background image

 

COND SGA-A & SGA-D Manuel_EN Rev3.doc 

Page 17 on 20 

Rev: 03/08/2006 

 

Resolution 

The input corresponding to a one-unit change in the least significant digit of the data 

acquisition /display equipment (Good resolution is not

 

necessarily equal to good 

accuracy.)

 

Sensing Element 

That part of the transducer, which reacts directly in response to the input. 

Sensitivity 

The minimum change in input signal to which an instrument can respond. This is the 
relationship between the change in strain gauge output to the level or magnitude of 

the COND SGA output 

Signal Conditioner 

A circuit module that offsets attenuates, amplifies, linearizes and/or filters the signal 
for input to an A/D converter. A typical output signal conditioning is 4 to 20 mA. The 

COND SGA is essentially a Signal Conditioner –more specifically known as a Strain 
Gauge Amplifier - in that it 

conditions 

(alters) the input signal from a load cell to an 

electrical output 

Single card assembly 

The COND SGA has only the one Printed Circuit Board assembly on which all the 

components are mounted. The assembly is then mounted inside an environmentally 
rugged enclosure. 

Span 

Span is otherwise identified as GAIN. It relates to the proportional output to the 

sensor input. Calibration of the COND SGA is determined by setting the Span (Gain) 
and Zero (Offset). 

Span Adjustment 

The ability to adjust the gain of a process or strain meter so that a specified display 

span in engineering units corresponds to a specified signal span. For instance, a 
display span of 200°F may correspond to the 16 mA span of a 4-20 mA transmitter 

signal. 

Stability 

The quality of an instrument or sensor to maintain a consistent output when a 

constant input is applied. 

Strain Gauge 

The strain gauge is a resistance bridge device where the bridge value alters linearly 
and proportionally to the force exerted on it – be it temperature, pressure, torque or 

load. The COND SGA is designed to convert this change in the of the strain gauge to 
a proportional electrical signal. 

Strain Gauge Amplifier 

The COND SGA is essentially a type of Signal Conditioner that it conditions (alters) 
the input signal from a strain gauge to an electrical output 

Torque Transducer 

The Torque Transducer is one of a series of STRAIN GAUGE sensors that the 

COND SGA input is designed to accept. (Torque Sensor, Load Cell and Temperature 
transducers). 

Zero 

Zero is otherwise identified as Offset. It relates to the proportional output to the 

sensor input. Calibration of the COND SGA is determined by setting the Span (Gain) 
and Zero (Offset). 

Zero Adjustment 

The ability to adjust the display of a process or strain meter so that zero on the 
display corresponds to a non-zero signal, such as 4 mA, 10 mA, or 1 Vdc. 

Zero Offset 

The difference expressed in degrees between true zero and an indication given by a 

measuring instrument. See Zero Suppression 

Zero Suppression 

The span of the COND SGA can be offset from zero (zero suppressed) such that 
neither limit of the span will be zero. For example, an COND SGA which measures a 

load of a 100kg span from 400kg to 500kg is said to have 400kG zero suppression. 

 

AC Alternating 

Current 

DC Direct 

Current 

Hz Hertz 

(Frequency) 

Содержание COND-SGA-A

Страница 1: ...9 3 4 2 Example A strain gauge has a sensitivity of 2 809 mV V 10 3 5 Shunt Calibration Switch SW1 8 10 3 6 Zero Offset Setting Switch SW2 10 3 6 1 Example An installation has a tare of 15 kg with a 200kg strain gauge which gives an output of 6 37mV V at 10V excitation 11 4 CALIBRATION 11 4 1 Output 11 4 2 Zero Offset 11 4 3 Sensitivity 11 4 4 Calibration Connections using mV Source 12 5 TROUBLESH...

Страница 2: ...f vibration agitation and electrically noisy environment The on board low pass filter can be switched in and adjusted from 1Hz to 5kHz using a series of DIP switches A wide range of proportional output options for currents and voltages can be configured by DIP switch settings Both the AC and DC versions are based on a common board and are mounted in an IP65 NEMA 4X ABS case 2 INSTALLING THE COND S...

Страница 3: ...he waterproof entry and strain relief will seal to a higher rating than the enclosure Cable diameter should be between 4mm 0 16 and 7mm 0 27 2 3 Cabling 2 3 1 Power Connection Two power supply options are available COND SGA A 220 230VAC 50 60Hz 110 120VAC 50 60Hz 5W Max COND SGA A COND SGA D 18 24V DC 5W approx 150mA fully loaded NOTE The COND COND SGA A can be powered from AC or DC sources whiche...

Страница 4: ... Individually shielded twisted multipair cable 7 0 25mm 2 pair Tinned copper drain Individually shielded in polyester tape Diameter 4 19 mm Impedance 54 Ohms Capacitance m core to core 115 pF core to shield 203 pF UK Farnell 585 646 Individually shielded twisted multipair cable 7 0 25mm 3 pair Tinned copper drain Individually shielded in polyester tape Diameter 6 86 mm Impedance 62 Ohms Capacitanc...

Страница 5: ...y on the COND SGA and the ve end is connected to the COND SGA output The current through the load is sunk by the COND SGA towards ground 0V N B In this mode neither connection to the output load is electrically common to the load cell Select this option by fitting the two jumpers JP1 and JP2 to the outside positions See Figure 3 2 In Source mode the ve end of the load is connected to the COND SGA ...

Страница 6: ...1 0V 0V 10V 5V Table 3 1 N B Full scale output on the voltage ranges is achieved with a bi polar input Note 1 Negative inputs can be accommodated on the current output ranges by setting the Zero switch SW2 to 50 Table 3 8 and setting SW1 to twice the required mV V setting Table 3 6 3 1 2 Switch 4 Analogue Output and Excitation Voltage Options SW4 SW4 1 2 3 4 5 6 7 8 10V 0 0 0 X X 1 Filter in 1 Fil...

Страница 7: ...h can be switched in to improve the performance and output signal quality in electrically noisy environments It can also be used to reduce the effects of high frequency fluctuations in the load or applied force to the load cell The cut off frequency of the filter is set by the DIP switch SW3 as illustrated in the table below 3 2 1 Switch 3 SW3 1 2 3 4 5 6 7 8 1Hz 0 0 0 0 0 0 1 1 5Hz 1 0 0 0 0 1 1 ...

Страница 8: ...6 must be ON and SW4 7 must be OFF SW3 1 2 3 4 5 6 7 8 50Hz 1 1 1 1 1 1 1 1 Table 3 5 3 3 Output Current Mode and Input Filter Settings Jumpers JP1 JP2 JP3 Refer to Figure 2 4 for details of wiring connections to J1 Figure 3 2 3 4 Span Gain Setting Switch 1 Ranges 1 to 60 from 0 06 mV V to 30 30 mV V ON 1 OFF 0 SW1 8 switches on the shunt cal function see Table 3 8 SW3 ...

Страница 9: ...COND SGA A SGA D Manuel_EN Rev3 doc Page 9 on 20 Rev 03 08 2006 3 4 1 SW1 Table 3 6 ...

Страница 10: ...associated wiring SW1 1 2 3 4 5 6 7 8 Shunt Cal ON x x x x x x x 1 Shunt Cal OFF x x x x x x x 0 Table 1 8 The 120k resistor can be taken out of circuit and replaced by a user defined leaded component by carefully cutting the fine link as shown in Figure 3 3 Use the right hand pad and either of the left hand pads to fit the new component The surface mount resistor can be reinstated by re connectin...

Страница 11: ...aving selected the polarity and the offset nearest to that required with the switches use the fine potentiometer P2 to achieve the final setting 4 3 Sensitivity Select the sensitivity as detailed in Chapter 3 Table 3 6 by means of SW1 Switches 1 4 of SW1 provide fine setting of the COND SGA sensitivity while switches 5 7 give coarse control This arrangement allows the COND SGA to cover a wide rang...

Страница 12: ...n conditions weight force or mV V this may be zero if required and note the analogue output having ensured that the SW1 settings are correct for the transducer sensitivity as step 1 above 3 Apply the known high calibration conditions for optimum accuracy this should be at least 75 of full load and note the analogue output 4 Use the fine trim control P1 to obtain the required change in Volts or mA ...

Страница 13: ...s not trapped in terminal cable break etc d Check the sensor is connected typically reading 350 Ohm across Strain Excite and and also Strain Input and of J2 with the power off e Check the Excitation voltage J2 is at 10V DC 5 1 1 For voltage output a Check V out and V out terminals are wired b Check the load is connected and is not open or short circuited c Check SW4 settings are correct for Voltag...

Страница 14: ...t is present but higher or lower in span or zero than expected a Check the installation for problems and repair where necessary b Poor termination c High resistance on cable leads d Low insulation impedance e Proximity to High Voltage Equipment Transformers Contactors Motors etc 5 4 2 Noisy Environment a Check if the source can be found and remove noise b Check the cable screening and ensure it is...

Страница 15: ... Manual The settings of the switches and links on the COND SGA card The calibration figures for the attached sensors The instrument loop to which the output is connected A record of the normal output if applicable A maintenance record of the COND SGA A contact phone number from the supplier for assistance 7 GLOSSARY AWG American Wire Gauge Background Noise The total noise floor from all sources of...

Страница 16: ...bration cycle Load The electrical demand of a process expressed as power watts current amps or resistance ohms Load Impedance The impedance presented to the output terminals of a transducer by the associated external circuitry Load cell The load cell is one of a series of Strain Gauge sensors that the COND SGA input is designed to accept Torque Sensor Pressure temperature transducers Low Pass Filt...

Страница 17: ... For instance a display span of 200 F may correspond to the 16 mA span of a 4 20 mA transmitter signal Stability The quality of an instrument or sensor to maintain a consistent output when a constant input is applied Strain Gauge The strain gauge is a resistance bridge device where the bridge value alters linearly and proportionally to the force exerted on it be it temperature pressure torque or l...

Страница 18: ... 06 29 mV V Gain adjustment Pot fine adj 0 06 1 0 mV V Offset adjustment Pot fine adj 0 1 25 FR Offset adjustment Switchable coarse adj 1 25 79 FR Output load Voltage output 2 mA Output load Current output 0 500 Ohms Bandwidth No filter and 2mV V DC 6 kHz Filter cut off Switchable ranges 1 5000 Hz Zero temperature coefficient 2 5mV V 0 002 0 009 ºC 2 5mV V FR Span temperature coefficient 0 007 0 0...

Страница 19: ...ears to have a defect in material or workmanship or fails during normal use within the period please contact your Distributor who will assist you in resolving the problem If it is necessary to return the product to SENSY s a please include a note stating name company address phone number and a detailed description of the problem Also please indicate if it is a warranty repair The sender is respons...

Страница 20: ...COND SGA A SGA D Manuel_EN Rev3 doc Page 20 on 20 Rev 03 08 2006 8 8 Connection Details Figure 8 1 ...

Отзывы: