality calculation Enabled Disabled Settings Air Quality Use VOC Use VOC in the Air Quality calculation Enabled Disabled Air Quality Settings Goo...

Страница 10: ...Disable Enable ABC Enable default Disable default if dual channel CO2 is selected Enable or disable ABC function for CO2 sensor calibration It is not recommended to disable this unless you are using...

Страница 11: ...as PM selected as a source in Analog Parameters RH Settings Parameter Description Selections Functionality RH Settings Offset RH offset 5 to 5 default 0 Adjust RH reading by up to 5 RH Settings Analog...

Страница 12: ...5000 g m3 default 0 g m3 This value corresponds to the lowest point on an analog scale for a TVOC reading This will correspond to any analog output that has TVOC selected as a source Analog Parameter...

Страница 13: ...100 00 default depends on source selection Based on full scale range of the selected sensor set the value above which the relay will activate For example if CO2 is selected its full available range is...

Страница 14: ...when this time has expired AND the turn off threshold is met Relay Settings Min Off Min off time 1 240s default 3s When relay de activates it will not activate again until this time has lapsed regard...

Страница 15: ...sult factory 00000010 EEPROM data corruption Consult factory 00000100 EEPROM write error Consult factory 00001000 Device is currently using factory defaults Reset to factory defaults Consult factory 0...

Страница 16: ...is will display several possible statuses in binary All zeros indicate no errors or warnings are present 00000001 Sensor hardware I2C fault Consult factory 00000010 Sensor error bad initialization ran...

Страница 17: ...nsor Data Error Consult factory 00000100 Sensor not ready Consult factory 00001000 Sensor fan speed warning Warning only No action necessary 00010000 Sensor fan failure Consult factory 00100000 Sensor...

Страница 18: ...000 g m3 3000 g m3 CO2 1200 PPM 1200 2000 PPM 2000 PPM Temp 64 79F 64 79F RH 30 60 30 60 10 90 The average air quality is calculated as follows for the sensors that have been enabled see Air Quality s...

Страница 19: ...ale factor 1 218 Data Source http aqt vru com emissions complete list of vocs Contamination Name Molecular Weight Scale factor ACETYLENE ACETYLEN 26 04 0 565 FORMALDEHYDE FORMALD 30 03 0 652 METHANOL...

Отзывы: