background image

 

Mistake description, 
personnel actions 

Possible consequences 

Actions 

Cover 

Ingress  of  water  into  device 
case.  Failure  of  the  device 
and  supported  automation 
system. 

1.  In  case  of  early  reveal-
ing: 

disconnect 

device 

power  supply,  dry  out  de-
vice cavity until full removal 
of  moisture,  and  place  a 
pack  of  silica  gel  dryer  into 
device cavity.  
2  In  case  of  late  revealing 
(appearance  of  corrosion, 
water  on  electronic  board, 
changing of color and struc-
ture  of  parts  material  sur-
face) - repair works at Man-
ufacturer.

 

2.3 Unit preparation for operation 

2.3.1 Before starting the operation the user must examine the signal device. It is re-

quired to control: 

-

  absence of device mechanical damages; 

-

  absence of unfastened or loose signal device elements; 

-

  correspondence  of  product  name,  product  designation,  serial  number,  marking 

with ones mentioned in operational documentation; 

-

  Completeness, according to the present Operation Manual; 

2.3.2 Before transducer installation it is required to perform its operation check. 
For operation check it is required to supply power on a signal device, within 1,5 se-

conds  signal  device  should  emit  one  short  sound  signal.  Then  signal  device  shall  be 
switched  to  an  operation mode  or  a  “sleep”  mode  (the  flashing  dot  or  a  last  interrogated 
sensor address shall appear on the screen). In case of sound signal missing or wrong indi-
cation on the screen, signal device should be deemed as malfunctioning. 

2.3.3 MS-K-500-3  should  be  fixated  to  a  flat  surface  using  screws  screwed  in 

mounting holes 9 (picture 1.1). 

MS-K-500-3S (picture 1.2) signal device should be fastened with latches 3, dimen-

sions of the looking glass - 

92x92±0,5 mm.  

2.3.4 Before installation it is required to perform the electric part installation. 

WARNING!

 

Ingress  of  liquid  into  enclosure  of  signaling  device  through  un-

sealed cable fittings shall be avoided. 

Signal device connection diagram is given at picture 2.1. Signal device is connected 

to a power and signal line using 3 wires of circuit: "+" (plus of power supply), "L" (line), "-" 
(minus 

– common cable wire). Disconnect supply power before wiring. 

МС-К-500-3

Л

-

к

л

ин

ии

пи

та

ни

я-

св

яз

и

си

ст

ем

ы

из

м

ер

ит

ел

ьн

ой

Е

Н

С

"

+

Конт.

Л

-

к

л

ин

ии

пи

та

ни

я-

св

яз

и

си

ст

ем

ы

из

м

ер

ит

ел

ьн

ой

Е

Н

С

"

+

Конт.

 

T

O

 SENS L

INE

 

Содержание SENS MS-K-500-3

Страница 1: ...Research and production enterprise SENSOR SENS device Signaling device MS K 500 3 MS K 500 3S Operation Manual ...

Страница 2: ... Technical specifications 3 1 3 Completeness 3 1 4 Design and operation 4 1 5 Marking 6 2 1 Safety measures notification 6 2 2 Operational limitations 6 2 4 Used items 8 3 MAINTENANCE 16 4 ROUTINE PRODUCT REPAIR 17 5 TRANSPORTATION AND STORAGE 17 6 UTILIZING 17 7 ANNEX A 18 ...

Страница 3: ...he range from minus 5 up to 50 C or S3 as per GOST R 52931 2008 1 2 Technical specifications 1 2 1 Mechanical impact resistance of MS K 500 3 and MS K 500 3C signal device corresponds to V1 as per GOST R 52931 1 2 2 Water and dust ingress protection degree of the signal device is IP54 accord ing to 1 2 3 Normal functioning of the signal device can be provided if the length of power and communicati...

Страница 4: ...llowing devices are installed under the signal device cover Record protection toggle 10 piezoelectric ring 6 and terminal clamp 8 designed for external circuits connec tion 1 housing 2 cover 3 cable fitting 4 looking glass 5 exterior panels 6 piezoelectric ring 7 control button 8 terminal clamp 9 installation orifice 10 record protection toggle 11 silicone gasket 12 protective sealing orifice 13 n...

Страница 5: ...signal device is config ured on reaction for certain events occurrence then if the event occurred certain status byte received the indicator displays the device address designation and value of the pa rameter the indication is glowing In accordance with operator s actions the signal device in operation mode interro gates the devices connected to a SENS line and displays the parameters set by the o...

Страница 6: ...f BK shall be only performed with power supply disconnected 2 2 Operational limitations 2 2 1 Use of a signaling device with mismatching power supply voltage is not al lowed 2 2 2 List of critical failures of signaling devices is given in table 2 1 Table 2 1 Failure Cause Actions A device is not op erable Mismatching power sup ply voltage Check and bring into accordance Power and or control circui...

Страница 7: ...k For operation check it is required to supply power on a signal device within 1 5 se conds signal device should emit one short sound signal Then signal device shall be switched to an operation mode or a sleep mode the flashing dot or a last interrogated sensor address shall appear on the screen In case of sound signal missing or wrong indi cation on the screen signal device should be deemed as ma...

Страница 8: ...king 9 2 3 5 After wiring it is required to configure signal device in accordance with a spe cific application It is necessary to check the accordance of settings recorded in configura tion data sheet for specific application and if necessary adjust the configuration Configu ration is made in accordance with cl 2 4 2 All changes must be recorded in configuration data sheet 2 3 6 Check operational ...

Страница 9: ...pressure Picture 2 3 Scrolling from one parameter to the other is executed by short pressing of the signal device right button Scrolling to next device parameter view is executed by long pressing or short pressing of the right button of signal device picture 2 4 Long press inscrease value Short press select parameter back left Long press decrease value Both buttons 1 go to settings mode 2 back und...

Страница 10: ...y carried out by the Manufacturer according to the purchase order data The reconfiguration of the signal device during operation may be needed if the purchase order data was incomplete or mismatching Signal device in configuration mode does not affect functionality of other devices in the line at the same time it neither interrogates transducer nor reacts on reaching of criti cal level Signal devi...

Страница 11: ...o exit without saving changes indica tor boards will show message no no saving End Any changes Err S SAV Back to menu Not saved Yes No Save No changes no Not saved cancelled Er tr Device not responding YES Save Saved t Wait Picture 2 7 If the saving reading calibration etc operations requires more than 1 second the screen will display t in the main field and Wait in the information field picture 2...

Страница 12: ...t d1 1 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адрес 002 Отступ от дна резерв SEtt d0 9 200м ПМП 201А Адрес 002 Отступ от дна резерв SEtt d0 9 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адрес 002 Глубина погружения SEtt d1 1 200м ПМП 201А Адре...

Страница 13: ...peration mode End End Br Picture 2 11 List of items sub items and configuration menu parameters is listed in table 8 3 Table 2 3 N o Item sub item parameter Note Desig nation Name Des ignati on Name unit of measure ment 1 SEE Not used 2 SEtt Main configurable parameters F Interrogation period s Set in accordance with 2 4 4 3 3 Br Indicator brightness 4 S SEE Table of devices set for viewing 1 n Se...

Страница 14: ...or brightness adjustment Brightness value ranges from 0 to 100 The more the Br value the more the bright ness It is recommended to set the middle brightness level value because the operation within the highest brightness values shall reduce the lifetime of OLED screen 2 4 4 2 Configuration table of viewed devices S SEE menu sub item provides adjustment of parameters set for viewing in opera tion m...

Страница 15: ...t will be flashing Set the required reaction short line event is ignored long line reaction is set Scroll to End item and exit with saving changes To delete devices from table it is required to perform the following actions Choose the record subjected for removal Change the device address to 00 Scroll to End item and exit with saving changes Notes 1 Device addresses are sorted automatically by inc...

Страница 16: ...interrogated by other signal device in the same time Warning If 0 address is used for configuration only one device can be con nected to the signaling device otherwise other devices can be reprogrammed by accident this can affect address and other settings i e only two devices with ad dress shall be in the line the signaling device and a device with unknown address 2 4 4 INDICATION OF ERRORS In ca...

Страница 17: ...depending on operating conditions 4 ROUTINE PRODUCT REPAIR 4 1 Product repair is replacement of broken parts and units it can be carried out by organization granted to do repair of explosion proof equipment Spare parts are supplied by the manufacturer 5 TRANSPORTATION AND STORAGE 5 1 Transportation conditions shall correspond to GOST 15150 69 at medium tem perature range from 50 C to 50 C Transpor...

Страница 18: ...ation conditions as to environment climatic as pects influence 1 1 2 5 1 5 2 GOST 30852 13 2002 IEC 60079 14 1996 Explosion proof electrical apparatus Part 14 Electrical installations in explosive gas atmos pheres other than mines 2 1 2 GOST 30852 16 2002 IEC 60079 17 1996 Explosion proof electrical apparatus Part 17 Inspection and maintenance of electrical installa tions in hazardous areas other ...

Страница 19: ...19 NPP SENSOR LLC RUSSIA 442965 Zarechny Penza region P O Box 737 phone fax 7 841 2 65 21 00 7 841 2 65 21 55 Corr 21 10 2019 ...

Отзывы: