STVS1

230 VAC TRANSFORMER CONTROLLER WITH
ANALOGUE INPUT

switch).

13. 

Operate the controller via the external device output voltages.

Optional settings

The standard configuration of the output voltages is as indicated in 

Table 1

 below. 

However, because more than 5 output voltages are available, it is possible to adjust 
the 5 steps by changing the internal wiring. 

Voltage

0—10 VDC 

or external 

potentiometer 

positions (MTV or 

MTP)*

0 VDC

-

2 VDC 4 VDC 6 VDC

8 VDC

9.5 VDC

Wires

-

Regulated output [VAC]

Voltages***

0

80**

110

140

170

190

230

Unregulated output [VAC]

L1

0

230

230

230

230

230

230

*

 See also the operational diagram on page 5 for the corresponding voltages.

**

 Available but not connected.

If more than 5 output voltages are available, it is possible to adjust the 5 steps by changing the internal wiring.

VERIFICATION OF INSTALLATION

ATTENTION

Use only tools and equipment with non-conducting handles when working on 
electrical devices.

 After connecting the unit to the mains supply, the green LED on its cover should light 
up to indicate that the controller is supplied. 

 Safe operation depends on proper installation. Before start up, ensure the following:

 

The mains supply is connected correctly.

 

Protection is provided against electrical shock.

 

The cables are the appropriate size and fuse-protected.

 

There is sufficient air flow around the unit.

The controller is equipped with TK terminals to connect to the thermal contact 
integrated in the motor. When actuated (in case of an overheated motor), the 
thermal contact cuts the voltage supply to the motor and switches on the red LED  
to indicate that it does not work.

 

ATTENTION

The unit is supplied with electrical energy at voltages high enough to inflict personal 
injury or threat to health. Take the relevant safety measures. 

ATTENTION

Disconnect and confirm that there is no live current flowing to the unit before servicing.

 

ATTENTION

Avoid exposing the controller to direct sunlight!

Содержание STVS1 Series

Страница 1: ...STVS1 230 VAC TRANSFORMER CONTROLLER WITH ANALOGUE INPUT Mounting and operating instructions ...

Страница 2: ...ALOGUE INPUT Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 VERIFICATION OF INSTALLATION 8 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 ...

Страница 3: ...fect the product performance Make sure the work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts A...

Страница 4: ...STVS1 50L22 5 0 5 20 mm T 8 0 A H STVS1 75L22 7 5 6 32 mm T 12 5 A H STVS1100L22 10 0 6 32 mm T 16 0 A H STVS1130L22 13 0 6 32 mm T 20 0 A H INTENDED AREA OF USE Fan speed control of voltage controllable motors pumps and fans in ventilation systems For indoor use only TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Maximum motor current Imax 13 A Unregulated output 230 VAC Imax 2 A TK monitoring fo...

Страница 5: ...NS Wiring and connections L Power supply phase 230 VAC 50 60 Hz N Power supply neutral Pe Earth terminal Pe Earth terminal L1 Unregulated output line N1 Unregulated output neutral N1 Regulated output to motor neutral U Regulated output to motor line TK Input TK monitoring for thermal motor protection TK 0V Ground 12V Output 12 VDC Imax 50 mA V Digital output 12 VDC Imax 50 mA 0 VDC TK fault 12 VDC...

Страница 6: ...vice will get For example in a technical room the correct installation height can be of great importance 3 3 If maximum ambient temperature cannot be adhered to please provide extra forced ventilation cooling Not respecting the abovelisted rules can reduce service life and relieves the manufacturer of any responsibilities For metal enclosures above 7 5 A 4 Once secured in position the mounting scr...

Страница 7: ...P P P P P P P P P P P P P P P P P P P P P P P X1 X1 X1 X1 X1 X1 X1 X1 X1 1 1 1 1 X1 X1 1 X1 1 1 1 X1 1 1 1 1 1 1 X X X X X X X1 1 X1 X X X X1 X1 1 X1 X1 X1 X1 X1 1 1 X10 0K 0 0 0K 0K 0 0K 0K 0 0 0K K K K K K K K K K K K K 0K K 0K 0K 0 0 0 0K K K K K K K K K K 0K K K 0K 0K 0 0 0 0 0K K K K K K K K K 0K 0 0 0 0 0 0 0K K K K K K K K K 0 0 0 0 0 0 0K K K K K K 0K K K K 0K 0 0 0 0 0 0 0 0 0K K K K 0K 0...

Страница 8: ...ON ATTENTION Use only tools and equipment with non conducting handles when working on electrical devices After connecting the unit to the mains supply the green LED on its cover should light up to indicate that the controller is supplied Safe operation depends on proper installation Before start up ensure the following The mains supply is connected correctly Protection is provided against electric...

Страница 9: ...alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should b...

Отзывы: