28
Operational Screens
When the monitor completes Start-
Up, it will enter Auto zero, and then
proceed to measure in Auto sample
mode. Under normal circumstances
the monitor will cycle from Auto
sample to Auto zero, and back to
Auto sample. If an alarm condition is
detected the monitor will enter Leak
Wait mode to ensure a leak is
detected. If the operator manually
overrides the auto sample operation,
the monitor will display Manual
Override until the operator exits
manual operation or the monitor time
outs and returns to normal operation.
Auto zero:
Auto zero measures the
fresh air (refrigerant free) zone
between each zone. Auto zero takes
approximately 24 seconds under
normal conditions. If the monitor
senses a high concentration of
refrigerant,
the
Auto
zero
measurement time is extended to
approximately 45 seconds.
Auto Sample:
Auto sample mode is
the normal measurement mode of
the monitor. It displays the PPM
level
beings
measured,
the
refrigerant and the current time. If
the Horn relay has been energized,
the fourth line will instruct the
operator to press the "RESET" key to
silence the horn. If the monitor is in
alarm, the fourth line will instruct the
operator to press the reset key to
clear alarms.
Leak Wait:
When the monitor is in
Auto sample mode and first senses a
change in PPM, it enters Leak Wait
mode. This ensures the monitor
truly detects a leak before activating
the Low Alarm relay and the Main
Alarm relay. The length of the wait
period depends upon the difference
between the concentration level and
the alarm trip point. The larger the
difference, the shorter the wait time.
If the concentration falls below the
alarm trip point, the system will
determine that it was a transient, and
return to normal operation.
Fault Mode:
When the monitor
detects a fault condition, it will enter
fault mode. The Main relay will
energize and "Trouble Alarm" will
be displayed in the third line of the
display.
Alarm Modes:
When the monitor
has sensed concentrations above
the alarm trip points, the associated
relays will be energized. The Low,
** Auto Zero**
Timer 24 12:00
Press ENT for Menu
Auto Sample AREA 1
PPM 0 12:00
R-134A
Press ENT for Menu
LEAK WAIT AREA 1
PPM 0 12:00
R-134A
Press ENT for Menu
Auto Sample AREA 1
PPM 0 12:00
Trouble Alarm
Press ENT for Menu