Pag. 14
3. In situ adjustment instructions
SMART3G gas detectors offer a field adjustment for the Zero, Span (response to gas), 4-20mA
and alarm thresholds values.
By operating through a magnetic wand on the Hall effect sensors ENTER NEXT and ESC one
person can verify the calibration and the parameters of the gas detector. This calibration is
defined as
non intrusive
beacuse it does not require the area to be declassified or the tran-
smitter to be opened for operating.
The magnetic wand is supplied on request.
Apply the magnetic wand close to the glass cover above the hall effect sensors you need to
operate on (ENTER, NEXT, ESC).
The display has a main menu with the items listed in Table 3. In correspondence of each item
of the main menu it’s possible to enter in a submenu by pressing ENTER. The description of
the ENTER, NEXT and EXIT magnets are described in Figure 4.
D i s p l a y e d
name
Meaning
Description
PSd
Password
1234. It allows to access the keypad menu, otherwise the user
can only reset the detector or visualise its firmware version.
To modify the alarm thresholds and the hysteresis value, the
password is 5345.
ZEro
Zero
When the detector is turned on for the first time, or when
a new kit sensor head is mounted into the instrument, the
ZERO calibration is recommended.
Span
Span
The Span allows the instrument calibration and is to be exe-
cuted if the response in gas of the instrument is not correct.
To run the Span calibration, it is essential the use of a sample
gas bottle with Target Gas.
t4.20
4-20 cali-
bration
4-20 mA output calibration
THr1
Threshold 1 Displays and allows editing of the first alarm threshold
THr2
Threshold 2 Displays and allows editing of the second alarm threshold
THr3
Threshold 3 Displays and allows editing of the third alarm threshold
HYSt
Hysteresis
Displays and allows editing of hysteresis of the alarm thre-
sholds
rES
Reset
Reset of the Fault status
VEr
Version
Detector firmware version
Adr
Address
To display and set the detectors’ address on the RS485 bus
bAUd
Baudrate
Displays and allows editing of the baud rate of the serial port.
List of available values: 9600, 115200
Table 3) Description of main menù voices