MOUNTING INSTRUCTIONS IN STEPS

Before you start mounting the GTT-1, read carefully 

Safety and Precautions”

 and 

follow these steps. Choose a smooth solid surface for installation (a wall, panel, etc.).

Follow these steps:

1. 

  Drill holes into the surface and secure the fastenings (hooks, wall plugs, etc.)into 
them. Mind the correct mounting position and unit mounting dimensions. (See

 

Fig. 1

 

Mounting dimensions

 and 

Fig. 2

 

Mounting position

.).

2. 

 Pay attention to the following instructions in order to minimize the operating 
temperature:

2.1 

 Respect the distances both between the wall / ceiling and the device and 
between  two devices as shown in 

Fig. 2. 

In order to ensure sufficient 

ventilation of the controller, clearance on every side has to be maintained.

2.2 

 When installing the device, please keep in mind that the higher you install  
it, the warmer the device will get. For example, in a technical room the 
correct installation height can be of great importance. 

2.3 

 If maximum ambient temperature cannot be adhered to, please provide 
extra forced ventilation / cooling. 

2.4 

 Leave sufficient space around the unit (for load connecting to the sockets).
Allow at least 90—100 mm for connection maintenance (to insert plug/
plugs into the sockets).

Not respecting the abovelisted rules can reduce service life and relieves the 

manufacturer of any responsibilities.

ATTENTION

It is recommended to install appropriate protective circuit on the input as 
this transformer controller is not internally short-circuit proof. Recommended 
automatic circuit breaker with “C” characteristics should be selected according to 
the transformer rated maximum current.

ATTENTION

Do not install the controller above heating equipment.

Fig. 1 Mounting dimensions 

Fig. 2 Mounting position

215

199

280

310

320

140

140

Correct

Incorrect

6

50

4x ø6

 

166

50

90

294

6

3. 

Fix the unit onto the wall / panel.

ATTENTION

A safety isolator / disconnect switch should be installed on the mains electricity 
side of all motor drives.

NOTE

The two Schuko sockets are intended only for connecting motors / fans. The total 
load connected to both sockets must not exceed the rated maximum current of 
the GTT-1 controller. Do not plug other types of electric appliances into them! 

TEMPERATURE BASED FAN 
SPEED CONTROLLER

GTT-1

Содержание GTT-1

Страница 1: ...Mounting and operating instructions TEMPERATURE BASED FAN SPEED CONTROLLER POWER RANGE 3 5 7 5 A GTT 1 ...

Страница 2: ...ON 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 7 VERIFICATION OF INSTALLATION 8 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 TEMPERATURE BASED FAN SPEED CONTROLLER GTT 1 ...

Страница 3: ...dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting servicing or r...

Страница 4: ... motors pumps and fans Application field greenhouses stables sheds For indoor use surface mounted Clean air with non aggressive non combustible gases TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Maximum motor current Imax depends on the version see article codes Temperature control 15 35 C Hysteresis 0 5 C Proportional range 5 C 7 step rotary switch Off position manual 5 step control Auto mode P...

Страница 5: ...tput voltage OFF 5 steps 110 140 170 190 230 VAC 80 VAC optional Min load current 180 mA 3 Temperature sensor probe Cable length 4 m Sensor type PT500 500 Ω at 0 C Sensor measuring range 30 70 C 4 Temperature setpoint potentiometer Operating range 15 35 C 5 7 position switch 0 Off position 1 5 Manual fan speed selection auto Automatic mode 6 Connections Cable gland clamping ranges 3 6 mm 8 13 mm C...

Страница 6: ...ered to please provide extra forced ventilation cooling 2 4 Leave sufficient space around the unit for load connecting to the sockets Allow at least 90 100 mm for connection maintenance to insert plug plugs into the sockets Not respecting the abovelisted rules can reduce service life and relieves the manufacturer of any responsibilities ATTENTION It is recommended to install appropriate protective...

Страница 7: ...ant ambient temperature 4 Plug the GTT 1 into the mains electricity network 5 Select the operating mode by turning the control switch knob on the right to the relevant position Fig 3 Fig 3 Knob positions a Temperature set point selection b Mode selection 280 310 320 280 310 320 5 1 Manual mode The standard configuration of the output voltages is as indicated in Table 1 below Output voltage Knob po...

Страница 8: ...sconnect and confirm that there is no live current flowing to the unit before servicing ATTENTION Avoid exposing the controller to direct sunlight TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication...

Отзывы: