Real time wind rating calculation: 
Wind power rating: 0001 (hexadecimal) = 1 = > wind power rating = 1 

COMMON PROBLEMS AND SOLUTIONS 

Device cannot be connected to PLC or computer 
Possible reasons: 
1) The computer has multiple COM ports. The selected port is incorrect. 
2) The device address is wrong, or there are devices with duplicate addresses (factory default is all 0x01). 
3) Baud rate, check mode, data bit, stop bit error. 
4) 485 bus is disconnected, or a and B lines are connected reversely. 
5) If the number of equipment is too much or the wiring is too long, it is necessary to supply power nearby, add 485 
intensifier, and increase 120 

Ω

 terminal resistance at the same time. 

6) USB to 485 driver is not installed or damaged. 
7) The equipment is damaged. 

Fault phenomenon: no output or output error 
Possible reasons: 
(1) The range corresponding error leads to PLC calculation error. Please refer to the technical indicators in the first part 
for the range. 
(2) Wrong wiring mode or wrong wiring sequence. 
(3) The power supply voltage is wrong (for 0-10V type, it is 24 V power supply). 
(4) The distance between transmitter and collector is too long, resulting in signal disorder. 
(5) PLC acquisition port is damaged. 
(6) The equipment is damaged. 

Address code

Function code

Number of valid bytes

wind power

CRC_L

CRC_H

0x01

0x03

0x02

0x00 0x01

0x79

0x84

* Response frame:

Address code

Function code

Starting address

Data length

CRC_L

CRC_H

0x01

0x03

0x00 0x03

0x00 0x01

0x74

0x0A

Содержание WS303U

Страница 1: ... WS303U Ultrasonic Wind Speed Direction Sensor Product Manual ...

Страница 2: ...sensor can measure the instantaneous value of wind speed and direction at the same time It is widely used in the fields of meteorology ocean environment airport port laboratory industry agriculture and transportation The equipment with built in electronic compass no longer has the requirement of orientation during installation It only needs to ensure the horizontal installation The whole machine s...

Страница 3: ...lled horizontally Supply voltage 10 30V DC 0 10V output is powered by 24 V Power consumption 485 0 12W 4 20mA 0 5V 0 10V 1 2W Range Wind speed 0 40m S customizable 0 5m starting wind speed Wind direction 0 360 Accuracy Wind speed 0 5 2 FS Wind direction 3 Resolution Wind speed 0 01 m s Wind direction 1 Working environment 40 80 0 95 RH Wind resistance 75 m s Response time 1S IP grade 485 type IP65...

Страница 4: ...al blue Wind direction signal positive green Negative wind direction signal ANALOG OUTPUT 1 Interface description Wide voltage power supply input 10 30V DC power supply For 0 10V output equipment the power supply is 24 v 2 Example of connection mode sensor sensor Analog signal collector Analog signal collector 4 wire wiring diagram 3 wire wiring diagram ...

Страница 5: ...lists the driver names of several different 485 converters 3 Computing method 3 1 conversion calculation of current mode output signal The measuring range is 0 40m s 4 20mA output When the output signal is 12mA the current wind speed is calculated The span of wind speed range is 40m s which is expressed by 16mA current signal 40m S 16mA 2 5m s ma that is the current changes 1mA and the wind speed ...

Страница 6: ...e of initial structure 4 bytes Address code 1 byte Function code 1 byte Data area n bytes Error check 16 bit CRC code Time to end structure 4 bytes Address code the address of the transmitter which is unique in the same communication network factory default is 0x01 Function code instruction function indication issued by the host Data area the data area is the specific communication data pay attent...

Страница 7: ...or configuration address Content Operation Definition 0000 H 40001 decimal Instantaneous wind speed Read only Real time value of wind speed expanded by 100 times 0001 H 40002 decimal wind direction Read only Real time value of wind direction integer 0 due north 90 due east 0002 H 40003 decimal Maximum wind speed Read only Maximum wind speed after power on of equipment expanded by 100 times 0003H 4...

Страница 8: ...20 Ω terminal resistance at the same time 6 USB to 485 driver is not installed or damaged 7 The equipment is damaged Fault phenomenon no output or output error Possible reasons 1 The range corresponding error leads to PLC calculation error Please refer to the technical indicators in the first part for the range 2 Wrong wiring mode or wrong wiring sequence 3 The power supply voltage is wrong for 0 ...

Отзывы: