OPERATING INSTRUCTIONS

ATTENTION

5.

 

Make sure the connections are correct before you power the unit.

 

 Make sure the mains supply voltage is within the admissible rated maximum 
current of the product.

1. 

Switch off the mains power supply before connecting any power cables.

2. 

Plug load (fan) cables into the socket according to the connecting diagram.

ATTENTION

Several fans can be connected in parallel to the controller as the maximum total 
current of all must not exceed the current rating of the controller. Maximum 2 
separate cable plugs can be connected to the sockets on the controller as the 
parallel connections are made internally. 

3. 

 Install the PT500 temperature probe in an appropriate zone in order to measure 
the relevant ambient temperature. 

4. 

Plug the GTT-1 into the mains electricity network.   

5. 

 Select the operating mode by turning the control switch / knob on the right to 
the relevant position (

Fig. 3

).

Fig. 3 Knob positions
a. Temperature set point selection

b. Mode selection

280

310

320

280

310

320

5.1 

 

Manual mode

 

The standard configuration of the output voltages is as indicated in 

Table 

1

 below. 

Output voltage

Knob 

position

0

-

1

2

3

4

5

Auto mode

Regulated 

output [VAC]

0

80*

110

140

170

190

230

According to 
temperature 

setpoint

Speed 

Off Low* Low Medium Medium Medium High

According to 

measured 

temperature

* Available but not connected.

5.2 

 

Automatic mode 

 When Auto mode has been selected, the controller  changes the five 
speeds automatically according to the setpoint temperature selected via 
the temperature potentiometer (

Fig. 3a

). The speed changes by increasing 

/ decreasing the temperature by 1 

°C

 and 0,5 

°C

 fixed hysteresis (see the 

operational diagram above).

TEMPERATURE BASED FAN 
SPEED CONTROLLER

GTT-1

Содержание GTT-1

Страница 1: ...Mounting and operating instructions TEMPERATURE BASED FAN SPEED CONTROLLER POWER RANGE 3 5 7 5 A GTT 1 ...

Страница 2: ...ON 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 7 VERIFICATION OF INSTALLATION 8 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 TEMPERATURE BASED FAN SPEED CONTROLLER GTT 1 ...

Страница 3: ...dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting servicing or r...

Страница 4: ... motors pumps and fans Application field greenhouses stables sheds For indoor use surface mounted Clean air with non aggressive non combustible gases TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Maximum motor current Imax depends on the version see article codes Temperature control 15 35 C Hysteresis 0 5 C Proportional range 5 C 7 step rotary switch Off position manual 5 step control Auto mode P...

Страница 5: ...tput voltage OFF 5 steps 110 140 170 190 230 VAC 80 VAC optional Min load current 180 mA 3 Temperature sensor probe Cable length 4 m Sensor type PT500 500 Ω at 0 C Sensor measuring range 30 70 C 4 Temperature setpoint potentiometer Operating range 15 35 C 5 7 position switch 0 Off position 1 5 Manual fan speed selection auto Automatic mode 6 Connections Cable gland clamping ranges 3 6 mm 8 13 mm C...

Страница 6: ...ered to please provide extra forced ventilation cooling 2 4 Leave sufficient space around the unit for load connecting to the sockets Allow at least 90 100 mm for connection maintenance to insert plug plugs into the sockets Not respecting the abovelisted rules can reduce service life and relieves the manufacturer of any responsibilities ATTENTION It is recommended to install appropriate protective...

Страница 7: ...ant ambient temperature 4 Plug the GTT 1 into the mains electricity network 5 Select the operating mode by turning the control switch knob on the right to the relevant position Fig 3 Fig 3 Knob positions a Temperature set point selection b Mode selection 280 310 320 280 310 320 5 1 Manual mode The standard configuration of the output voltages is as indicated in Table 1 below Output voltage Knob po...

Страница 8: ...sconnect and confirm that there is no live current flowing to the unit before servicing ATTENTION Avoid exposing the controller to direct sunlight TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication...

Отзывы: