background image

Page 8

FlexPI Product Guide

When attaching the sensor cable to the surface, the type and the spacing of the fasteners are both 
extremely important. The fasteners must hold the sensor cable firmly against the surface without 
pressing into the jacket. Most of the contact between the cable and the mounting surface occurs at 
the fasteners. Therefore, using a fastener every 30 cm (1 ft.) will provide good contact between the 
sensor cable and the mounting surface (see 

Figure 11:

Figure 13:

 and 

Figure 14:

). Select 

fasteners that hold the cable directly against the surface. Do not use fasteners which place a layer 
between the cable and the mounting surface. This layer prevents direct contact and acts as an 
insulator.

There are a wide variety of commercially available cable fasteners for use on any type of building 
material. Even permanent tape can be used to attach the sensor cable. When selecting fasteners, 
remember that the outside diameter of the sensor cable is 3.6 mm (0.14 in.) nominal. Choose 
fasteners that hold the cable firmly against the protected surface without pressing into the cable 
jacket. If you are attaching cable to a stock cage, or fence, use cable ties that are pulled hand-
tight. Do not use mechanical cable tie tools. For added security, you can use steel bar ties or 
twisted wire. However, do not overtighten the bar ties or wires.

Installation rules

Use one processor and sensor cable on one type of building material. Do not use one 
processor and sensor cable to protect more than one type of surface.

The maximum recommended cable spacing is 1.25 m (4 ft.).

The minimum recommended cable spacing is 30 cm (1 ft.).

Keep roofs separate from other parts of the installation.

For roof installation on steel beams, the maximum recommended cable spacing is 1.8 m 
(6 ft.).

On roofs with wooden trusses the cable spacing should match the spacing of the trusses, 
typically 61 cm (2 ft.).

Sensor cable can be installed directly on the underside of a roof’s surface.

For increased security, use additional cable passes on the lower levels of walls and roofs 
(i.e., the first 2 m, 6.6 ft.) which is where most break-ins occur. 

Keep floors separate from other parts of the installation.

When attaching the sensor cable to a surface area, the cable must be in close contact with the 
protected surface. 

FlexPI sensor cable can be installed inside metal conduit. The conduit must be in close 
contact with the protected surface (maximum 1 m, 3.3 ft. separation between fasteners). After 
cutting the conduit, ensure that there are no burrs or sharp edges that could damage the 
sensor cable as it is pulled through.

If windows are included as part of a protected surface, it is recommended that a security grille 
be installed over the windows. The sensor cable that is protecting the surface should then be 
installed along the outside edge of each window frame.

For outdoor surface protection (e.g., fences, walls) install the processor indoors, then use 
lead-in cable to connect the processor to the sensor cable at the start of the zone. The 
maximum cable run for lead-in cable is 30 m (98 ft.).

Security cage protection

To protect security cages, attach the sensor cable to the security cage using nylon cable ties 
spaced 30 cm (1 ft.) apart. The cable spacing depends on the required level of security, with 1 m 
(3.3 ft.) spacing recommended. The cable should be attached to the secure side of the cage, and 
cable loops should be used at support posts for increased sensitivity.

Содержание FlexPI C8DA0402-001

Страница 1: ...Product Guide FlexPI Interior Intrusion Detection Sensor C8DA0402 001 Rev B January 13 2014 ...

Страница 2: ...dance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause ha...

Страница 3: ...s 10 2 Installation 15 Installing the sensor cable 15 Cable handling 15 Installing cable on security cages 16 Installing cable on walls 16 Installing cable on roofs 17 Installing cable on floors 17 Embedding sensor cable in buildings and walls 17 Protecting windows and skylights 17 Protecting pipes and data cables 17 Installing terminators 18 Splicing cable 19 Outdoor cable installation 19 Install...

Страница 4: ...ng the Threshold 32 Setting the cut Count and time Window 33 The Cut Profile 33 Setting the Climb Alarm parameters sustained attack 33 Setting the climb Time and Window 34 Area Preparation 35 Bar graph received signal strength indicator 35 Step 1 Setting the Filter Response 36 Step 2 Calibrating the FlexPI Gain Threshold 36 Setting the Climb Alarm parameters sustained attack 38 Setting the Cut Ala...

Страница 5: ...eter most intruders while alerting police or security Each FlexPI system is a self contained intrusion detection sensor consisting of a processor an enclosure up to 600 m of sensor cable and a terminator The cable mounting hardware power supply alarm communication wiring and alarm annunciator are Customer supplied Figure 1 FlexPI system components 300 m sensor cable 30 m lead in cable data cable p...

