www.sentera.eu
MIW-RTVS1-EN-000 - 03 / 11 / 2020
8 - 12
TRANSFORMER FAN SPEED CONTROLLER WITH
MODBUS RTU COMMUNICATION
RTVS1
2.
Crimp the RJ45 cable for the gateway connector and plug it into the socket. It
is used to connect the unit to a PC or another master device for monitoring or
manual control via Modbus holding register 14. To do so, you will need Sentera’s
Modus to USB converter
To modify or monitor parameters
of a Sentera device via Modbus RTU, we advise using the 3SModbus software.
The 3SModbus software is free and can be downloaded via our website:
and installed on your computer. The Modbus to
USB converter
allows you to connect a Sentera device to the
USB port of your computer and to monitor or adjust the different parameters -
see
Application examples 1
and
2
.
Application example 1: Manual mode - control via Modbus holding register 14
CNVT-USB-RS485
Master
RTVS1
A /
B G
N
D
Application example 2: Automatic mode - demand based ventilation
RTVS1
Slave - Sentera
sensor
CO
2
3.
To assure correct communication, the NBT needs to be activated in only two
devices on the Modbus RTU network. If necessary, enable the NBT resistor via
3SModbus or Sensistant (
Holding register 9
).
Example 1
Example 2
RX
ТX
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
On a Modbus RTU network, two bus terminators (NBTs) need to be activated.
NOTE
Do not expose to direct sunlight!
CAUTION