Table 1.1—General Specifications
Liquid
Compensation and
Correction Factors
Temperature and pressure compensation
Meter factor compensation
Shrinkage factor compensation
Live BS&W correction
Live density correction
Dynamic oil fraction (watercut)—derived from flowing density or watercut analyzer; automatic
base density updates from flowing density measurement
Chisholm-Steven orifice meter multiphase correction for steam
Chisholm-Steven cone meter multiphase correction for steam
Flow Streams
Two integral compensated flow run inputs
Up to 20 remote flow runs via NUFLO Scanner 2000 series flow computers in local area
Scanner network
Three additional integral uncompensated pulse/frequency inputs
Bidirectional flow measurement
Up to 8 gas streams using gas chromatograph inputs or user-entered static compositions
16-point calibrations for all inputs (linear factory and multipoint meter factor calibrations also
supported); see
Table 1.6—Flow Correction Factors, page 18
for information on multipoint
meter factor calibration
Stacked differential pressure and static pressure inputs for rangeability
RTD Inputs
2 channels
100-Ω platinum RTD with 2-wire, 3-wire, or 4-wire interface
Range: –40 °C to 427 °C (–40 °F to 800 °F), excluding RTD uncertainty
Accuracy: ± 0.2 °C (0.36 °F) over sensing range at calibrated temperature
Temperature effect: ± 0.3 °C (0.54 °F) over operating range
A/D resolution: 24 bits
Sample rate: 0.1 seconds to 12 hours
Configurable shutoff for power savings when transducer warm-up period is not required
Analog Inputs
4 channels and 3 additional channels (current measurement only) configurable through Pulse/
Frequency Inputs
1 to 5 V, 0 to 5 V, 4 to 20 mA, or 0 to 20 mA (AN IN 5,6,7 are 4 to 20 mA or 0 to 20 mA only)
Accuracy: ± 0.030% of span maximum error at 25 °C (77 °F)
Temperature effect: ± 0.25% of span over operating range
Impedance: > 60 k
Ω
for 1 to 5 V input; approximately 250 Ω for 4 to 20 mA input
Transmitter voltage supply is configurable: 8.5 V to 24 V
Over-voltage protection: 30 VDC
A/D resolution: 22 bits (minimum 20 effective bits)
Linearity error: ± 0.020% max.; ± 0.010% typical
Single-ended inputs
Sample rate: 0.1 seconds to 12 hours
Four previous calibrations available stored in device
Configurable shutoff for saving power when transducer warm-up period is not required
10
Section 1
QRATE Scanner 3300 integrated control flow computer
Содержание QRATE Scanner 3300
Страница 54: ...This page intentionally left blank 48 Section 2 QRATE Scanner 3300 integrated control flow computer...
Страница 74: ...This page intentionally left blank 68 Section 4 QRATE Scanner 3300 integrated control flow computer...
Страница 78: ...This page intentionally left blank 72 Section 5 QRATE Scanner 3300 integrated control flow computer...
Страница 82: ...This page intentionally left blank 76 Section 6 QRATE Scanner 3300 integrated control flow computer...
Страница 88: ...This page intentionally left blank B 4 Appendix B QRATE Scanner 3300 integrated control flow computer...