It is recommended to use RVS-2×1.0mm² twisted multi-strand copper core wire to lay through the metal or flame
retardant tube. The actual working voltage of the manual call-point at the farthest end of the connection is guaranteed
to be more than 10V. Otherwise, the wire diameter of the wire should be increased.
Insert a slotted screwdriver into the slot of the
card and push it down firmly so that the buckle
on the upper cover is disengaged from the slot
on thebase, and then pull the slotted screwdriver
to the right to disengage the upper cover from
the base slot. Then, in the same way, the other
buckle on thesame side is separated from the
base card slot. After that, grasping the upper
cover and pullingit to one side, the upper cover
can be separatedfrom the base. During the
disassembly, be careful not to damage the buckle
and the card slot.
At least one manual call-point should be set for each fire zone, and the any position within the partition to the manual
call-point should not exceed 30 meters. The specific parameters should be reference to "Code for Design of Automatic
Fire Alarm System" (GB 50116-2013).The installation of the manual call-point should refer to the standard drawing
"Fire Alarm and Fire Control" 04X501. Manual call-points are installed on walls that are perpendicular to the ground
or other partitions that are perpendicular to the ground.
Maintenance should be done by a professional company (preferably the Manufacturer).
7
.
Wiring requirements
8
.
Disassembly method
9
.
Installation Environment
10
.
Maintenance