www.sentera.eu
MIW-RDCZ-EN-003 - 29 / 10 / 2020
7 - 12
5.
Insert the connecting cables through the grommets of the unit.
Fig. 4 Mounting dimensions - surface mounting
Fig. 5 Mounting position
64
64
2X
ø4,3
fix
fix
82
91
10 38
52
Correct
Incorrect
6.
Do the wiring according to the wiring diagram (see
) using the information
from section “
”.
7.
Put the internal enclosure into the external one and fix it using the delivered
screws and washers. (
8.
Put back the frame cover of the enclosure.
9.
Switch on the power supply.
10.
Customise the factory settings to the desired ones via the 3-button interface,
the 3SModbus software or Sensistant.
Optional settings
If your unit is the first or the last unit on the Mdbus RTU network (see
Example 1
and
Example 2
), enable the NBT resistor via 3SModbus or the menu of the controller. If
your device is not an end device, leave the NBT disabled (default Modbus setting).
Example 1
Example 2
RX
ТX
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
OPERATING INSTRUCTIONS
Choosing the operating mode
To choose the desired operating mode, press the up
and down
buttons
simultaneously in order to access the Setup mode. The decimal point after the values
indicates that the unit is in Setup Mode.
The display shows “RUN”. To change the run mode, press the
button. Use the up
and down
buttons to select “1” for automatic mode or “0” - for manual mode.
RDCZ
RESIDENTIAL FAN SPEED
CONTROLLER