Страница 6: ...se bands that optimize the sensor s response for the protected surface and the expected type of attack Other detection parameters include the Climb Alarm Settings sustained attack the Cut Alarm Settings number of impacts Time Window time in which a sustained attack or the number of impacts must occur to generate an alarm Gain Settings four discrete signal amplification levels FlexPI also includes ...

Страница 7: ...ermine the security requirements and expectations for a FlexPI installation There are a number of factors which must be considered when planning the installation The primary factors are the value of the assets being protected and the required level of security For a high security application where a sophisticated attack is possible the sensor cable spacing should be kept at a minimum This will inc...

Страница 8: ...cm 1 ft Keep roofs separate from other parts of the installation For roof installation on steel beams the maximum recommended cable spacing is 1 8 m 6 ft On roofs with wooden trusses the cable spacing should match the spacing of the trusses typically 61 cm 2 ft Sensor cable can be installed directly on the underside of a roof s surface For increased security use additional cable passes on the lowe...

Страница 9: ...structure or to the floor As with other parts of the building the type of building material dictates the number of cable passes required Embedding sensor cable With careful planning the sensor cable can be embedded in walls floors or even roofs during construction The recommended method is to install metal conduit inside the structure during the construction phase When the construction is complete...

Страница 10: ...e to the mounting surface must hold the cable firmly against the surface without pressing into the jacket or damaging the cable The fasteners must be appropriate for the specific type of surface Figure 2 Double pass security cage installation use cable loops at support posts for increased sensitivity double cable pass using 1 m spacing on 3 m security cage 30 cm 12 in recommended cable tie spacing...

Страница 11: ...w security application single pass on 8 ft wall 61 cm 2 ft 61 cm 2 ft 61 cm 2 ft 61 cm 2 ft 2 44 m 8 ft terminator FlexPI processor sensor cable power data cable 81 cm 2 7 ft 81 cm 2 7 ft 81 cm 2 7 ft 2 44 m 8 ft terminator FlexPI processor sensor cable power data cable 1 22 m 4 ft 1 22 m 4 ft 2 44 m 8 ft terminator FlexPI processor sensor cable power data cable ...

Страница 12: ...nduit terminator FlexPI processor sensor cable power data cables sensor cable around windows 1 2 2 m terminator FlexPI processor sensor cable 61 cm 2 ft 3 ft reduced cable spacing on lower portion of roof NOTE Cable installed indoors on 4 f t 91 cm the underside of the roof sensor cable cable tie 30 50 cm data cable conduit sensor cable metal conduit fastener 1 m 3 25 ft max sensor cable ...

Страница 13: ... cable with permanent tape cable tie 30 cm sensor cable 12 in support post sensor cable 30 cm 12 in cable ties do not allow the sensor cable to be pinched between the post and the cage If the cage is tightly secured to the post wrap the cable around the post as illustrated cable clip sensor cable 30 cm 12 in cable clip mounting surface fastener sensor cable permanent tape 30 cm sensor cable 12 in ...

Страница 14: ...Page 14 FlexPI Product Guide Figure 15 Using corner loops 10 15 cm inside corner outside corner 4 6 in corner loop fastener 10 15 cm 4 6 in corner loop ...

Страница 15: ...g is a list of cable handling Do s and Don ts Apply consistent light tension approximately 2 25 kg 5 lbs while mounting the sensor cable Install the sensor cable in metal conduit if the cable is being installed in an area where it may be prone to damage from vandalism equipment or materials see Figure 10 DO NOT use plastic conduit When using cable ties to attach the sensor cable to a security cage...

Страница 16: ... at the hinged side of the door Continue installing the cable on the security cage Figure 16 illustrates sensor cable installation on a security cage door Installing cable on walls The cable spacing depends on the type of building material and the required level of security The maximum recommended spacing for any type of wall surface is 1 25 m 4 ft The minimum recommended spacing is 30 cm 1 ft see...

Страница 17: ...y heavy rain Installing cable on floors Attach the cable to the underside of the floor either directly to the subfloor or to the support structure Base the number of cable passes required on the type of floor Embedding sensor cable in buildings and walls This type of installation requires the installation of metal conduit inside the walls during the construction of the building Senstar recommends ...

Страница 18: ...fully separate the strands of the exposed braided shield Tightly twist the strands into a single conductor and then carefully remove 6 mm 0 25 in of insulation from the center conductor DO NOT nick the center conductor Insert the twisted shield into one of the terminals on the terminal block and tighten the screw Insert the center conductor into the adjacent terminal and tighten the screw Insert t...

Страница 19: ...als and tighten the screws Insert the 2 center conductors into the 2 adjacent opposing terminals and tighten the screws Ensure that shield meets shield and center conductor meets center conductor Line up the terminal block with the center of the splice enclosure and apply 3 or 4 wraps of electrical tape at each of the 2 points where the cable will fit into the cable guide bars Align the 2 taped se...

Страница 20: ...away from the beginning of the zone by connecting lead in cable to the processor and splicing the lead in to the sensor cable There are two flanges on the enclosure that include 5 mm 0 375 in holes for mounting the enclosure on a flat stable surface Figure 20 illustrates the FlexPI processor features and Table 1 includes feature descriptions Figure 21 shows a mounted enclosure The mounting hardwar...

Страница 21: ...THRESHOLD switch Sets the input signal amplification before the signal is processed 4 settings from 1 low to 4 high 12 Enclosure cover mounting holes X4 4a GAIN THRESHOLD LEDs 4 LEDs correspond to 4 Gain settings LED ON switch ON 13 T4 SENSOR CABLE connection GND SHIELD connect twisted braided shield FLEX IN CENTER connect center conductor 5 S5 MISC switch miscellaneous controls S5 1 sets the freq...

Страница 22: ...Installing the processor Page 22 FlexPI Product Guide Figure 21 Enclosure mounting mounting hardware sensor cable alarm data cable and power cable ...

Страница 23: ...4 Sensor cable and lead in cable connections are made exactly the same way Figure 22 illustrates the sensor cable connection procedure Pass the sensor cable or lead in cable through the left side cable gland Prepare the cable for connection by following steps 1 2 and 3 in Figure 17 Figure 22 Connecting the sensor cable lead in cable 4 5 Insert the terminal block into T4 Insert the twisted shield a...

Страница 24: ...s are complete and verified Figure 23 shows the sensor cable to processor connection procedure Figure 24 shows the input output wiring connections to the FlexPI processor Figure 23 Connecting the data and power cables 2 3 1 Feed the data and power cable through the right Replace terminal block T5 and tighten the cable Carefully remove 6 mm 0 25 in of insulation side cable gland remove terminal blo...

Страница 25: ...ns sensor cable relay output and RELAY CONNECTIONS 30V 0 5 A RELAY T5 PWR INPUT 12 48 VDC T4 SUPERVISION SONALERT ALARM NC COM NO NC COM NO COM NO FLEX IN GND VDC VDC ALARM NO ALARM COM ALARM NC SONALERT NO SONALERT COM SUPERVISION NO SUPERVISION COM SUPERVISION NC SHIELD CENTER power input connections ...

Страница 26: ...Installing the processor Page 26 FlexPI Product Guide ...

Страница 27: ...ter Settings sets the sensor s frequency response Sensitivity Switch SW2 Gain Threshold Settings S4 Gain Settings Cable sets the amplification of the input signal received from the sensor cable before processing Impact Count Selector JP4 Cut S3 Cut Alarm Settings Window sec Threshold Count Cut Profile Sets the number and intensity of discrete impacts which must occur within the specified time Wind...

Страница 28: ...cted surface For example To simulate an impact attack Cut Alarm strike the surface using moderate to strong force with a hard object such as the handle or blade of a large screwdriver Wait approximately two seconds between impacts and wait about four seconds after each Cut Alarm to allow the processor s filters to clear To simulate a sustained attack Climb Alarm on a hard surface e g brick cinder ...

Страница 29: ...justments before changing the processor s settings First make the changes using the calibrate tool Then view a magnitude or frequency response plot using the new settings while testing the installation If the changes do not result in the required level of detection continue making and reviewing adjustments When the results are satisfactory download the new parameters to the processor CAUTION Some ...

Страница 30: ...ned activity is added to the total Time 10 Time Sets the period of Time that the received signal must exceed the climb Threshold to cause an alarm The Time must be accumulated within the climb alarm Window setting 2 sec Filter Settings The filter settings are used to customize the sensor s frequency response to the type of mounting surface and the installation environment Correct adjustment of the...

Страница 31: ...the length of the cable 6 Once the Frequency response is adequate close the Calibrate tool save the UCM file and download the new settings to the processor Step 2 Calibrating the Gain Settings The Cable Gain is used to amplify the input signal from the sensor cable before it is processed FlexPI has four Cable Gain Settings ranging from 1 lowest to 4 highest 1 Using the sensor s default Gain Settin...

Страница 32: ... surface 2 If any of the attack simulations impacts do not register as Cut Counts lower the Cut Alarm Threshold 3 Repeat this process until each simulated attack impact registers as a Cut Count and leads to an alarm 4 Once the Threshold is set monitor the system for nuisance alarms If the nuisance alarm rate NAR is unacceptable try to determine and correct the source Otherwise raise the Threshold ...

Страница 33: ...arm parameters sustained attack 1 Start recording a UCM Magnitude response plot tool and perform the simulated sustained attack scenario along the protected surface 2 If the attack simulation does not cause an alarm lower the Climb Alarm Threshold and repeat the tests 3 Repeat this process until the simulated attack always causes a Climb alarm 4 Once the Threshold is set monitor the system for nui...

Страница 34: ... also affect the Cut Alarm Settings If the Cut Alarm parameters have already been set retest and if required adjust the Cut Alarm parameters after changing the Cable Gain setting Note For settings available via the UCM that are not adjustable using the onboard switches the default values listed in the UCM apply Figure 26 Calibration switches S1 CLIMB S2 TIME WINDOW S3 CUT S4 GAIN THRESHOLD S5 MISC...

Страница 35: ...oring sawing cutting digging chiselling climbing If the Time Window lapses before the Time setting is exceeded the processor resets both parameters S2 Time Window Sets the maximum time in which the specified Climb Time must accumulate to cause an alarm AND Sets the maximum time in which the specified number of Cuts impacts must occur to cause an alarm 8 to 128 seconds S3 Cut Sets the number of imp...

Страница 36: ...length of the sensor cable Look for a response that is above the Threshold 6th LED is illuminated but below the top of the bar graph 10th LED is OFF 4 If the signal response does not illuminate the green LED increase the Gain setting one level and repeat the test OR If the signal response always reaches the top of the bar graph decrease the Gain setting one level and repeat the test 5 When the imp...

Страница 37: ...he switches conduct tests sensor alarms raise gain monitor NAR too many NAs calibration complete lower gain too many NAs sensor alarms change frequency response band reset gain to 2 and return to first conduct tests calibrate via UCM OR redeploy cable and repeat procedure conduct tests N Y Y N N Y Y N monitor NAR NAR nuisance alarm rate NAs nuisance alarms gain already at maximum N Y N Y both resp...

Страница 38: ...is 4 impacts and the Time Window is 32 seconds If the security regulations at your facility do not define specific Cut Count and Time Window settings then these parameters should be set according to the probability of nuisance impacts occurring within a specific timeframe For example if nuisance impacts can occur but never in rapid succession then the Cut Count can be set to 2 with a short Time Wi...

Страница 39: ...e is an advanced parameter which can be adjusted only through the UCM For switch calibration the Cut Profile is ON at the default setting of 20 This means that each time an Impact is recorded 20 of the Climb Window setting is added to the time remaining in the Climb Window see Figure 29 Note If there no Gain Threshold setting functions for both Cut alarm and Climb alarm detection change the Filter...

Страница 40: ...rm Figure 30 illustrates the Climb Alarm concept of a sustained attack within a specified time Figure 29 Understanding the Cut Alarm Figure 30 Understanding the Climb Alarm Threshold 10 time Window 30 10 20 5 15 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 reset counter Threshold 10 time Window 30 Cut Profile 20 add 6 seconds for each count 10 20 5 15 30 29 28 27 26 25 24 23 22 2...

Страница 41: ... with black jacket 300 m 984 ft reel when ordering allow for an overage of 5 30 m lead in cable G5SP0201 Non sensitive lead in cable with black jacket 30 m 98 ft reel FlexPI accessories termination splice kit C6KT2600 single zone termination splice kit cable ties GH0916 nylon tie wraps 1000 piece bag double loop bar ties 82 130020 steel bar ties 15 cm 6 in long 18 AWG 1000 pieces UCM software UCM ...

Страница 42: ...Page 42 FlexPI Product Guide ...

Страница 43: ...ontrols calibration adjustments via the Universal Configuration Module software application calibration adjustments via onboard switches adjustable filter settings frequency response Alarm outputs 2 form C relays rated 30 VDC 1 A max non inductive load 1 ALARM relay activates to signal sensor alarm condition 1 SUPERVISION relay activates to signal enclosure tamper condition cable fault condition p...

Страница 44: ...on Alarm LED Alarm LED UCM connected LED Enclosure door open LED Supervision mechanical enclosure tamper switch sensor wires lead in cable processor operation Temperature 0º to 70ºC 0º to 158º F Relative humidity 0 to 95 non condensing Frequency response switch selectable frequency response bands 100 300 Hz 300 900 Hz UCM adjustable frequency response band 100 900 Hz ...

Отзывы: