background image

User  Manual

Manual Call-point 

CP-5110

1

.

Summary

The CP-5110 manual call-point is installed in public places, such as the wall of the building walkway

near the hotel 

information desk and other eye-catching places. After you confirming the fire, press the button to send a fire alarm signal 

to the controller. The CP-5110 manual call-point adopts a large plastic structure and it is consisting of two parts: the 

mounting base and top cover. The installation and disassembly of the CP-5110 manual call-point are simple and easy, 

which is convenient for engineering debugging and maintenance. After pressing the button, you need to reset it with a 

dedicated key, just inset the key into the keyhole and push it. 

This product is not suitable for use in the following locations:

    

  (1

)

 There is a large oil mist and corrosive gases pollution.

      (2

)

 The relative humidity is greater than 95%.

4. 

Product introduction

 

In the normal working status, the indicator of the product is off. When there is a fire, press the button in the middle of the 

product and the two alarm indicators will be on, (If the anode is connected to the LED, the cathode is connected to R1 , the 

indicator will be on and there will generate a 30

±2

mA alarm current on the line L1 and L2. If the anode is connected to the LED, 

the cathode is connected to R2 , the indicator will be on and there will generate a 44

±2

mA alarm current on the line L1 and 

L2. If the anode is connected to the C, the cathode is connected to R1 , the indicator will be off and there will generate a 

35

±2

mA alarm current on the line L1 and L2.If the anode is connected to the C, the cathode is connected to R2 , the indicator 

will be off and there will generate a 51

±2

mA alarm current on the line L1 and L2.)The controller will recognize the alarm 

through the current change and send an alarm signal. To exit the alarm, you need to reset it with a dedicated key provided 

by the company.Environment: Temperature -10

℃~

+55

, Relative humidity ≤95% RH (40

℃±

2

), indoor. Executive 

standard: EN 54-11.

2

Appearance and size

3

Electrical parameter

5

Wiring Guideline