PRODUCT DESCRIPTION

The RTVS1 series of transformer fan speed controllers regulate the rotational speed 
of single-phase voltage controllable motors in five steps by varying the output 
voltage. They are equipped with auto-transformer(s) and feature Modbus RTU 
communication, TK monitoring for thermal motor protection. 

ARTICLE CODES

Article code

Rated max.  current  [A]

Fuse [A]

Current rating, no load [A]

RTVS1-15L22

1,5

T-2,5 A-H

0,04

RTVS1-25L22

2,5

T-4 A-H

0,06

RTVS1-35L22

3,5

T-5 A-H

0,08

RTVS1-50L22

T-8 A-H

0,1

RTVS1-75L22

7,5

T-10 A-H

0,12

INTENDED AREA OF USE

 

 Fan  speed  control  of  voltage  controllable  motors  (pumps  and  fans)  in  ventilation            
systems

 

Demand based ventilation in greenhouses, sheds and stables.

 

 Ventilation based on temperature, relative humidity, carbon dioxide, air quality 
(TVOC) or carbon monoxide*

 

    For  indoor  use,  surface  mounted

*Selection can be made via RTVS1 Modbus holding register 20.

TECHNICAL DATA

 

 Supply voltage: 230 VAC / 50—60 Hz

 

Modbus RTU communication

 

TK monitoring for thermal motor protection

 

Operating modes:

 

 Automatic (from low to high or from high to low): Fan speed based on input from 

external Sentera sensor or potentiometer connected to the RJ45 master socket

 

 Manual: Fan speed based on user input via Modbus Holding Register 12

 

Selectable output update interval from 5 s to 10 min

 

LED status indication

 

Modbus RTU communication via RJ45 connectors

 

Unregulated output 230 VAC (I max 16 A, resistive load)

 

Bootloader for uploading new firmware via Modbus RTU

 

Enclosure: plastic (R-ABS, UL94-V0, grey RAL 7035)

 

Protection standard: IP54 (according to EN 60529)

 

Operating ambient conditions:

 

Temperature: -10—35 °C

 

Rel. humidity: 5—85 % rH (non-condensing)

STANDARDS

 

Low Voltage Directive 2014/35/EC: 

 

 

 

 

EN 60529:1991 Degrees of protection provided by en-closures (IP Code) 

Amendment AC:1993 to EN 60529

 

 EN 60730-1:2011 Automatic electrical controls for household and similar use - 

Part 1: General requirements

TRANSFORMER FAN SPEED CONTROLLER WITH 
MODBUS RTU COMMUNICATION

RTVS1

Содержание RTVS1

Страница 1: ...Mounting and operating instructions TRANSFORMER FAN SPEED CONTROLLER WITH MODBUS RTU COMMUNICATION RTVS1 ...

Страница 2: ...SCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 9 VERIFICATION OF INSTALLATION 11 TRANSPORT AND STORAGE 12 WARRANTY AND RESTRICTIONS 12 MAINTENANCE 12 TRANSFORMER FAN SPEED CONTROLLER WITH MODBUS RTU COMMUNICATION RTVS1 ...

Страница 3: ...t is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting servic...

Страница 4: ...mounted Selection can be made via RTVS1 Modbus holding register 20 TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Modbus RTU communication TK monitoring for thermal motor protection Operating modes Automatic from low to high or from high to low Fan speed based on input from external Sentera sensor or potentiometer connected to the RJ45 master socket Manual Fan speed based on user input via Modbus ...

Страница 5: ... be activated manually via Modbus Holding register 14 or automatically in case of an RTVS1 alarm L N INPUT Power supply neutral L Power supply phase 230 VAC 50 60 Hz TK Input TK monitoring for thermal motor protection TK RJ45 master socket to connect a Sentera HVAC transmitter for demand based fan speed control in automatic mode Pin 1 24 VDC Supply voltage Pin 2 Pin 3 A Modbus RTU communication si...

Страница 6: ...he warmer the device will get For example in a technical room the correct installation height can be of great importance Do not install the controller above heating equipment or heat sources 3 3 If maximum ambient temperature cannot be adhered to please provide extra forced ventilation cooling Not respecting the abovelisted rules can reduce service life and relieves the manufacturer of any respons...

Страница 7: ...the 3SModbus software or Sensistant For the default factory setting see the Modbus register map The desired fan speed can be adjusted via Modbus holding register 14 For the complete Modbus register data refer to the product Modbus Register Map which is a separate document attached to the article code on the website and contains the registers list NOTE Optional settings 1 In automatic mode a Senter...

Страница 8: ...lled on your computer The Modbus to USB converter CNVT USB RS485 allows you to connect a Sentera device to the USB port of your computer and to monitor or adjust the different parameters see Application examples 1 and 2 Application example 1 Manual mode control via Modbus holding register 14 CNVT USB RS485 Master RTVS1 A B GND Application example 2 Automatic mode demand based ventilation RTVS1 Sla...

Страница 9: ...orward mode 3 1 Manual mode The value is taken by Holding Register 12 where you can set the desired output step see the steps and corresponding voltages in Table 1 above 3 2 Automatic modes When Auto mode has been selected the controller changes the five speeds automatically according to the values measured by the sensor connected to the RJ45 master socket There are two automatic modes 3 2 1 Autom...

Страница 10: ... diagram below for an example with steps from 2 to 5 An example of Auto Reverse mode the steps threshold configuration is as follows Step 1 0 Step 2 75 Step 3 50 Step 4 25 Step 5 1 can be as low as 0 1 is given in Fig 5 below When the Input value is above 1 device switches to Step 5 above 25 Step 4 above 50 Step 3 above 75 Step 2 up to 100 When the Input value decreases the hysteresis delta is sub...

Страница 11: ... the sensor if sensor is lost the article stays on the last step selected If both communications are lost device stays on the last step selected In Auto modes if there is no communication to the control monitoring station the article continues to operate autonomously while the sensor is connected 18 Sensor output register value number Select which sensor output will be used as input to the device ...

Страница 12: ...n manufacturing Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In ...

Отзывы: