45
INSTALLATION AND OPERATION INSTRUCTIONS — FENCE PROTECTION SYSTEMS
6
SYSTEM STARTUP AND TESTING
General
System startup and testing consist of powering up the system and making tests to verify proper
operation and detection of fence disturbances. The
Magal-Senstar
Field Performance Analyzer
(FPA) and a good quality ohmmeter capable of reading 1 megohm
±
10% and resistances of up to 10
megohms are required.
Once all system components are installed and interconnected, power will be applied and the system
adjusted and tested for proper operation. This procedure involves the following steps:
Verify wiring connections.
Apply power to the FPS-3 Central Controller and MX-5300.
Perform tests at the FPS-3 Central Controller.
Perform tests and record measurements at each field-mounted dual zone pre-amp.
Adjust FPS-3 Central Controller/MX-5300 based on field measurements.
Verify Connections
Before proceeding with system startup, verify that:
All equipment has been installed and connected.
The FPS-3 Central Controller is correctly connected to the MX-5300. Connections are local bus
ribbon cable, audio cable and power connections. See Figures 9 and 49.
FPS-3 Central Controller internal switch settings should be:
•
Address switch SW1 set for correct controller address. Default factory setting is for zones
1-30. See Figure 51.
•
Jumper JP2 installed for zones 1-30, removed for zones 31-60. See Figure 51.
•
The gain setting for all zones set to 4. This is the normal factory default setting. See
Figure 52.
Applying power
Apply power to the MX-5300. This will power both the MX-5300 and the FPS-3 Central Controller.
If this system has not been previously powered and programmed, the MX-5300 display may show
communications failures or other alarm indications. Properly program the MX-5300 before proceeding
with systems tests.