WIRING AND CONNECTIONS 

Article type

RSMFF-2R

RSMFG-2R

VIN

18—34 VDC

18—34 VDC

15—24 VAC ±10%

GND

Ground

Common ground

AC ~

A

Modbus RTU (RS485), signal A

Modbus RTU (RS485), signal A

/B

Modbus RTU (RS485), signal /B

Modbus RTU (RS485), signal /B

AO1

Analogue / modulating output 1 for temperature 

measurement (0—10 VDC / 0—20 mA / PWM)

Analogue / modulating output 1 for temperature 

measurement (0—10 VDC / 0—20 mA / PWM)

GND

Ground AO1

Common ground

AO2

Analogue / modulating output 2 for relative humidity 

measurement (0—10 VDC / 0—20 mA / PWM)

Analogue / modulating output 2 for relative humidity 

measurement (0—10 VDC / 0—20 mA / PWM)

GND

Ground AO2

Common ground

AO3

Analogue / modulating output 3 for CO

2

 

measurement (0—10 VDC / 0—20 mA / PWM)

Analogue / modulating output 3 for CO

2

 

measurement (0—10 VDC / 0—20 mA / PWM)

GND

Ground AO3

Common ground

Connections

Spring contact terminal blocks, cable cross section: 1,5 mm

2

ATTENTION

The -F version of the product is not suited for 3-wire connection. It has separate 
grounds for power supply and analogue output. Connecting both grounds 
together might result in incorrect measurements. Minimum 4 wires are required 
to connect -F type sensors.

The -G version is intended for 3-wire connection and features a ‘common ground’. 
This means that the ground of the analogue output is internally connected with 
the ground of the power supply. For this reason, -G and -F types cannot be 
used together on the same network. Never connect the common ground of -G 
type articles to other devices powered by a DC voltage. Doing so might cause 
permanent damage to the connected devices.

MOUNTING & OPERATING INSTRUCTIONS IN STEPS 

Before you start mounting the unit, read carefully 

“Safety and Precautions”

Choose a smooth surface for installation (a wall, panel and etc.).

ATTENTION

Mount the sensor in a well-ventilated area, where it receives adequate airflow 
for proper operation and hide it from direct sunlight. Make sure it can be easily 
accessed for service.

Follow these steps:

1. 

 Using a flat screwdriver, remove the front white cover by releasing the snap-fits 
on its both sides (see 

Fig. 1

 

Snap-fits release

).

2. 

 Insert the cables through the opening on the rear plate (see 

Fig. 2 

Mounting 

dimensions

.)

3. 

 Using suitable fastening materials (not supplied), position the room sensor at 
least 1,5 m from the floor. When planning the installation, allow enough clearance 
for maintenance and service. Mount the sensor in a well-ventilated area. Mind 
the correct mounting position and unit dimensions. See 

Fig. 2

 and 

Fig. 3

RSMFX-2R

MULTIFUNCTIONAL 
ROOM TRANSMITTER 

Содержание RSMF-2R Series

Страница 1: ...Mounting and operating instructions RSMFX 2R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Страница 2: ...ODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING OPERATING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 9 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 RSMFX 2R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Страница 3: ...work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before co...

Страница 4: ...ating outputs 0 10 VDC mode min load 50 kΩ RL 50 kΩ 0 20 mA max load 500 Ω RL 500 Ω PWM open collector type PWM Frequency 1 kHz min load 50 kΩ RL 50 kΩ PWM voltage level 3 3 VDC or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 0 100 Selectable CO2 range 0 2 000 ppm Ambient light sensor with adjustable active and standby level Replaceable CO2 sensor element 3 LEDs fo...

Страница 5: ...rements Test configuration operational conditions and performance criteria for transducers with integrated or remote signal conditioning Low Voltage Directive 2014 35 EU EN 60529 1991 Degrees of protection provided by enclosures IP Code Amendment AC 1993 to EN 60529 EN 60730 1 2011 Automatic electrical controls for household and similar use Part 1 General requirements WEEE 2012 19 EC RoHs Directiv...

Страница 6: ...nnect F type sensors The G version is intended for 3 wire connection and features a common ground This means that the ground of the analogue output is internally connected with the ground of the power supply For this reason G and F types cannot be used together on the same network Never connect the common ground of G type articles to other devices powered by a DC voltage Doing so might cause perma...

Страница 7: ...according to the wiring diagram see Fig 4 Fig 4 Wiring and connections Output 1 Temperature Output 2 relative humidity Output 3 CO2 Supply voltage RSMFF 2R 18 34 VDC RSMFG 2R 18 34 VDC 15 24 VAC 10 Modbus RTU A B 5 Put back the cover snap it in 6 Switch on the mains supply 7 Customise the factory settings to the desired ones via the 3SModbus software or Sensistant if necessary For the default fact...

Страница 8: ... code on our website Calibration procedure Sensor calibration is not necessary In the unlikely event of CO2 sensor element failure this component can be replaced All sensor elements are calibrated and tested in our factory Bootloader Thanks to the bootloader functionality the unit firmware can be updated via Modbus RTU communication With 3SM boot Application part of 3SM Center software suite boot ...

Страница 9: ...y level Ambient light level Active level Input Register 42 indicates Low intensity VERIFICATION OF INSTALLATION INSTRUCTIONS After switching on the power supply one of the LEDs lights up according to the status of the measured variable If this is not the case check the connections TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two year...